Date |
Text |
2007-04-14 11:48:58 | ** UNSAT ** |
| |
| ** PLEASE SEE THIS REVIEW IS FOR REVISION #8 AS |
| SUBMITTED TO ADDRESS *PROVISO* FROM ISSUANCE OF |
| PERMIT** |
| |
| ** PLEASE SEE THAT MOST OF THE *PROVISO* NOTES HAVE |
| BEEN ADDRESSED HOWEVER DUE TO CHANGES IN REVISION #7 |
| AND SOME ITEMS WHICH STILL NEED TO BE REVISITED ON |
| PROVISO, PLEASE SEE THE COMMENTS BELOW. |
| |
| 1) NOTE: PLEASE KNOW THAT DUE TO THE CLEARANCE |
| REQUIREMENTS FOR THE GENERATOR WHICH WAS COMMENTED ON |
| IN REVISION FOR ARCHITECTURAL DATED 3/1/07 THE PLANS AS |
| SUBMITTED DO NOT INDICATE THE MINIMUM CLEARANCES FOR |
| THE UNIT PER NEC 110.26 AND THAT WHICH IS SET-FORTH |
| FROM THE MANUFACTURES SPECIFICATIONS. |
| 110.3, 90.7 |
| |
| 2) NOTE: PLEASE CLARIFY THE CONTROL DEVICE FOR ELEVATOR |
| ROOM PER 1-6.1. OCCUPANCY DEVICE REQUIRED. |
| 13-415.1.ABC.1.1 |
| |
| 3) NOTE: PLEASE SEE PANEL 1-HEE WHICH NEEDS TO INDICATE |
| AND LABEL THE ROOMS IN WHICH THEY FEED AND THE |
| DESIGNATION FOR THE * ELEVATOR MACHINE RM LTS*. |
| 408.4, 620.23 |
| |
| 4) NOTE: PLEASE SEE THE PROVISO WHICH WAS TO REVISE |
| CIRCUITS FOR THE ELEVATOR ROOMS, WHICH WAS TO INCLUDE |
| THE LIGHTING AND RECEPTACLES, YET ONLY THE REVISED |
| LIGHTING PLANS WERE SUBMITTED. PLEASE SEE THE SHEETS |
| FOR THESE ROOMS SHOULD HAVE ALSO BEEN SUBMITTED. |
| 620.23 |
| FBC 106.1.2 |
| |
| 5) NOTE: PLEASE SEE THE ELECTRICAL RISER DIAGRAM AND |
| NOTES FOR REVISION #7 WHICH AHS NOT BEEN CHANGED. |
| PLEASE SEE THAT THE ATS SWITCHES WHICH HAVE BEEN |
| REVISED ON OTHER DOCUMENTS HAVE NOT BEEN REVISED ON |
| RISER DIAGRAM. |
| PLEASE SEE NOTES DATED 3/24/07 |
| PLEASE BE SURE TO REVISE POWER PLANS, PANEL SCHEDULES, |
| LOADS ETC. |
| FBC 106.3.5.1.2, 106.1.2 |
| |
| 6) NOTE: PLEASE CLARIFY STAIR 11 LIGHTS AND LOCATIONS |
| FOR THE PHOTO-METRIC LEVELS. PREVIOUS PLANS INDICATE |
| LIGHTING IN THE STAIR AREA ABOVE THE STAIRS AND SOME |
| SHEETS INDICATE THESE AT THE UPPER LEVEL AND LOWER |
| LEVEL WHICH DO NOT SEEM THEY WOULD PROVIDE THE NEEDED. |
| PLEASE SEE THE PHOTO-METRIC PLANS WHICH DO INDICATE THE |
| LIGHT FIXTURE ABOVE STAIRS AND IF THIS IS HOW THE |
| LIGHTING LEVELS ARE DERIVED THEN THE PLACEMENT OF THE |
| LIGHTING FIXTURES ON THE LIGHTING PLANS WOULD NOT WORK |
| AND PROVIDE THE LIGHTING. |
| LS 101 7.8.1.3, 7.9.2.2 |
| PLEASE SEE NEXT COMMENT. |
| |
| 7) NOTE: PLEASE SEE THAT LIGHTING PLANS AND |
| PHOTO-METRIC PLANS STILL NEED COORDINATION OG LIGHTING |
| FIXTURES. PLEASE SEE THAT THE SAME FIXTURES WHICH ARE |
| INDICATED AS EM TYPE FIXTURES ON LIGHTING PLANS ARE NOT |
| THE SAME ONES IN ALL LOCATIONS ON PHOTO-METRIC PLANS. |
| PLEASE KNOW AS BASED ON COMMENT ABOVE AND THE NEXT |
| COMMENT FOR NIGHT LIGHTING AND EMERGENCY LIGHTING, |
| THESE WILL ALL NEED TO BE ADJUSTED AND REVISED TO |
| CORRELATE. |
| FBC 106.1.2 |
| LS 101 7.8, 7.9 |
| |
| 8) NOTE: PLEASE KNOW THAT A MEETING WILL BE REQUIRED TO |
| GO OVER PLANS AND PROPOSED *NIGHT-LIGHTS* AS SHOWN ON |
| PLANS. PLEASE KNOW THAT EMERGENCY FIXTURES ARE REQUIRED |
| FOR EGRESS PATHS UNDER NORMAL AND EMERGENCY HOWEVER THE |
| NUMBER OF FIXTURES BEING PROPOSED FOR NIGHT LIGHTS |
| WHICH WILL BE LEFT *ON* 24/7/365 DOES NOT TAKE INTO |
| CONSIDERATION OF THE REQUIREMENT OF THE FLORIDA ENERGY |
| CODE. |
| PLEASE SEE THESECTION BELOW WHICH IS TAKEN DIRECTLY |
| FROM NFPA-101. *7.8.1.2.2* WHICH IS LOCATED ALONG WITH |
| TEXT FOR SECTION OF 7.8. |
| PLEASE KNOW THAT DUE TO THE COMPLEXITY OF THE EGRESS |
| LIGHTING, THE ACTUAL DESIGNATED EGRESS PATH/PATHS NEEDS |
| TO BE DETERMINED AS A STARTING POINT FOR FINDING THE |
| MINIMUM REQUIRED. |
| PLEASE KNOW THAT THIS OFFICE HAS CONTACTED THE FLORIDA |
| BUILDING COMMISSION TO GO OVER THE REQUIREMENTS OF |
| CHAPTER 13 AND THE INTENT.CONSIDERATION NEEDS TO BE |
| GIVEN FOR THE INTENT AND AT THE SAME TIME MEETING THE |
| REQUIRED LIFER SAFETY FOR NORMAL AND EMERGENCY EGRESS |
| LIGHTING DURING OCCUPANCY OF BUILDING. |
| |
| *7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY |
| BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTER 11 |
| THROUGH CHAPTER 42. FOR THE PURPOSES OF THIS |
| REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED |
| STAIRS, AISLES, CORRIDORS, RAMPS, ESCALATORS, AND |
| PASSAGEWAYS LEADING TO AN EXIT. FOR THE PURPOSES OF |
| THIS REQUIREMENT, EXIT DISCHARGE SHALL INCLUDE ONLY |
| DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS, |
| ESCALATORS, WALKWAYS, AND EXIT PASSAGEWAYS LEADING TO A |
| PUBLIC WAY. |
| 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF |
| OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE |
| FOR USE, UNLESS OTHERWISE PROVIDED IN 7.8.1.2.2. |
| 7.8.1.2.1 ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH |
| LOCATIONS AND FOR SUCH PERIODS OF TIME AS ARE NECESSARY |
| TO MAINTAIN THE ILLUMINATION TO THE MINIMUM CRITERIA |
| VALUES HEREIN SPECIFIED. |
| 7.8.1.2.2 AUTOMATIC, MOTION SENSOR?TYPE LIGHTING |
| SWITCHES SHALL BE PERMITTED WITHIN THE MEANS OF EGRESS, |
| PROVIDED THAT THE SWITCH CONTROLLERS ARE EQUIPPED FOR |
| FAIL-SAFE OPERATION, THE ILLUMINATION TIMERS ARE SET |
| FOR MINIMUM 15-MINUTE DURATION, AND THE MOTION SENSOR |
| IS ACTIVATED BY ANY OCCUPANT MOVEMENT IN THE AREA |
| SERVED BY THE LIGHTING UNITS. |
| |
| ** PLEASE SEE ONE SET OF THE PLANS WHICH WAS SUBMITTED |
| HAS REDLINED LOCATIONS WHICH ARE ALSO HIGH-LIGHTED FOR |
| AREAS WHICH NEED TO BE GONE OVER. |
| ** PLEASE CONTACT THIS OFFICE ONCE THE MINIMUM |
| LIFE-SAFETY DESIGNATED EGRESS PATHS ARE DONE TO SET UP |
| A MEETING TO GO OVER PLANS AND SCENARIOS. |
| |
| ** PLEASE KNOW THAT DUE TO THE COMPLEXITY OF THE NOTES |
| ABOVE AND THE TIME CONSIDERATION WHICH WILL BE GIVEN TO |
| ADDRESS THE ABOVE, THE ORIGINAL DATE OF 60DAYS HAS BEEN |
| EXTENDED AS DISCUSSED WITH THE ENGINEER OF RECORD. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2007-04-14 09:59:47 | REVIEW IN PROGRESS |