Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop P
Sequence Number 7
Notes
Date Text
2007-09-10 17:14:48REVISIONS DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT P1-1.0 CLOUD AND NUMBER ALL REVISIONS. REVISIONS
 SEEN WITH NO CLOUDS OR REVISION NUMBERS. SECTION
 106.1.3.
  
 2. SHTS P1-2.0 & P1-2.1 ROOM A2.316 SINK SHALL BE
 ACCESSIBLE. PLEASE SHOW CLEAR FLOOR SPACE AND TURNING
 AREA REQUIRED BY SECTIONS 11-4.24.5 & 11-4.2.3.--
 CLOUD AND NUMBER ALL REVISIONS. SECTION 106.1.3.
  
 3. SHT P3-20 RISERS DO NOT REFLECT THE FLOOR PLAN.--
 RISER P/2, SEE PROVISO FOR CLEANOUT DOWNSTREAM OF
 JANITOR SINK 3RD FLOOR. SEE PREVIOUS APPROVED SHEETS
 WITH COMMENT ABOUT REVISIONS.--SINK S-1 BY THE BASE
 OF RISER P/4, (RM A1.709), DOES NOT REFLECT REVISION
 #11 CHANGE.--SINK S-1 BY THE TOILET ROOM A2.705
 CONNECTS TO BOTH RISERS P/7 & P/4. PLEASE CLARIFY.--
 SINK SK-1 DOWNSTREAM OF TOILET ROOM A2.107 DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRELATE THE RISER WITH
 THE FLOOR PLANS. SECTION 106.1.1.
  
 4. SHT P3-3.0 RISER DOES NOT REFLECT THE FLOOR PLAN FOR
 THE OFFSET OF THE SINK IN THE JANITOR ROOM, NOR FOR THE
 CLEANOUT PRIOR TO THE SINK UPSTREAM OF THE EWC-1 BY THE
 JANITOR ROOM A4.105. PLEASE CORRELATE RISER AND FLOOR
 PLAN. SECTION 106.1.1.
  
 5. SHT P3-6.0 THE WATER LINES FOR THE SINK BY THE
 ELECTRIC W/H IN THE JANITOR ROOM A4.105 DO NOT REFLECT
 THE SINK LOCATION ON THE FLOOR PLAN. THE RISER SHOWS
 THEM TURNING INTO THE JANITOR ROOM, BUT THE FLOOR PLAN
 SHOWS THE SINK IN THE HALLWAY OUTSIDE THE JANITOR ROOM.
 THE WATER RISER FOR THE TOILET ROOM A2.105 DOES NOT
 REFLECT THE PIPING SHOWN ON SHT P2.30 FOR THE SINK IN
 ROOM A2.730. PLEASE CORRELATE RISER AND FLOOR PLANS.
 SECTION 106.1.1.
  
 EVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]