Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop E
Sequence Number 43
Notes
Date Text
2009-06-10 11:26:23** DENIED REVIEW**
  
 ** PLANS AND FINAL REVISIONS NEED TO BE SUBMITTED WITH
 COORDINATION OF ALL DRAWINGS. THESE ARE THE FINAL
 RECORD PLANS TO BE ON FILE. ALL ITEMS NEED TO BE
 COORDINATED AND CORRECTED.
  
 * THE FOLLOWING WILL BE SOME EXAMPLES ONLY OF AREAS IN
 WHICH THERE ARE DISCREPANCIES ON PLANS.
  
 **** THIS REVIEW IS NOT BASED ON THE COMPARISON OF
 PLANS WITH THE FIELD OR JOBSITE LOCATION.
  
 **** ONE OF THE REDLINED SET OF PLANS WHICH WAS USED IN
 REVIEW WILL REMAIN IN THIS OFFICE. IN NUMEROUS PREVIOUS
 REVIEWS AND MEETINGS IT WAS STATED TO CALL TO GO OVER
 ANY QUESTIONS ON COMMENTS WITH RESPECT TO PLANS OR
 PROPOSED DESIGN. IT IS STRONGLY RECOMMENDED THAT A
 MEETING BE HELD TO GO OVER ANY COMMENTS WHICH MAY NOT
 BE CLEAR OR UNDERSTOOD IN ANY WAY. THIS MEETING SHOULD
 BE HELD WITH REPRESENTATIVES FROM THE GENERAL
 CONTRACTOR, ELECTRICAL CONTRACTOR, ARCHITECTURAL FIRM,
 ENGINEERING FIRM AND THE CITY OF WEST PALM BEACH.
  
 **** THE LIGHTING CONTROL PANEL WILL BE NOTED AS LCP IN
 MANY OF THE COMMENTS BELOW.
  
 **** MANY OF THE COMMENTS BELOW WILL BE GENERAL TO THE
 SECTIONS OF CODES FOR LIGHTING CONTROLS, PANEL SCHEDULE
 AND RECORD PLANS.
 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4. 408.4, 106.5,
 106.1.1, 106.1.2 ETC
 MORE SPECIFIC CODES WILL BE NOTED IN OTHER LOCATIONS.
 ** PLEASE BE SURE TO SEE 408.4 WHICH REQUIRE ALL
 LOCATIONS TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH
 THEY FEED. STATING *RECEPTACLES* OR * LIGHTING* IS NOT
 SPECIFIC FOR PANEL SCHEDULES OR PANEL SCHEDULES ON
 RECORD PLANS.
  
 1) NOTE: PLEASE SUBMIT AN UPDATE LAYOUT OF ALL
 ELECTRICAL ROOMS WHICH EQUIPMENT WAS ADDED. FOR EXAMPLE
 THERE ARE NEW TRANSFORMERS AND PANELS FOR SOME
 LOCATIONS THROUGH OUT THE PLANS. THE TRANSFORMER FOR
 PANEL A FOR EXAMPLE COULD NOT BE LOCATED ON PLAN.
 SEE OTHER NOTES BELOW WITH RESPECT TO OTHER PANELS AND
 COORDINATION OF PLANS.110.26, FBC 106.1.2,106.1.1,
 106.5 FOR COORDINATION OF RECORD DOCUMENTS.
 THE MAIN ELECTRICAL ROOM IS ONE EXAMPLE OF EQUIPMENT
 BEING ADDED WHICH IS NOT PART OF THE REVISED PLANS. THE
 RECORD PLANS DO NOT INCLUDE OTHER WORK WHICH HAS BEEN
 DONE.
  
 2) NOTE: PLEASE SUBMIT PANEL SCHEDULE FOR NEW PANEL *A*
 WHICH IS NOW SHOWN ON PLANS. PLEASE BE SURE TO
 COORDINATE. 408.4
  
 3) NOTE: PLEASE SHOW LOCATION OF THE TRANSFORMER FOR
 THE SAME PANEL *A*. 450.9, 450.13, 110.26 ETC. AS THIS
 IS NOT SHOWN CODE COMPLIANCE CAN NOT BE DETERMINED.
  
 4) NOTE: PLEASE REMOVE ALL WORK IN AREAS FOR WHICH THE
 *PHOTO MUSEUM* WILL BE LOCATED. ONE EXAMPLE IS THE 2ND
 FLOOR WHICH STILL INDICATES LIGHTING AND OTHER ITEMS
 WHICH ARE NOW NO LONGER PART OF THE BASE BUILDING.
 PLEASE TAKE A LOOK AT THEIR TENANT SPACE PLANS AND
 REMOVE LIGHTS AS NEEDED.
 PLEASE ALSO COMPLETE LATEST REVISED PLANS FOR COMMON
 AREAS WHICH ARE TO BE FED FROM BASE BUILDING AND ARE
 NOT PART OF THE TENANT SPACE.
 THE RISER STILL INDICATES THE 800A BREAKER FOR THE
 PHOTO-MUSEUM EVEN THOUGH THE SPACE IS FED FROM A
 SEPARATE SERVICE.
 SEE D2.106
  
 5) NOTE: RECEPTACLES IN MAIN MECHANICAL ROOM DO NOT
 CONNECT TO ANY CIRCUIT.
  
 6) NOTE: PLEASE SEE 2-HA-18 WHICH IS SHOWN AS EXTERIOR
 LIGHTS ON PLANS YET THE LCP IS NOT COMPLETE OR LISTS
 THE CIRCUIT. THE PANEL SCHEDULE FOR HA-18 IS SHOWN AS
 SPARE EVEN THOUGH IT IS ON PLANS.
  
 7) NOTE: PLEASE SEE 2-HC-18 IS NOTED ON PLANS YET NOT
 ON LCP.
  
 8) NOTE: PLEASE SEE 2-HA-10 WHICH IS NOT ON LCP.
  
 9) NOTE: PLEASE SEE 2-HB-8 WHICH IS SHOWN AS EXTERIOR
 LIGHTS ON PANEL SCHEDULE HOWEVER THE LCP STATES THIS IS
 FOR LIGHTING INSIDE IN OPEN WORK AREA.
  
 10) NOTE: PLEASE SEE 2-HA-19 WHICH IS NOT LISTED ON LCP
 HOWEVER ON PLANS AND PANEL SCHEDULE.
  
 11) NOTE: PLEASE SEE FIRST LEVEL COMMON AREAS WHICH DO
 NOT INDICATE ANY LIGHTING, LIGHTING CONTROLS, AND
 CIRCUITS ETC WHICH ARE NOT PART OF THE PHOTO MUSEUM
 SPACE.
 13-415.1.ABC.1.1,1.2, .1.3.
  
 12) NOTE: PLEASE COMPLETE PLANS WITH NEW LIGHTING FOR
 COMMON AREAS OUTSIDE PHOTO MUSEUM SPACE. PLEASE SEE
 NFPA-101 7.8 AND 7.9 FOR COMPLETE LIGHTING IN COMMON
 AREAS FOR LIFE SAFETY. OTHER ITEMS SUCH AS HORNS,
 STROBES, HORN/STROBE FOR COMPLIANCE WITH NFPA-72 AND
 COMPLIANCE WITH FBC 11-4.27.4 SHALL ALSO BE MET. FIRE
 ALARM PLANS HAVE NOT BEEN UPDATED AND COORDINATED TO
 DATE OF THIS REVIEW.
  
 13) NOTE: PLEASE SEE EE FIXTURE ON C2-2.2 WHICH DOES
 NOT INDICATE ANY CIRCUIT OR CONTROL. THE PREVIOUS PLANS
 DID SHOW CIRCUITING AND CONTROLS.
  
 14) NOTE: WHERE ARE THE CONTROLS FOR 1-GHA18-20?
  
 15) NOTE: PLANS SHOW CIRCUIT 1-GLA-30 AS A DEDICATED
 CIRCUIT FOR SODA MACHINE HOWEVER BASED ON THE PLANS
 THIS SAME CIRCUIT IS SHOWN IN MORE THAN ONE LOCATION.
 ONE LOCATION IS THE STORAGE ROOM IN GARAGE WHICH
 INDICATES THE SAME CIRCUIT.
  
 16) NOTE: PLEASE SEE CIRCUIT 1LB3-21 AND 24 WHICH BOTH
 INDICATE CIRCUITS TO COMMON AREA RECEPTACLES IN SPACE
 A1.115. ARE NOT ONE OF THESE AT LEAST A DEDICATED
 CIRCUIT FOR SODA MACHINE?
  
 17) NOTE: PLEASE SEE CIRCUIT 1-GLEA-2 WHICH INDICATES
 PLANS A J-BOX YET THIS IS CIRCUITED AS A FA NAC.
  
 18) NOTE: PLEASE SEE 1-LC2-31 ON PLANS SHOWN AS CIRCUIT
 TO ROOM C1.101 HOWEVER PANEL SCHEDULE INDICATES
 C1.301??
  
 19) NOTE: PLEASE SEE POWER PLANS FOR EXAMPLE E1-1.1
 WHICH DOES NOT SHOW THE NEW PANELS 1TV AND 1LS-1. THESE
 ARE SHOWN ON E7-7.0 YET NOT COORDINATED.
 THE PANEL SCHEDULE FOR EACH OF THESE INDICATED ROOM
 LOCATIONS HOWEVER PANEL NOT AS ON PLANS. ONE OF THESE
 WOULD BE 1TV WHICH STATES THE LOCATION AS A1.406 YET
 SHEET E7-7.0 SHOWS THIS IN ANOTHER LOCATION NEXT TO
 1LS-1.
  
 20) NOTE: PLEASE SEE 1TV WHICH IS SHOWN AS 200AMP MLO
 ON SCHEDULE AND ON RISER THIS IS SHOWN AS 150AMP. ??
  
 21) NOTE: PLEASE SEE 1LD2-13 ON PANEL SCHEDULE WHICH
 STATES THIS IS FOR AHU-1 PUMP. YET PLANS INDICATE THIS
 FOR GENERAL RECEPTACLE CIRCUIT FEEDING OTHER AREAS
 BESIDES PUMP?
  
 22) NOTE: PLEASE SEE 2-LA-3-3 ON PANEL WHICH STATES
 THIS FEEDING LOCATION A2.213 YET THE PLANS SHOWS THE
 LOCATION IN FOYER SINGLE LOCATION A2.003.
  
 23) NOTE: PLEASE SEE 2LD-2-3 WHICH IS NOT SPECIFIC TO
 ROOMS AND LOCATIONS IN WHICH THIS CIRCUIT FEEDS. PANEL
 SCHEDULE DOES NOT LIST LOCATIONS AS FOUND ON PLANS.
  
 24) NOTE: PLEASE SEE 2LD2-6 WHICH IS SHOWN AS SPARE ON
 PANEL SCHEDULE HOWEVER THE PLANS ON E1-2.2 STILL HAS
 CIRCUIT SHOWN.
  
 25) NOTE: PLEASE CORRELATE ALL POWER AND RELEVANT
 CHANGES ON POWER PLANS E1-1.1 WITH E7-7.0.
 THERE ARE NUMEROUS ITEMS
  
 26) NOTE: PLEASE SEE 1LA3-10 WHICH PER PANEL SCHEDULE
 IT STATES COMMISSION OFFICE HOWEVER PLEASE SEE SHEET
 E7-7.0 WHICH INDICATES THIS AS A DEDICATE RECEPTACLE IN
 THE FLAGLER GALLERY.
  
 27) NOTE: PLEASE SEE 1LA3-18 WHICH DOES LIST THIS AS
 A1-308 ON PLANS HOWEVER PLEASE SEE E7-7.0
  
 28) NOTE: PLEASE SEE 3LD2-9 NEEDS TO BE SPECIFIC TO
 ROOMS AND AREAS IN WHICH THEY FEED. THE PLANS INDICATE
 MANY MORE LOCATIONS THAN WHAT IS LISTED ON PANEL
 SCHEDULE.
  
 29) NOTE: PLEASE SEE 3LC-19 NEED TO BE SPECIFIC TO ALL
 ROOMS AND AREAS IN WHICH THEY FEED.
  
 30) NOTE: PLEASE SEE 3LD3-21 ON PANEL SCHEDULE WHICH
 INDICATES THIS AS A SPARE CIRCUIT HOWEVER THE PLANS
 STILL SHOW THIS CIRCUIT.
  
 31) NOTE: PLEASE SEE 3LD3-6 WHICH THE PANEL SCHEDULE
 INDICATES THIS AS A SPARE YET THE PLANS STILL INDICATES
 THIS AS A CIRCUIT BEING USED.
  
 32) NOTE: PLEASE SEE CIRCUITS 4LA3-5 AND -24 WHICH ARE
 BOTH SHOWN TIED TOGETHER ON PLANS. WHY ARE THESE NOT
 SEPARATED?
  
 33) NOTE: PLEASE SEE MULTIPLE SETS OF FURNITURE WORK
 STATIONS WHICH SHOW THE SAME CIRCUITING 4LB3-26,28,30.
 PLEASE SEE 220.14(I) FOR LOADS PER YOKE. PLEASE PROVIDE
 INFORMATION ON HOW MANY RECEPTACLES ARE ON THE CIRCUITS
 AS SHOWN FOR KNOWN LOADS. THIS WAS GONE OVER IN
 ORIGINAL REVIEW EVEN BEFORE PERMIT ISSUANCE FOR KNOWN
 LOADS AND LOADS FIGURED AT 180VA. THE REVIEW COMMENTS
 CAN BE PROVIDED ALONG WITH E-MAILS IN WHICH QUESTIONS
 WERE RAISED.
  
 34) NOTE: PLEASE SEE MULTIPLE SETS OF FURNITURE WORK
 STATIONS WHICH SHOW THE SAME CIRCUITING 4LA3-15,17,19.
 PLEASE SEE 220.14(I) FOR LOADS PER YOKE. PLEASE PROVIDE
 INFORMATION ON HOW MANY RECEPTACLES ARE ON THE CIRCUITS
 AS SHOWN FOR KNOWN LOADS.
 THIS WAS GONE OVER IN ORIGINAL REVIEW EVEN BEFORE
 PERMIT ISSUANCE FOR KNOWN LOADS AND LOADS FIGURED AT
 180VA. THE REVIEW COMMENTS CAN BE PROVIDED ALONG WITH
 E-MAILS IN WHICH QUESTIONS WERE RAISED.
  
 35) NOTE: PLANS STILL STATE IT EQUIPMENT TO BE DONE BY
 OTHERS. HOWEVER THE RECORD SET OF PLANS NEED TO NOW
 SHOW ALL OF THIS WORK BEING COMPLETED. PLEASE COMPLETE
 THE IT PANEL SCHEDULE. THE SCHEDULE DOES INDICATE THE
 CIRCUITING FOR AC EQUIPMENT ETC HOWEVER NO OTHER
 EQUIPMENT IS SHOWN BEING FED FROM THIS PANEL.
 WHERE IS ALL OF THE OTHER EQUIPMENT BEING FED FROM?
 CIRCUITS? LOADS? ETC
 408.4,310.16,240.3,220, ETC
 645 (ALL)
  
 36) NOTE: PLEASE PROVIDE INFORMATION ON THE EPO AT THE
 DOOR FOR IT ROOM.
 PLEASE SEE 645.10 FOR THE REQUIRED DISCONNECTING MEANS
 TO ALL EQUIPMENT INCLUDING AC EQUIPMENT.
 THERE IS A CIRCUIT ON 1LED-27 FOR SHUNT TRIP CIRCUIT
 HOWEVER THE IT PANEL OR FEED TO IT PANEL DOES NOT
 INDICATE ANY SHUNT TRIP TYPE MAIN BREAKER OR BRANCH
 BREAKER. THE RISER DOES NOT INDICATE A SHUNT FOR ANY OF
 THE MAIN BREAKERS OR FEEDERS.
 PLEASE PROVIDE INFORMATION AND DETAIL FOR THIS.
  
 37) NOTE: PLEASE SEE 4LEB-10 WHICH IS SHOWN AS SPARE ON
 PANEL SCHEDULE YET THE PLANS STILL INDICATE THIS
 CIRCUIT.
  
 38) NOTE: PLEASE SEE 4IT 15,17 ON PANEL SCHEDULE THIS
 IS SHOWN TO RM A4.416 YET THE PLANS DO NOT INDICATE
 THIS.
  
 39) NOTE: PLEASE SEE 4LD2- 5 STATES RECEPTACLES IN ROOM
 4-106 HOWEVER THIS IS SHOWN ON PLANS FEEDING OTHER
 AREAS ALSO.
  
 40) NOTE: PLEASE SEE 4LC2-13 WHICH IS SHOWN ON PANEL TO
 ROOM A4-201 HOWEVER ON PLANS THIS IS LOCATED AT THE
 OTHER END OF THE FLOOR.
  
 41) NOTE: PLEASE SEE 4LC3-9 AND 25 WHICH IS SHOWN TO
 ROOM/AREA C4.202 YET THE PANEL SCHEDULE INDICATES ONE
 OF THESE FOR THIS LOCATION AND ONE OF THESE FOR A
 DIFFERENT LOCATION. THERE IS ALSO THE FACT THE J-BOX IS
 ALSO FED FROM THE ONE OF THESE CIRCUITS WHICH IS #25.
 IS THIS CORRECT FOR THE J-BOX?
  
 42) NOTE: PLEASE SEE 4LD3-3, 22 AS BOTH ARE SHOWN ON
 PLANS, HOWEVER PLEASE SEE THAT THE PANEL SCHEDULE FOR
 22 IS BLANK.
  
 43) NOTE: PLEASE SEE MULTIPLE SETS OF FURNITURE WORK
 STATIONS WHICH SHOW THE SAME CIRCUITING SUCH AS
 5LA3-21, 23. PLEASE SEE 220.14(I) FOR LOADS PER YOKE.
 PLEASE PROVIDE INFORMATION ON HOW MANY RECEPTACLES ARE
 ON THE CIRCUITS AS SHOWN FOR KNOWN LOADS. THIS WAS GONE
 OVER IN ORIGINAL REVIEW EVEN BEFORE PERMIT ISSUANCE FOR
 KNOWN LOADS AND LOADS FIGURED AT 180VA. THE REVIEW
 COMMENTS CAN BE PROVIDED ALONG WITH E-MAILS IN WHICH
 QUESTIONS WERE RAISED.
  
 44) NOTE: PLEASE SEE 5LA2- 34 WHICH ON THE PANEL
 SCHEDULE IT STATES ELECTRICAL ROOM A5.107 RECEPTACLES.
 HOWEVER THE PLANS SHOW A COMPLETELY DIFFERENT CIRCUIT
 WHICH FEEDS MANY OTHER LOCATIONS. THE CIRCUIT ON PLANS
 FOR THIS ROOM IS NOT #34. SEE THE FOLLOWING COMMENT.
  
 45) NOTE: PLEASE SEE 5LA2-3 ON PANEL SCHEDULE WHICH
 STATES CORRIDOR LIGHTING. HOWEVER ON PLANS THIS FEEDS
 ROOM ABOVE WHICH IS A5.107, 5.103,5.104,203 ETC
  
 46) NOTE: PLEASE SEE A1.014 ON PLANS SHOWS HA-1 HOWEVER
 THE DESIGNATION ON PANEL SCHEDULE IS NOT THE SAME.
 SHOWS A DIFFERENT ROOM.
  
 47) NOTE: PLEASE SEE 1HA-12 ON PLANS AND PANEL SCHEDULE
 HOWEVER THIS IS NOT PART OF THE LCP.
  
 48) NOTE: PLEASE SEE 410.8 A-D FOR MINIMUM LIGHTING
 FIXTURE CLEARANCES FROM COMBUSTIBLES IN CLOSETS WITH
 SHELVING. PLEASE SEE STORAGE CLOSETS A1.612,613.14.
 PLEASE PROVIDE EXACT SHELVING DIMENSION ON PLANS SO
 THAT THE CLEARANCES CAN BE DETERMINED.
  
 49) NOTE: PLEASE SEE 1HA-2 WHICH THE PLANS , THE PANEL
 SCHEDULE AND THE LCP DO NOT CORRELATE. THE CIRCUITING
 ON PLANS SHOWS ONE LOCATION/ROOM WHICH IS THE GALLERY
 A1.306 YET THE PANEL STATES THIS CIRCUIT IS FOR
 EXTERIOR FIXTURES. THE LCP DOES NOT INDICATE ANY OF
 THESE.
  
 50) NOTE: PLEASE REVISE FIXTURE SCHEDULE AND SUBMIT.
 FIXTURES FOR EXISTING LOCATION AND REVISED LOCATIONS ON
 PLANS CAN NOT BE DETERMINED AS CODE COMPLIANT WITH THE
 EXISTING REVISED CALCULATIONS PER 13-415.2.
  
 51) NOTE: PLEASE SHOW LOCATIONS OF REQUIRED OVER RIDES
 ON THE 3RD FLOOR EAST END OF LIBRARY. REVISION 17
 DELETED THE REQUIRED OVER RIDES BASED ON
 FURNITURE/SHELVING LAYOUT. ALL REVISED PLANS UP TO THIS
 LATEST REVISION STILL INDICATE EACH OF THE CIRCUITS
 WILL GO TO OVER RIDE SWITCHES HOWEVER NEW LOCATIONS
 WERE NOT SHOWN.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 OF THE FBC. LOCATION
 REQUIRES THE OCCUPANT TO SEE ALL LIGHTING WHICH IS
 BEING OVER RIDDEN OR MEET EXCEPTIONS.
  
 52) NOTE: PLEASE UPDATE ALL LCP. MANY OF THESE DO NOT
 LIST THE CIRCUITS ON THE PANEL SCHEDULES OR THE
 LOCATIONS LISTED ARE NOT CORRECT.
  
 53) NOTE: PLEASE SEE 1HC-19 AS THIS IS ON PLAN AND
 SCHEDULE HOWEVER NOT ON LCP.
  
 54) NOTE: PLEASE SEE LOBBY D1.003 WHERE ARE THE LIGHTS
 WHICH IS NOT PART OF THE PHOTO MUSEUM? FBC CHAPTER 10,
 NFPA- 101 7.8, 7.9.
 NEC CHAPTERS 2,3,4, GIVEN AS GENERAL SECTIONS.
 PLANS ARE BLANK.
  
 55) NOTE: PLEASE SEE C1.102 AS THERE IS NO CIRCUIT
 LISTED OR SHOWN FOR LIGHTING. WHERE DOES THIS
 INTERCONNECT AND WITH WHICH CIRCUIT?
  
 56) NOTE: PLEASE SEE 2HA-12 WHICH IS NOT SPECIFIC TO
 ROOMS AND AREAS.
  
 57) NOTE: PLEASE SEE 2HA-19 WHICH IS ON PLANS, ON PANEL
 SCHEDULE HOWEVER LCP IS BLANK AND DOES NOT INDICATE.
  
 58) NOTE: PLEASE SEE A2.210 AND .211 ROOMS. WHERE DO
 THE LIGHTS IN THESE TWO ROOMS CONNECT? THE PLANS APPEAR
 TO MAYBE CONNECT TO 2HA-47 HOWEVER BASED ON THE PANEL
 SCHEDULE THESE TWO ROOMS ARE NOT LISTED.
  
 59) NOTE: PLEASE SEE 3HA-16 WHICH IS SHOWN ON PLANS,
 YET THERE IS NOTHING ON PANEL SCHEDULE OR LCP.
  
 60) NOTE: PLEASE SEE 3HA-6 STATES ON THE PANEL SCHEDULE
 THIS FEEDS A3.009 AND A3.402 YET THE PLANS INDICATE
 A3.402 BEING FED FROM 3HA-8. PLEASE SEE OTHER LOCATIONS
 NOT SPECIFIC.
  
 61) NOTE: PLEASE 3HA-8 WHICH IS NOT SPECIFIC.
  
 62) NOTE: PLEASE COMPLETE PLANS WITH CIRCUITING, LOADS
 AND LIGHTING FOR STAGE AREA LIGHTING. PLANS SHOW *TO BE
 BY OTHERS* HOWEVER THAT WAS WHEN NONE OF THAT
 INFORMATION WAS KNOWN. THIS IS THE END OF THE BUILDING
 ALL OF THE LIGHTING, CIRCUITING, LOADS ETC ARE KNOWN AT
 THIS TIME WHICH NEEDS TO BE COMPLETE ON PLANS.
 220,13-415.1.ABC.1.1, .1.3 ETC
  
 63) NOTE: PLEASE SEE AREAS C3.110,.109,0309 ETC. THE
 NORMAL LIGHTING IN THIS AREA DOES NOT HAVE ANY CIRCUIT
 NOTED OR SHOWN.
  
 64) NOTE: PLEASE SEE E2-4.1, LIGHTS IN CORRIDOR A4.009
 WHICH DOES NOT INDICATE ANY CIRCUITING FOR NORMAL
 LIGHTING??
  
 65) NOTE: PLEASE SEE 4HC-12 WHICH IS LISTED ON THE LCP
 HOWEVER NOT ON PANEL SCHEDULE.
  
 66) NOTE: PLEASE SEE 4HC-2 WHICH IS ON SCHEDULE FOR
 LIGHTING IN ELEVATOR LOBBY 5 AND 6; HOWEVER THIS SAME
 LOBBY AREA DOES NOT HAVE ANY CIRCUIT FOR THE LIGHTING
 ON PLANS. IN FACT THE LIGHTING ON PLANS IS ALL SHOWN AS
 EMERGENCY CIRCUITED LIGHTING HOWEVER NO CIRCUIT OR
 CONNECTION TO OTHER CIRCUITS IS SHOWN.
 THE CIRCUIT 4HC-2 ON PLANS IS ONLY FEEDING THE C4.105
 ROOM AND ALSO THE TWO BATHROOMS C4.102,.103 WHICH DOES
 NOT COORDINATE WITH THE PANEL SCHEDULE.
  
 67) NOTE: PLEASE SEE 4HC-10 WHICH IS ON PANEL SCHEDULE
 HOWEVER ON LCP.
  
 68) NOTE: PLEASE SEE 5HA-3 WHICH IS LISTED ON THE LCP
 HOWEVER IT IS NOT ON THE PANEL SCHEDULE. ** PLEASE SEE
 THIS SHEET OF PLANS. E2-5.1, GO OVER PLANS. SEE
 COMMENTS BELOW.
  
 69) NOTE: PLEASE SEE 5HA-17 WHICH STATES * OPEN WORK
 AREA A5.404 HOWEVER ON THE PLANS THIS IS COMPLETELY
 SEPARATE. A5.112,.104,.103.
  
 70) NOTE: PLEASE SEE AREAS OF NORMAL LIGHTING A5.507,
 .506, .504,.501,.528,.503,.505,.508 ETC WHICH DO NOT
 SHOW ANY CIRCUITING ON PLANS.
  
 71) NOTE: PLEASE SEE 5HB-5 WHICH IS SHOWN ON PLANS, YET
 THIS IS SHOWN AS A SPARE ON PANEL SCHEDULE.
  
 72) NOTE: FEE BALANCE OF $1160.00 IS DUE BEFORE PICKING
 UP PLANS AND RESUBMITTING NEW REVISIONS.
  
  
 **** THIS IS NOT AN EXHAUSTED LIST OF ALL POSSIBLE
 ITEMS. THESE HAVE BEEN GIVEN AS EXAMPLES ONLY! THESE
 ARE NOT ALL ITEMS.
  
  
  
  
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  