2007-03-01 09:13:56BUILDING PLAN REVIEW
 PERMIT: 06100574
 ADD: 401 CLEMATIS ST
 CONT: CATALFUMO
 TEL: (561)282-8265
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2005 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION # 6REVIEW
 ACTION: DENIED
  
 SHEETS: A1-GA.1,
 A1-GA.2
 A1-GA.3
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) SHEETS A1-GA.1, A1-GA.2 & A1-GA.3,
 ALL SHOW EXHAUST FANS BUT THE HEIGTH ABOVE THE FINISH
 FLOOR SLAB HAS NOT BEEN PROVIDED OR A CUT SECTION
 THAT WOULD PROVIDE AT WHAT ELEVATION THE BOTTOM OF THE
 ENCLOSURE WILL BE ABOVE THE FINISH FLOOR SLAB.
 11-4.4.1 GENERAL.
 OBJECTS PROJECTING FROM WALLS (FOR EXAMPLE, TELEPHONES)
 WITH THEIR LEADING EDGES BETWEEN 27 INCHES AND 80
 INCHES (685 MM AND 2030 MM) ABOVE THE FINISHED FLOOR
 SHALL PROTRUDE NO MORE THAN 4 INCHES (102 MM) INTO
 WALKS, HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES [SEE
 FIGURE 11-8 (A)]. OBJECTS MOUNTED WITH THEIR LEADING
 EDGES AT OR BELOW 27 INCHES (685 MM) ABOVE THE FINISHED
 FLOOR MAY PROTRUDE ANY AMOUNT [SEE FIGURE 11-8 (A) AND
 FIGURE 11-8 (B)]. FREE-STANDING OBJECTS MOUNTED ON
 POSTS OR PYLONS MAY OVERHANG 12 INCHES (305 MM) MAXIMUM
 FROM 27 INCHES TO 80 INCHES (685 MM TO 2030 MM) ABOVE
 THE GROUND OR FINISHED FLOOR [SEE FIGURE 11-8 (C) AND
 FIGURE 11-8 (D)]. PROTRUDING OBJECTS SHALL NOT REDUCE
 THE CLEAR WIDTH OF AN ACCESSIBLE ROUTE OR MANEUVERING
 SPACE [SEE FIGURE 11-8 (E)].
  
 11-4.4.2 HEADROOM.
 WALKS, HALLS, CORRIDORS, PASSAGEWAYS, AISLES, OR OTHER
 CIRCULATION SPACES SHALL HAVE 80 INCHES (2030 MM)
 MINIMUM CLEAR HEAD ROOM [SEE FIGURE 11-8 (A)]. IF
 VERTICAL CLEARANCE OF AN AREA ADJOINING AN ACCESSIBLE
 ROUTE IS REDUCED TO LESS THAN 80 INCHES (2032 MM)
 (NOMINAL DIMENSION), A BARRIER TO WARN BLIND OR
 VISUALLY-IMPAIRED PERSONS SHALL BE PROVIDED [SEE FIGURE
 11-8 (C-1)].
  
 3)PLEASE SEE ELECTRICAL COMMENTS FOR SHEET A1-GA.3
 CONCERNING THE LOCATION OF THE FENCE AND THE LOCATION
 OF GENERATOT TO GENERATOR ON THE ROOF TOP OF THE
 PARKING GARAGE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  