Plan Review Notes For Permit 06100574 |
Permit Number |
06100574 |
|
Review Stop |
E |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2007-03-01 07:32:49 | **** UNSAT **** | | | | 1) NOTE: PLEASE SEE THE ARCHITECTURAL REVISIONS | | SUBMITTED ARE SHOWING NEW FENCING AND CLEARANCES AROUND | | THE CURRENT GENERATOR UNIT AND THE FUTURE GENERATOR | | UNITS WHICH DO NOT MEET EGRESS REQUIREMENTS AND MINIMUM | | CLEARANCE REQUIREMENTS FOR THE NEC 110.26 AND NFPA-110. | | PLEASE OBTAIN INFORMATION ON THE ELECTRICAL BREAKER | | PANEL LOCATIONS, PLEASE SEE ONLY ONE PATH IS BEING | | SHOWN AND THE PATH OF EGRESS DOES NOT MINIMUM WIDTHS. | | PLEASE SEE THAT DEPENDING ON EQUIPMENT AND NUMEROUS | | OTHER FACTORS THE FENCING AND WALLS SHOWN ARE WAY UNDER | | THE MINIMUM AREA REQUIRED ABOUT THE ELECTRICAL | | EQUIPMENT. | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN | | CONTACTING THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | 561-805-6717 | | [email protected] |
|