2007-09-10 17:14:48 | REVISIONS DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| 1. SHT P1-1.0 CLOUD AND NUMBER ALL REVISIONS. REVISIONS |
| SEEN WITH NO CLOUDS OR REVISION NUMBERS. SECTION |
| 106.1.3. |
| |
| 2. SHTS P1-2.0 & P1-2.1 ROOM A2.316 SINK SHALL BE |
| ACCESSIBLE. PLEASE SHOW CLEAR FLOOR SPACE AND TURNING |
| AREA REQUIRED BY SECTIONS 11-4.24.5 & 11-4.2.3.-- |
| CLOUD AND NUMBER ALL REVISIONS. SECTION 106.1.3. |
| |
| 3. SHT P3-20 RISERS DO NOT REFLECT THE FLOOR PLAN.-- |
| RISER P/2, SEE PROVISO FOR CLEANOUT DOWNSTREAM OF |
| JANITOR SINK 3RD FLOOR. SEE PREVIOUS APPROVED SHEETS |
| WITH COMMENT ABOUT REVISIONS.--SINK S-1 BY THE BASE |
| OF RISER P/4, (RM A1.709), DOES NOT REFLECT REVISION |
| #11 CHANGE.--SINK S-1 BY THE TOILET ROOM A2.705 |
| CONNECTS TO BOTH RISERS P/7 & P/4. PLEASE CLARIFY.-- |
| SINK SK-1 DOWNSTREAM OF TOILET ROOM A2.107 DOES NOT |
| REFLECT THE FLOOR PLAN. PLEASE CORRELATE THE RISER WITH |
| THE FLOOR PLANS. SECTION 106.1.1. |
| |
| 4. SHT P3-3.0 RISER DOES NOT REFLECT THE FLOOR PLAN FOR |
| THE OFFSET OF THE SINK IN THE JANITOR ROOM, NOR FOR THE |
| CLEANOUT PRIOR TO THE SINK UPSTREAM OF THE EWC-1 BY THE |
| JANITOR ROOM A4.105. PLEASE CORRELATE RISER AND FLOOR |
| PLAN. SECTION 106.1.1. |
| |
| 5. SHT P3-6.0 THE WATER LINES FOR THE SINK BY THE |
| ELECTRIC W/H IN THE JANITOR ROOM A4.105 DO NOT REFLECT |
| THE SINK LOCATION ON THE FLOOR PLAN. THE RISER SHOWS |
| THEM TURNING INTO THE JANITOR ROOM, BUT THE FLOOR PLAN |
| SHOWS THE SINK IN THE HALLWAY OUTSIDE THE JANITOR ROOM. |
| THE WATER RISER FOR THE TOILET ROOM A2.105 DOES NOT |
| REFLECT THE PIPING SHOWN ON SHT P2.30 FOR THE SINK IN |
| ROOM A2.730. PLEASE CORRELATE RISER AND FLOOR PLANS. |
| SECTION 106.1.1. |
| |
| EVIEW BY KEN STEVENS |