Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop E
Sequence Number 7
Notes
Date Text
2007-04-14 11:48:58** UNSAT **
  
 ** PLEASE SEE THIS REVIEW IS FOR REVISION #8 AS
 SUBMITTED TO ADDRESS *PROVISO* FROM ISSUANCE OF
 PERMIT**
  
 ** PLEASE SEE THAT MOST OF THE *PROVISO* NOTES HAVE
 BEEN ADDRESSED HOWEVER DUE TO CHANGES IN REVISION #7
 AND SOME ITEMS WHICH STILL NEED TO BE REVISITED ON
 PROVISO, PLEASE SEE THE COMMENTS BELOW.
  
 1) NOTE: PLEASE KNOW THAT DUE TO THE CLEARANCE
 REQUIREMENTS FOR THE GENERATOR WHICH WAS COMMENTED ON
 IN REVISION FOR ARCHITECTURAL DATED 3/1/07 THE PLANS AS
 SUBMITTED DO NOT INDICATE THE MINIMUM CLEARANCES FOR
 THE UNIT PER NEC 110.26 AND THAT WHICH IS SET-FORTH
 FROM THE MANUFACTURES SPECIFICATIONS.
 110.3, 90.7
  
 2) NOTE: PLEASE CLARIFY THE CONTROL DEVICE FOR ELEVATOR
 ROOM PER 1-6.1. OCCUPANCY DEVICE REQUIRED.
 13-415.1.ABC.1.1
  
 3) NOTE: PLEASE SEE PANEL 1-HEE WHICH NEEDS TO INDICATE
 AND LABEL THE ROOMS IN WHICH THEY FEED AND THE
 DESIGNATION FOR THE * ELEVATOR MACHINE RM LTS*.
 408.4, 620.23
  
 4) NOTE: PLEASE SEE THE PROVISO WHICH WAS TO REVISE
 CIRCUITS FOR THE ELEVATOR ROOMS, WHICH WAS TO INCLUDE
 THE LIGHTING AND RECEPTACLES, YET ONLY THE REVISED
 LIGHTING PLANS WERE SUBMITTED. PLEASE SEE THE SHEETS
 FOR THESE ROOMS SHOULD HAVE ALSO BEEN SUBMITTED.
 620.23
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE THE ELECTRICAL RISER DIAGRAM AND
 NOTES FOR REVISION #7 WHICH AHS NOT BEEN CHANGED.
 PLEASE SEE THAT THE ATS SWITCHES WHICH HAVE BEEN
 REVISED ON OTHER DOCUMENTS HAVE NOT BEEN REVISED ON
 RISER DIAGRAM.
 PLEASE SEE NOTES DATED 3/24/07
 PLEASE BE SURE TO REVISE POWER PLANS, PANEL SCHEDULES,
 LOADS ETC.
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE CLARIFY STAIR 11 LIGHTS AND LOCATIONS
 FOR THE PHOTO-METRIC LEVELS. PREVIOUS PLANS INDICATE
 LIGHTING IN THE STAIR AREA ABOVE THE STAIRS AND SOME
 SHEETS INDICATE THESE AT THE UPPER LEVEL AND LOWER
 LEVEL WHICH DO NOT SEEM THEY WOULD PROVIDE THE NEEDED.
 PLEASE SEE THE PHOTO-METRIC PLANS WHICH DO INDICATE THE
 LIGHT FIXTURE ABOVE STAIRS AND IF THIS IS HOW THE
 LIGHTING LEVELS ARE DERIVED THEN THE PLACEMENT OF THE
 LIGHTING FIXTURES ON THE LIGHTING PLANS WOULD NOT WORK
 AND PROVIDE THE LIGHTING.
 LS 101 7.8.1.3, 7.9.2.2
 PLEASE SEE NEXT COMMENT.
  
 7) NOTE: PLEASE SEE THAT LIGHTING PLANS AND
 PHOTO-METRIC PLANS STILL NEED COORDINATION OG LIGHTING
 FIXTURES. PLEASE SEE THAT THE SAME FIXTURES WHICH ARE
 INDICATED AS EM TYPE FIXTURES ON LIGHTING PLANS ARE NOT
 THE SAME ONES IN ALL LOCATIONS ON PHOTO-METRIC PLANS.
 PLEASE KNOW AS BASED ON COMMENT ABOVE AND THE NEXT
 COMMENT FOR NIGHT LIGHTING AND EMERGENCY LIGHTING,
 THESE WILL ALL NEED TO BE ADJUSTED AND REVISED TO
 CORRELATE.
 FBC 106.1.2
 LS 101 7.8, 7.9
  
 8) NOTE: PLEASE KNOW THAT A MEETING WILL BE REQUIRED TO
 GO OVER PLANS AND PROPOSED *NIGHT-LIGHTS* AS SHOWN ON
 PLANS. PLEASE KNOW THAT EMERGENCY FIXTURES ARE REQUIRED
 FOR EGRESS PATHS UNDER NORMAL AND EMERGENCY HOWEVER THE
 NUMBER OF FIXTURES BEING PROPOSED FOR NIGHT LIGHTS
 WHICH WILL BE LEFT *ON* 24/7/365 DOES NOT TAKE INTO
 CONSIDERATION OF THE REQUIREMENT OF THE FLORIDA ENERGY
 CODE.
 PLEASE SEE THESECTION BELOW WHICH IS TAKEN DIRECTLY
 FROM NFPA-101. *7.8.1.2.2* WHICH IS LOCATED ALONG WITH
 TEXT FOR SECTION OF 7.8.
 PLEASE KNOW THAT DUE TO THE COMPLEXITY OF THE EGRESS
 LIGHTING, THE ACTUAL DESIGNATED EGRESS PATH/PATHS NEEDS
 TO BE DETERMINED AS A STARTING POINT FOR FINDING THE
 MINIMUM REQUIRED.
 PLEASE KNOW THAT THIS OFFICE HAS CONTACTED THE FLORIDA
 BUILDING COMMISSION TO GO OVER THE REQUIREMENTS OF
 CHAPTER 13 AND THE INTENT.CONSIDERATION NEEDS TO BE
 GIVEN FOR THE INTENT AND AT THE SAME TIME MEETING THE
 REQUIRED LIFER SAFETY FOR NORMAL AND EMERGENCY EGRESS
 LIGHTING DURING OCCUPANCY OF BUILDING.
  
 *7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY
 BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTER 11
 THROUGH CHAPTER 42. FOR THE PURPOSES OF THIS
 REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES, CORRIDORS, RAMPS, ESCALATORS, AND
 PASSAGEWAYS LEADING TO AN EXIT. FOR THE PURPOSES OF
 THIS REQUIREMENT, EXIT DISCHARGE SHALL INCLUDE ONLY
 DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS, WALKWAYS, AND EXIT PASSAGEWAYS LEADING TO A
 PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF
 OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE
 FOR USE, UNLESS OTHERWISE PROVIDED IN 7.8.1.2.2.
 7.8.1.2.1 ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH
 LOCATIONS AND FOR SUCH PERIODS OF TIME AS ARE NECESSARY
 TO MAINTAIN THE ILLUMINATION TO THE MINIMUM CRITERIA
 VALUES HEREIN SPECIFIED.
 7.8.1.2.2 AUTOMATIC, MOTION SENSOR?TYPE LIGHTING
 SWITCHES SHALL BE PERMITTED WITHIN THE MEANS OF EGRESS,
 PROVIDED THAT THE SWITCH CONTROLLERS ARE EQUIPPED FOR
 FAIL-SAFE OPERATION, THE ILLUMINATION TIMERS ARE SET
 FOR MINIMUM 15-MINUTE DURATION, AND THE MOTION SENSOR
 IS ACTIVATED BY ANY OCCUPANT MOVEMENT IN THE AREA
 SERVED BY THE LIGHTING UNITS.
  
 ** PLEASE SEE ONE SET OF THE PLANS WHICH WAS SUBMITTED
 HAS REDLINED LOCATIONS WHICH ARE ALSO HIGH-LIGHTED FOR
 AREAS WHICH NEED TO BE GONE OVER.
 ** PLEASE CONTACT THIS OFFICE ONCE THE MINIMUM
 LIFE-SAFETY DESIGNATED EGRESS PATHS ARE DONE TO SET UP
 A MEETING TO GO OVER PLANS AND SCENARIOS.
  
 ** PLEASE KNOW THAT DUE TO THE COMPLEXITY OF THE NOTES
 ABOVE AND THE TIME CONSIDERATION WHICH WILL BE GIVEN TO
 ADDRESS THE ABOVE, THE ORIGINAL DATE OF 60DAYS HAS BEEN
 EXTENDED AS DISCUSSED WITH THE ENGINEER OF RECORD.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-04-14 09:59:47REVIEW IN PROGRESS


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved