2007-04-11 09:38:08 | 1. ON PAGE E5-1.1 GA PLANS MAKE REFERENCE TO A FIVE |
| HUNDRED GALLON, DOUBLE WALL SUB-BASE FUEL TANK. PLEASE |
| INDICATE WHAT UL LISTING CAN BE EXPECTED FOR THIS FUEL |
| TANK. PLEASE PROVIDE PRODUCT APPROVALS AND INFORMATION |
| TO THIS OFFICE REGARDING THIS FUEL TANK. |
| |
| 2. CO SENSORS ARE ILLUSTRATED ON THE DRAWINGS. PLEASE |
| PROVIDE DETAILS ON THESE DEVICES. THESE DEVICES ARE TO |
| BE UL LISTED AND PLEASE INDICATE IF THESE DEVICES WILL |
| BE FACTORY OR FIELD SET. MOUNTING HEIGHTS, AREA OF |
| COVERAGE, AND TESTING PROCEDURES SHALL BE DOCUMENTED TO |
| THIS OFFICE. WHAT POWERS THESE DEVICES AND ARE THEY |
| EQUIPPED WITH PROVISIONS SHOULD LOSS OF POWER OCCURS. |
| IF BATTERY POWER EXISTS, HOW LONG CAN THEY BE EXPECTED |
| TO OPERATE. ALSO PLEASE INDICATE WHAT SET POINTS THESE |
| DETECTORS WILL BE SET AT. WHAT PARTS PER MILLION WILL |
| ACTIVATE THESE SENSORS. |
| |
| 3. A VISUAL REPRESENTATION OF THE FIREFIGHTERS SMOKE |
| CONTROL PANEL NEEDS TO BE ILLUSTRATED AT TIME OF SHOP |
| DRAWING SUBMITTAL. THE SMOKE CONTROL PANEL SHALL |
| DISPLAY A GRAPHIC REPRESENTATION OF THE BUILDING AND |
| THE SYSTEM TO INCLUDE HAND, ON, AND AUTO CONTROLS. |
| |
| 4. PLEASE PROVIDE THIS OFFICE IN WRITING WHEN THE |
| TEMPORARY STANDPIPE SYSTEM WILL BE INSTALLED AT THE |
| PARKING GARAGE AND THE FUTURE BUILDING. CERTAIN CODE |
| REQUIREMENTS MANDATE THIER INSTALLATION WHEN THEY REACH |
| CERTAIN HEIGHT OR FLOOR ARRANGEMENTS. |
| |
| |