Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop B
Sequence Number 8
Notes
Date Text
2007-04-03 10:20:52BUILDING PLAN REVIEW
 PERMIT: 06100574
 ADD: 401 CLEMATIS ST
 CONT: CATALFUMO
 TEL: (561)307-4776
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION# 6REVIEW
 ACTION: DENIED
  
 1)ONE SET OF PLANS WILL BE RETAINED FOR POSSIBLE
 SUBMITTAL TO THE STATE. PLANS INDICATE REVISION# 6
 PRINTED ON 2-19-07 BUT THE DESIGNER OF RECORD SIGNED
 AND SEALED THEM ON 2-13-07, SIX DAYS BEFORE THEY WERE
 PRINTED. WHAT IS REALLY PECULIAR THAT BOTH THE
 ARCHITECT AND STRUCTURAL ENGINEER WOULD MAKE THE SAME
 MISTAKE.......
  
 ARCHITECT'S
 61G1-16.003 USE OF SEAL.
 THE PERSONAL SEAL, SIGNATURE AND DATE OF THE ARCHITECT
 OR INTERIOR DESIGNER SHALL APPEAR ON ALL ARCHITECTURAL
 OR INTERIOR DESIGN DOCUMENTS TO BE FILED FOR PUBLIC
 RECORD AND SHALL BE CONSTRUED TO OBLIGATE HIS PARTNERS
 OR HIS CORPORATION. A CORPORATE SEAL ALONE IS
 INSUFFICIENT. DOCUMENTS SHALL BE SIGNED PERSONALLY AND
 SEALED BY THE RESPONSIBLE ARCHITECT OR INTERIOR
 DESIGNER. FINAL OFFICIAL RECORD DOCUMENTS (NOT
 TRACINGS, ETC.) SHALL BE SO SIGNED. THE SIGNING AND
 SEALING OF THE SPECIFICATION INDEX SHEETS SHALL BE
 CONSIDERED ADEQUATE. ALL DRAWING SHEETS AND PAGES SHALL
 BE SO SIGNED AND SEALED. AN ARCHITECT OR INTERIOR
 DESIGNER SHALL NOT AFFIX, OR PERMIT TO BE AFFIXED, HIS
 SEAL OR NAME TO ANY PLAN, SPECIFICATIONS, DRAWINGS, OR
 OTHER RELATED DOCUMENT WHICH WAS NOT PREPARED BY HIM OR
 UNDER HIS RESPONSIBLE SUPERVISING CONTROL AS PROVIDED
 IN RULE CHAPTER 61G1-23, F.A.C. AN ARCHITECT OR
 INTERIOR DESIGNER SHALL NOT USE HIS SEAL OR DO ANY
 OTHER ACT AS AN ARCHITECT OR INTERIOR DESIGNER UNLESS
 HOLDING AT THE TIME A CERTIFICATE OF REGISTRATION AND
 ALL REQUIRED RENEWALS THEREOF.
 SPECIFIC AUTHORITY 481.2055, 481.221 FS. LAW
 IMPLEMENTED 481.221, 481.225(1)(E), (G), (J),
 481.2251(1)(G), (H), (I) FS. HISTORY?NEW 12-23-79,
 FORMERLY 21B-16.03, AMENDED 7-27-89, FORMERLY
 21B-16.003, AMENDED 11-21-94, 4-18-00.
  
 ENGINEER'S
 61G15-23.002 SEAL, SIGNATURE AND DATE SHALL BE
 AFFIXED.
 (1) A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND
 AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS, REPORTS,
 FINAL BID DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER?S REPRESENTATIVE, OR OTHER DOCUMENTS PREPARED OR
 ISSUED BY SAID REGISTRANT AND BEING FILED FOR PUBLIC
 RECORD. THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED
 AS PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS,
 SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER. (2)
 EACH SHEET OF PLANS AND PRINTS WHICH MUST BE SEALED
 UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL BE
 SEALED, SIGNED AND DATED BY THE PROFESSIONAL ENGINEER
 IN RESPONSIBLE CHARGE. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET.
 IF PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME
 AND LICENSE NUMBER, AS WELL AS, THE NAME, ADDRESS, AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
 ENGINEERS WORKING FOR LOCAL, STATE OR FEDERAL
 GOVERNMENT AGENCIES SHALL LEGIBLY INDICATE THEIR NAME
 AND LICENSE NUMBER, AND MAY INDICATE THE NAME AND
 ADDRESS OF THE AGENCY. A COVER OR INDEX SHEET FOR
 ENGINEERING SPECIFICATIONS MAY BE USED AND THAT SHEET
 MUST BE SIGNED, SEALED AND DATED BY THOSE PROFESSIONAL
 ENGINEERS IN RESPONSIBLE CHARGE OF THE PRODUCTION AND
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX SO THAT THE USER WILL BE AWARE OF EACH
 PORTION OF THE SPECIFICATIONS FOR WHICH EACH
 PROFESSIONAL ENGINEER IS RESPONSIBLE. ENGINEERING
 REPORTS MUST BE SIGNED, SEALED AND DATED ON A SIGNATURE
 PAGE OR COVER LETTER BY EACH PROFESSIONAL ENGINEER WHO
 IS IN RESPONSIBLE CHARGE OF ANY PORTION OF THE REPORT.
 A PROFESSIONAL ENGINEER MAY ONLY SEAL AN ENGINEERING
 REPORT, PLAN, PRINT OR SPECIFICATION IF THAT
 PROFESSIONAL ENGINEER WAS IN RESPONSIBLE CHARGE OF THE
 PREPARATION AND PRODUCTION OF THE ENGINEERING DOCUMENT
 AND THE PROFESSIONAL ENGINEER HAS THE EXPERTISE IN THE
 ENGINEERING DISCIPLINE USED IN PRODUCING THE
 ENGINEERING DOCUMENT IN QUESTION.
 (3) A PROFESSIONAL ENGINEER SHOULD NOT SEAL ORIGINAL
 DOCUMENTS MADE OF MYLAR, LINEN, SEPIA OR OTHER
 MATERIALS WHICH CAN BE CHANGED BY THE ENTITY WITH WHOM
 SUCH DOCUMENT(S) ARE FILED UNLESS THE PROFESSIONAL
 ENGINEER ACCOMPANIES SUCH DOCUMENT(S) WITH A SIGNED AND
 SEALED LETTER MAKING THE RECEIVER AWARE THAT COPIES OF
 THE ORIGINAL DOCUMENT AS DESIGNED BY THE PROFESSIONAL
 ENGINEER HAVE BEEN RETAINED BY THE PROFESSIONAL
 ENGINEER AND THAT THE PROFESSIONAL ENGINEER WILL NOT BE
 RESPONSIBLE FOR ANY SUBSEQUENT CHANGES TO THE
 REPRODUCIBLE ORIGINAL DOCUMENTS.
 (4) A PROFESSIONAL ENGINEER SHOULD NOT SEAL PRELIMINARY
 PLANS WHICH ARE NOT INTENDED FOR PERMIT, CONSTRUCTION,
 OR BIDDING PURPOSES. IF A PERMITTING AGENCY REQUIRES
 THAT PRELIMINARY PLANS SUBMITTED FOR REVIEW PURPOSES BE
 SIGNED AND SEALED, THEN THE ENGINEER SHOULD CLEARLY
 NOTE SUCH LIMITATIONS ON THE FACE OF THE PLANS, BY
 USING TERMS SUCH AS ?PRELIMINARY,? ?FOR REVIEW ONLY,?
 ?NOT FOR CONSTRUCTION,? OR ANY OTHER SUITABLE STATEMENT
 WHICH DENOTES THAT THE DOCUMENTS ARE FOR DESIGN REVIEW
 ONLY AND ARE NOT INTENDED FOR PERMIT, CONSTRUCTION, OR
 BIDDING PURPOSES.
 (5) ENGINEERS WHO WISH TO SIGN AND SEAL ELECTRONICALLY
 TRANSMITTED PLANS, SPECIFICATIONS, REPORTS, FINAL BID
 DOCUMENTS, OR OTHER DOCUMENTS SHALL FOLLOW THE
 PROCEDURES SET FORTH IN RULE 61G15-23.003, F.A.C.
 SPECIFIC AUTHORITY 471.025 FS. LAW IMPLEMENTED 471.025
 FS. HISTORY?NEW 1-8-80, AMENDED 1-20-85, FORMERLY
 21H-23.02, AMENDED 5-14-86, FORMERLY 21H-23.002,
 AMENDED 11-15-94, 8-18-98, 2-3-00, 2-22-01, 2-5-04.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]