Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop E
Sequence Number 5
Notes
Date Text
2007-03-01 07:32:49**** UNSAT ****
  
 1) NOTE: PLEASE SEE THE ARCHITECTURAL REVISIONS
 SUBMITTED ARE SHOWING NEW FENCING AND CLEARANCES AROUND
 THE CURRENT GENERATOR UNIT AND THE FUTURE GENERATOR
 UNITS WHICH DO NOT MEET EGRESS REQUIREMENTS AND MINIMUM
 CLEARANCE REQUIREMENTS FOR THE NEC 110.26 AND NFPA-110.
 PLEASE OBTAIN INFORMATION ON THE ELECTRICAL BREAKER
 PANEL LOCATIONS, PLEASE SEE ONLY ONE PATH IS BEING
 SHOWN AND THE PATH OF EGRESS DOES NOT MINIMUM WIDTHS.
 PLEASE SEE THAT DEPENDING ON EQUIPMENT AND NUMEROUS
 OTHER FACTORS THE FENCING AND WALLS SHOWN ARE WAY UNDER
 THE MINIMUM AREA REQUIRED ABOUT THE ELECTRICAL
 EQUIPMENT.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6717
 [email protected]