Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop P
Sequence Number 6
Notes
Date Text
2007-06-15 10:31:31DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P1.1.3U THE STORAGE ROOM B1.101 SHOWS SANITARY
 PIPING. PLEASE INDICATE THE TYPE OF FIXTURE AND THE
 TYPE OF DRAINAGE FITTING FOR THE FIXTURE.A REVISION
 IS REQUIRED FOR THE SANITARY RISER DIAGRAM TO REFLECT
 THE CHANGES TO THE SANITARY SYSTEM. SECTION 106.1.1.
  
 2. SHT P1-6.0 THE TRENCH DRAIN AT THE BOTTOM OF THE
 LOWER RAMP HAS BEEN DELETED, BUT IS STILL SHOWN ON THE
 STORM RISER DIAGRAM ON SHT P3.7.0. PLEASE CORRELATE
 RISER AND FLOOR PLAN LAYOUT.
  
 2. SHT P1-6.0SHOWS 6" AREA DRAINS, BUT THE RISER
 DIAGRAM ON SHT P3-7.0 SHOWS 8" AREA DRAINS. PLEASE
 CORRELATE RISER AND FLOOR PLAN.
  
 3. SHT P1-6.0 AREA DRAINS HAVE BEEN DELETED ON THE FLAT
 LEVELS OF THE ROOF AND LOWER ROOF SECTION. PLEASE
 INDICATE IF THE SLAB WILL BE SLOPED TO THE AREA DRAINS
 NOW SHOW AT THE BOTTOM OF THE RAMPS.
  
 4. SHT P1-6.0 THE AREA DRAIN IS SHOWN AT THE BOTTOM OF
 THE SECOND RAMP, (NORTH END), ON THE FLOOR PLAN, BUT
 THE RISER DIAGRAM SHOWS THE AREA DRAIN ON THE ROOF
 ABOVE THE RAMP. PLEASE CLARIFY & CORRELATE RISER AND
 FLOOR PLAN. SECTION 106.1.1.
  
 5. REVISIONS ARE REQUIRED FOR SHTS P1-2.3, P1.3.3,
 P1-4.3, & P1-6.0SHOWING THE NEW AREA DRAINS AND
 SHOWING THE CHANGED LOCATION OF THE RWL RISER #6.
  
 REVIEW BY KEN STEVENS