2007-03-24 17:49:26 | ** UNSAT ** |
| |
| |
| ** GARAGEREVISION #7** |
| |
| 1) NOTE: PLEASE SEE THE RISER HAS NOW CHANGED ATS-3 TO |
| A 400AMP UNIT, HOWEVER PLEASE SEE THE LEFT SIDE OF |
| ATS-3 AS IT IS STILL SHOWN AS A 260AMP UNIT. |
| PLEASE ALSO SUBMIT THE REVISED MANUFACTURES SPECS/CUT |
| SHEETS FOR THE NEW PROPOSED UNIT.(110.3, 90.7) |
| PLEASE COORDINATE ALONG WITH ELECTRICAL SHEET FOR MAIN |
| ELECTRICAL ROOM WHICH WAS NOT SUBMITTED YET THE |
| DESIGNATION ON SHEET 4-1.0 CONTAINS THE 260AMP UNIT. |
| FBC 106.1.2 |
| |
| 2) NOTE: PLEASE SEE PLANS INDICATE A REVISION TO THE |
| LOAD CALCULATIONS ON THE MAIN BUILDING LOAD SUMMARY; |
| HOWEVER THE LOADS DID NOT CHANGE FROM THE PERMITTED SET |
| OF PLANS. A CLOUD AND A REV #7 IS SHOWN, BUT NOTHING |
| WAS REVISED. |
| PLEASE SEE THAT THE LOADS OF THESE NEW MOTORS NEED TO |
| SHOW *LARGEST* AT 125% AND PLEASE KNOW THAT AS THESE |
| MOTOR LOADS MAY BE RUN FOR THREE OR MORE HOURS THE |
| LOADS SHALL BE SHOWN AT 125%. |
| 215.3, 230.42, 220, 430 ETC. |
| PLEASE REVISE CALCULATIONS. |
| PLEASE ALSO KEEP IN MIND THE *PROVISO* WHICH WAS GIVEN |
| WHICH NEEDED LOAD CALCULATIONS TO BE REVISED AND BASED |
| ON THESE SHEETS FOR REVISION #7, LOADS WERE NOT |
| REVISED. |
| IF REVISION #6 HAS NOT HAD THIS CHANGE BASED ON |
| *PROVISO* PLEASE KNOW IT MAY BE THAT REVISED SHEETS ARE |
| INSERTED BEFORE REVIEW OF REVISION #6 IS DONE? |
| |
| 3) NOTE: PLEASE SUBMIT THE REVISED GENERATOR SPECS FOR |
| THE INCREASED SIZE INCLUDING FUEL CONSUMPTION FOR ADDED |
| SIZE AND INCREASED LOADS. RECORD PLANS NEED TO REVISE |
| FUEL CONSUMPTION AND LOADS. |
| NFPA-110 |
| NFPA 70 110.3, 90.7. |
| FBC 106.1.2 |
| |
| 4) NOTE: THE EXHAUST FANS ARE LABELED EF-1 FOR FIRST |
| FLOOR AND THEN EF-2 FOR SECOND FLOOR, EF-3 FOR THIRD |
| FLOOR AND THEN FOURTH AND FIFTH LEVELS ARE ALSO LABELED |
| EF-3 FOR THESE FANS ON OTHER LEVELS??? |
| PLEASE PROVIDE SPECIFIC DESIGNATIONS FOR EACH EXHAUST |
| FAN. PLEASE KNOW IF THEY ARE ON LEVEL 2M, THEN LABEL |
| EACH ON LEVEL 2 AS THERE ARE MULTIPLE FANS PER FLOOR. |
| PLEASE LABEL FANS ON OTHER LEVELS AS THE FANS ON THOSE |
| SPECIFIC LEVELS. |
| EF-4A NE CORNER?, EF-4B NE CORNER ?ORANY OTHER |
| SPECIFIC DESIGNATION OF CHOICE. |
| PLEASE SEE 408.4 AS THIS REQUIRES THE SPECIFIC |
| DESIGNATIONS AND NOT TO BE GENERIC. PLEAS CALL IF THERE |
| ANY QUESTIONS. |
| ** PLEASE BE SURE TO ADJUST THE DESIGNATIONS ON THE |
| BUILDING/ MECHANICAL PLANS ALSO. |
| |
| 5) NOTE: PLEASE SEE FBC 132-413.1ABC.1 FOR VOLTAGE |
| DROP. THE MCC SHOWS #12AWG FOR THE UPPER FLOORS AND THE |
| DISTANCE SEEMS TO EXCEED THE % PERMITTED. |
| PLEASE PROVIDE VOLTAGE DROP CALCULATIONS FOR THESE OR |
| INCREASE CONDUCTOR SIZES FOR LONGER RUNS. THIS IS NOT |
| FOR LOWER LEVELS WITH LESS DISTANCE. |
| |
| 6) NOTE: PLEASE BE SURE TO ADJUST THE GENERATOR |
| SPECIFICATIONS ON ANY OTHER SHEETS WHICH CONTAIN THE |
| DESIGNATIONS. |
| FBC 106.1.2 |
| |
| 7) NOTE: PLEASE SUBMIT LV DETAIL FOR WIRING OF THE |
| CARBON MONOXIDE DEVICES/SYSTEM. |
| CAN BE ON THE SAME GARAGE SHEETS AND A TYPICAL DETAIL. |
| FBC 106.3.5.1.2 |
| |
| ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES( |
| BUILD/MECH/FIRE) WHICH MAY CONTAIN COMMENTS THAT MAY |
| AFFECT ELECTRICAL SHEETS. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |