2009-06-10 11:26:23 | ** DENIED REVIEW** |
| |
| ** PLANS AND FINAL REVISIONS NEED TO BE SUBMITTED WITH |
| COORDINATION OF ALL DRAWINGS. THESE ARE THE FINAL |
| RECORD PLANS TO BE ON FILE. ALL ITEMS NEED TO BE |
| COORDINATED AND CORRECTED. |
| |
| * THE FOLLOWING WILL BE SOME EXAMPLES ONLY OF AREAS IN |
| WHICH THERE ARE DISCREPANCIES ON PLANS. |
| |
| **** THIS REVIEW IS NOT BASED ON THE COMPARISON OF |
| PLANS WITH THE FIELD OR JOBSITE LOCATION. |
| |
| **** ONE OF THE REDLINED SET OF PLANS WHICH WAS USED IN |
| REVIEW WILL REMAIN IN THIS OFFICE. IN NUMEROUS PREVIOUS |
| REVIEWS AND MEETINGS IT WAS STATED TO CALL TO GO OVER |
| ANY QUESTIONS ON COMMENTS WITH RESPECT TO PLANS OR |
| PROPOSED DESIGN. IT IS STRONGLY RECOMMENDED THAT A |
| MEETING BE HELD TO GO OVER ANY COMMENTS WHICH MAY NOT |
| BE CLEAR OR UNDERSTOOD IN ANY WAY. THIS MEETING SHOULD |
| BE HELD WITH REPRESENTATIVES FROM THE GENERAL |
| CONTRACTOR, ELECTRICAL CONTRACTOR, ARCHITECTURAL FIRM, |
| ENGINEERING FIRM AND THE CITY OF WEST PALM BEACH. |
| |
| **** THE LIGHTING CONTROL PANEL WILL BE NOTED AS LCP IN |
| MANY OF THE COMMENTS BELOW. |
| |
| **** MANY OF THE COMMENTS BELOW WILL BE GENERAL TO THE |
| SECTIONS OF CODES FOR LIGHTING CONTROLS, PANEL SCHEDULE |
| AND RECORD PLANS. |
| 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4. 408.4, 106.5, |
| 106.1.1, 106.1.2 ETC |
| MORE SPECIFIC CODES WILL BE NOTED IN OTHER LOCATIONS. |
| ** PLEASE BE SURE TO SEE 408.4 WHICH REQUIRE ALL |
| LOCATIONS TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH |
| THEY FEED. STATING *RECEPTACLES* OR * LIGHTING* IS NOT |
| SPECIFIC FOR PANEL SCHEDULES OR PANEL SCHEDULES ON |
| RECORD PLANS. |
| |
| 1) NOTE: PLEASE SUBMIT AN UPDATE LAYOUT OF ALL |
| ELECTRICAL ROOMS WHICH EQUIPMENT WAS ADDED. FOR EXAMPLE |
| THERE ARE NEW TRANSFORMERS AND PANELS FOR SOME |
| LOCATIONS THROUGH OUT THE PLANS. THE TRANSFORMER FOR |
| PANEL A FOR EXAMPLE COULD NOT BE LOCATED ON PLAN. |
| SEE OTHER NOTES BELOW WITH RESPECT TO OTHER PANELS AND |
| COORDINATION OF PLANS.110.26, FBC 106.1.2,106.1.1, |
| 106.5 FOR COORDINATION OF RECORD DOCUMENTS. |
| THE MAIN ELECTRICAL ROOM IS ONE EXAMPLE OF EQUIPMENT |
| BEING ADDED WHICH IS NOT PART OF THE REVISED PLANS. THE |
| RECORD PLANS DO NOT INCLUDE OTHER WORK WHICH HAS BEEN |
| DONE. |
| |
| 2) NOTE: PLEASE SUBMIT PANEL SCHEDULE FOR NEW PANEL *A* |
| WHICH IS NOW SHOWN ON PLANS. PLEASE BE SURE TO |
| COORDINATE. 408.4 |
| |
| 3) NOTE: PLEASE SHOW LOCATION OF THE TRANSFORMER FOR |
| THE SAME PANEL *A*. 450.9, 450.13, 110.26 ETC. AS THIS |
| IS NOT SHOWN CODE COMPLIANCE CAN NOT BE DETERMINED. |
| |
| 4) NOTE: PLEASE REMOVE ALL WORK IN AREAS FOR WHICH THE |
| *PHOTO MUSEUM* WILL BE LOCATED. ONE EXAMPLE IS THE 2ND |
| FLOOR WHICH STILL INDICATES LIGHTING AND OTHER ITEMS |
| WHICH ARE NOW NO LONGER PART OF THE BASE BUILDING. |
| PLEASE TAKE A LOOK AT THEIR TENANT SPACE PLANS AND |
| REMOVE LIGHTS AS NEEDED. |
| PLEASE ALSO COMPLETE LATEST REVISED PLANS FOR COMMON |
| AREAS WHICH ARE TO BE FED FROM BASE BUILDING AND ARE |
| NOT PART OF THE TENANT SPACE. |
| THE RISER STILL INDICATES THE 800A BREAKER FOR THE |
| PHOTO-MUSEUM EVEN THOUGH THE SPACE IS FED FROM A |
| SEPARATE SERVICE. |
| SEE D2.106 |
| |
| 5) NOTE: RECEPTACLES IN MAIN MECHANICAL ROOM DO NOT |
| CONNECT TO ANY CIRCUIT. |
| |
| 6) NOTE: PLEASE SEE 2-HA-18 WHICH IS SHOWN AS EXTERIOR |
| LIGHTS ON PLANS YET THE LCP IS NOT COMPLETE OR LISTS |
| THE CIRCUIT. THE PANEL SCHEDULE FOR HA-18 IS SHOWN AS |
| SPARE EVEN THOUGH IT IS ON PLANS. |
| |
| 7) NOTE: PLEASE SEE 2-HC-18 IS NOTED ON PLANS YET NOT |
| ON LCP. |
| |
| 8) NOTE: PLEASE SEE 2-HA-10 WHICH IS NOT ON LCP. |
| |
| 9) NOTE: PLEASE SEE 2-HB-8 WHICH IS SHOWN AS EXTERIOR |
| LIGHTS ON PANEL SCHEDULE HOWEVER THE LCP STATES THIS IS |
| FOR LIGHTING INSIDE IN OPEN WORK AREA. |
| |
| 10) NOTE: PLEASE SEE 2-HA-19 WHICH IS NOT LISTED ON LCP |
| HOWEVER ON PLANS AND PANEL SCHEDULE. |
| |
| 11) NOTE: PLEASE SEE FIRST LEVEL COMMON AREAS WHICH DO |
| NOT INDICATE ANY LIGHTING, LIGHTING CONTROLS, AND |
| CIRCUITS ETC WHICH ARE NOT PART OF THE PHOTO MUSEUM |
| SPACE. |
| 13-415.1.ABC.1.1,1.2, .1.3. |
| |
| 12) NOTE: PLEASE COMPLETE PLANS WITH NEW LIGHTING FOR |
| COMMON AREAS OUTSIDE PHOTO MUSEUM SPACE. PLEASE SEE |
| NFPA-101 7.8 AND 7.9 FOR COMPLETE LIGHTING IN COMMON |
| AREAS FOR LIFE SAFETY. OTHER ITEMS SUCH AS HORNS, |
| STROBES, HORN/STROBE FOR COMPLIANCE WITH NFPA-72 AND |
| COMPLIANCE WITH FBC 11-4.27.4 SHALL ALSO BE MET. FIRE |
| ALARM PLANS HAVE NOT BEEN UPDATED AND COORDINATED TO |
| DATE OF THIS REVIEW. |
| |
| 13) NOTE: PLEASE SEE EE FIXTURE ON C2-2.2 WHICH DOES |
| NOT INDICATE ANY CIRCUIT OR CONTROL. THE PREVIOUS PLANS |
| DID SHOW CIRCUITING AND CONTROLS. |
| |
| 14) NOTE: WHERE ARE THE CONTROLS FOR 1-GHA18-20? |
| |
| 15) NOTE: PLANS SHOW CIRCUIT 1-GLA-30 AS A DEDICATED |
| CIRCUIT FOR SODA MACHINE HOWEVER BASED ON THE PLANS |
| THIS SAME CIRCUIT IS SHOWN IN MORE THAN ONE LOCATION. |
| ONE LOCATION IS THE STORAGE ROOM IN GARAGE WHICH |
| INDICATES THE SAME CIRCUIT. |
| |
| 16) NOTE: PLEASE SEE CIRCUIT 1LB3-21 AND 24 WHICH BOTH |
| INDICATE CIRCUITS TO COMMON AREA RECEPTACLES IN SPACE |
| A1.115. ARE NOT ONE OF THESE AT LEAST A DEDICATED |
| CIRCUIT FOR SODA MACHINE? |
| |
| 17) NOTE: PLEASE SEE CIRCUIT 1-GLEA-2 WHICH INDICATES |
| PLANS A J-BOX YET THIS IS CIRCUITED AS A FA NAC. |
| |
| 18) NOTE: PLEASE SEE 1-LC2-31 ON PLANS SHOWN AS CIRCUIT |
| TO ROOM C1.101 HOWEVER PANEL SCHEDULE INDICATES |
| C1.301?? |
| |
| 19) NOTE: PLEASE SEE POWER PLANS FOR EXAMPLE E1-1.1 |
| WHICH DOES NOT SHOW THE NEW PANELS 1TV AND 1LS-1. THESE |
| ARE SHOWN ON E7-7.0 YET NOT COORDINATED. |
| THE PANEL SCHEDULE FOR EACH OF THESE INDICATED ROOM |
| LOCATIONS HOWEVER PANEL NOT AS ON PLANS. ONE OF THESE |
| WOULD BE 1TV WHICH STATES THE LOCATION AS A1.406 YET |
| SHEET E7-7.0 SHOWS THIS IN ANOTHER LOCATION NEXT TO |
| 1LS-1. |
| |
| 20) NOTE: PLEASE SEE 1TV WHICH IS SHOWN AS 200AMP MLO |
| ON SCHEDULE AND ON RISER THIS IS SHOWN AS 150AMP. ?? |
| |
| 21) NOTE: PLEASE SEE 1LD2-13 ON PANEL SCHEDULE WHICH |
| STATES THIS IS FOR AHU-1 PUMP. YET PLANS INDICATE THIS |
| FOR GENERAL RECEPTACLE CIRCUIT FEEDING OTHER AREAS |
| BESIDES PUMP? |
| |
| 22) NOTE: PLEASE SEE 2-LA-3-3 ON PANEL WHICH STATES |
| THIS FEEDING LOCATION A2.213 YET THE PLANS SHOWS THE |
| LOCATION IN FOYER SINGLE LOCATION A2.003. |
| |
| 23) NOTE: PLEASE SEE 2LD-2-3 WHICH IS NOT SPECIFIC TO |
| ROOMS AND LOCATIONS IN WHICH THIS CIRCUIT FEEDS. PANEL |
| SCHEDULE DOES NOT LIST LOCATIONS AS FOUND ON PLANS. |
| |
| 24) NOTE: PLEASE SEE 2LD2-6 WHICH IS SHOWN AS SPARE ON |
| PANEL SCHEDULE HOWEVER THE PLANS ON E1-2.2 STILL HAS |
| CIRCUIT SHOWN. |
| |
| 25) NOTE: PLEASE CORRELATE ALL POWER AND RELEVANT |
| CHANGES ON POWER PLANS E1-1.1 WITH E7-7.0. |
| THERE ARE NUMEROUS ITEMS |
| |
| 26) NOTE: PLEASE SEE 1LA3-10 WHICH PER PANEL SCHEDULE |
| IT STATES COMMISSION OFFICE HOWEVER PLEASE SEE SHEET |
| E7-7.0 WHICH INDICATES THIS AS A DEDICATE RECEPTACLE IN |
| THE FLAGLER GALLERY. |
| |
| 27) NOTE: PLEASE SEE 1LA3-18 WHICH DOES LIST THIS AS |
| A1-308 ON PLANS HOWEVER PLEASE SEE E7-7.0 |
| |
| 28) NOTE: PLEASE SEE 3LD2-9 NEEDS TO BE SPECIFIC TO |
| ROOMS AND AREAS IN WHICH THEY FEED. THE PLANS INDICATE |
| MANY MORE LOCATIONS THAN WHAT IS LISTED ON PANEL |
| SCHEDULE. |
| |
| 29) NOTE: PLEASE SEE 3LC-19 NEED TO BE SPECIFIC TO ALL |
| ROOMS AND AREAS IN WHICH THEY FEED. |
| |
| 30) NOTE: PLEASE SEE 3LD3-21 ON PANEL SCHEDULE WHICH |
| INDICATES THIS AS A SPARE CIRCUIT HOWEVER THE PLANS |
| STILL SHOW THIS CIRCUIT. |
| |
| 31) NOTE: PLEASE SEE 3LD3-6 WHICH THE PANEL SCHEDULE |
| INDICATES THIS AS A SPARE YET THE PLANS STILL INDICATES |
| THIS AS A CIRCUIT BEING USED. |
| |
| 32) NOTE: PLEASE SEE CIRCUITS 4LA3-5 AND -24 WHICH ARE |
| BOTH SHOWN TIED TOGETHER ON PLANS. WHY ARE THESE NOT |
| SEPARATED? |
| |
| 33) NOTE: PLEASE SEE MULTIPLE SETS OF FURNITURE WORK |
| STATIONS WHICH SHOW THE SAME CIRCUITING 4LB3-26,28,30. |
| PLEASE SEE 220.14(I) FOR LOADS PER YOKE. PLEASE PROVIDE |
| INFORMATION ON HOW MANY RECEPTACLES ARE ON THE CIRCUITS |
| AS SHOWN FOR KNOWN LOADS. THIS WAS GONE OVER IN |
| ORIGINAL REVIEW EVEN BEFORE PERMIT ISSUANCE FOR KNOWN |
| LOADS AND LOADS FIGURED AT 180VA. THE REVIEW COMMENTS |
| CAN BE PROVIDED ALONG WITH E-MAILS IN WHICH QUESTIONS |
| WERE RAISED. |
| |
| 34) NOTE: PLEASE SEE MULTIPLE SETS OF FURNITURE WORK |
| STATIONS WHICH SHOW THE SAME CIRCUITING 4LA3-15,17,19. |
| PLEASE SEE 220.14(I) FOR LOADS PER YOKE. PLEASE PROVIDE |
| INFORMATION ON HOW MANY RECEPTACLES ARE ON THE CIRCUITS |
| AS SHOWN FOR KNOWN LOADS. |
| THIS WAS GONE OVER IN ORIGINAL REVIEW EVEN BEFORE |
| PERMIT ISSUANCE FOR KNOWN LOADS AND LOADS FIGURED AT |
| 180VA. THE REVIEW COMMENTS CAN BE PROVIDED ALONG WITH |
| E-MAILS IN WHICH QUESTIONS WERE RAISED. |
| |
| 35) NOTE: PLANS STILL STATE IT EQUIPMENT TO BE DONE BY |
| OTHERS. HOWEVER THE RECORD SET OF PLANS NEED TO NOW |
| SHOW ALL OF THIS WORK BEING COMPLETED. PLEASE COMPLETE |
| THE IT PANEL SCHEDULE. THE SCHEDULE DOES INDICATE THE |
| CIRCUITING FOR AC EQUIPMENT ETC HOWEVER NO OTHER |
| EQUIPMENT IS SHOWN BEING FED FROM THIS PANEL. |
| WHERE IS ALL OF THE OTHER EQUIPMENT BEING FED FROM? |
| CIRCUITS? LOADS? ETC |
| 408.4,310.16,240.3,220, ETC |
| 645 (ALL) |
| |
| 36) NOTE: PLEASE PROVIDE INFORMATION ON THE EPO AT THE |
| DOOR FOR IT ROOM. |
| PLEASE SEE 645.10 FOR THE REQUIRED DISCONNECTING MEANS |
| TO ALL EQUIPMENT INCLUDING AC EQUIPMENT. |
| THERE IS A CIRCUIT ON 1LED-27 FOR SHUNT TRIP CIRCUIT |
| HOWEVER THE IT PANEL OR FEED TO IT PANEL DOES NOT |
| INDICATE ANY SHUNT TRIP TYPE MAIN BREAKER OR BRANCH |
| BREAKER. THE RISER DOES NOT INDICATE A SHUNT FOR ANY OF |
| THE MAIN BREAKERS OR FEEDERS. |
| PLEASE PROVIDE INFORMATION AND DETAIL FOR THIS. |
| |
| 37) NOTE: PLEASE SEE 4LEB-10 WHICH IS SHOWN AS SPARE ON |
| PANEL SCHEDULE YET THE PLANS STILL INDICATE THIS |
| CIRCUIT. |
| |
| 38) NOTE: PLEASE SEE 4IT 15,17 ON PANEL SCHEDULE THIS |
| IS SHOWN TO RM A4.416 YET THE PLANS DO NOT INDICATE |
| THIS. |
| |
| 39) NOTE: PLEASE SEE 4LD2- 5 STATES RECEPTACLES IN ROOM |
| 4-106 HOWEVER THIS IS SHOWN ON PLANS FEEDING OTHER |
| AREAS ALSO. |
| |
| 40) NOTE: PLEASE SEE 4LC2-13 WHICH IS SHOWN ON PANEL TO |
| ROOM A4-201 HOWEVER ON PLANS THIS IS LOCATED AT THE |
| OTHER END OF THE FLOOR. |
| |
| 41) NOTE: PLEASE SEE 4LC3-9 AND 25 WHICH IS SHOWN TO |
| ROOM/AREA C4.202 YET THE PANEL SCHEDULE INDICATES ONE |
| OF THESE FOR THIS LOCATION AND ONE OF THESE FOR A |
| DIFFERENT LOCATION. THERE IS ALSO THE FACT THE J-BOX IS |
| ALSO FED FROM THE ONE OF THESE CIRCUITS WHICH IS #25. |
| IS THIS CORRECT FOR THE J-BOX? |
| |
| 42) NOTE: PLEASE SEE 4LD3-3, 22 AS BOTH ARE SHOWN ON |
| PLANS, HOWEVER PLEASE SEE THAT THE PANEL SCHEDULE FOR |
| 22 IS BLANK. |
| |
| 43) NOTE: PLEASE SEE MULTIPLE SETS OF FURNITURE WORK |
| STATIONS WHICH SHOW THE SAME CIRCUITING SUCH AS |
| 5LA3-21, 23. PLEASE SEE 220.14(I) FOR LOADS PER YOKE. |
| PLEASE PROVIDE INFORMATION ON HOW MANY RECEPTACLES ARE |
| ON THE CIRCUITS AS SHOWN FOR KNOWN LOADS. THIS WAS GONE |
| OVER IN ORIGINAL REVIEW EVEN BEFORE PERMIT ISSUANCE FOR |
| KNOWN LOADS AND LOADS FIGURED AT 180VA. THE REVIEW |
| COMMENTS CAN BE PROVIDED ALONG WITH E-MAILS IN WHICH |
| QUESTIONS WERE RAISED. |
| |
| 44) NOTE: PLEASE SEE 5LA2- 34 WHICH ON THE PANEL |
| SCHEDULE IT STATES ELECTRICAL ROOM A5.107 RECEPTACLES. |
| HOWEVER THE PLANS SHOW A COMPLETELY DIFFERENT CIRCUIT |
| WHICH FEEDS MANY OTHER LOCATIONS. THE CIRCUIT ON PLANS |
| FOR THIS ROOM IS NOT #34. SEE THE FOLLOWING COMMENT. |
| |
| 45) NOTE: PLEASE SEE 5LA2-3 ON PANEL SCHEDULE WHICH |
| STATES CORRIDOR LIGHTING. HOWEVER ON PLANS THIS FEEDS |
| ROOM ABOVE WHICH IS A5.107, 5.103,5.104,203 ETC |
| |
| 46) NOTE: PLEASE SEE A1.014 ON PLANS SHOWS HA-1 HOWEVER |
| THE DESIGNATION ON PANEL SCHEDULE IS NOT THE SAME. |
| SHOWS A DIFFERENT ROOM. |
| |
| 47) NOTE: PLEASE SEE 1HA-12 ON PLANS AND PANEL SCHEDULE |
| HOWEVER THIS IS NOT PART OF THE LCP. |
| |
| 48) NOTE: PLEASE SEE 410.8 A-D FOR MINIMUM LIGHTING |
| FIXTURE CLEARANCES FROM COMBUSTIBLES IN CLOSETS WITH |
| SHELVING. PLEASE SEE STORAGE CLOSETS A1.612,613.14. |
| PLEASE PROVIDE EXACT SHELVING DIMENSION ON PLANS SO |
| THAT THE CLEARANCES CAN BE DETERMINED. |
| |
| 49) NOTE: PLEASE SEE 1HA-2 WHICH THE PLANS , THE PANEL |
| SCHEDULE AND THE LCP DO NOT CORRELATE. THE CIRCUITING |
| ON PLANS SHOWS ONE LOCATION/ROOM WHICH IS THE GALLERY |
| A1.306 YET THE PANEL STATES THIS CIRCUIT IS FOR |
| EXTERIOR FIXTURES. THE LCP DOES NOT INDICATE ANY OF |
| THESE. |
| |
| 50) NOTE: PLEASE REVISE FIXTURE SCHEDULE AND SUBMIT. |
| FIXTURES FOR EXISTING LOCATION AND REVISED LOCATIONS ON |
| PLANS CAN NOT BE DETERMINED AS CODE COMPLIANT WITH THE |
| EXISTING REVISED CALCULATIONS PER 13-415.2. |
| |
| 51) NOTE: PLEASE SHOW LOCATIONS OF REQUIRED OVER RIDES |
| ON THE 3RD FLOOR EAST END OF LIBRARY. REVISION 17 |
| DELETED THE REQUIRED OVER RIDES BASED ON |
| FURNITURE/SHELVING LAYOUT. ALL REVISED PLANS UP TO THIS |
| LATEST REVISION STILL INDICATE EACH OF THE CIRCUITS |
| WILL GO TO OVER RIDE SWITCHES HOWEVER NEW LOCATIONS |
| WERE NOT SHOWN. |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2 OF THE FBC. LOCATION |
| REQUIRES THE OCCUPANT TO SEE ALL LIGHTING WHICH IS |
| BEING OVER RIDDEN OR MEET EXCEPTIONS. |
| |
| 52) NOTE: PLEASE UPDATE ALL LCP. MANY OF THESE DO NOT |
| LIST THE CIRCUITS ON THE PANEL SCHEDULES OR THE |
| LOCATIONS LISTED ARE NOT CORRECT. |
| |
| 53) NOTE: PLEASE SEE 1HC-19 AS THIS IS ON PLAN AND |
| SCHEDULE HOWEVER NOT ON LCP. |
| |
| 54) NOTE: PLEASE SEE LOBBY D1.003 WHERE ARE THE LIGHTS |
| WHICH IS NOT PART OF THE PHOTO MUSEUM? FBC CHAPTER 10, |
| NFPA- 101 7.8, 7.9. |
| NEC CHAPTERS 2,3,4, GIVEN AS GENERAL SECTIONS. |
| PLANS ARE BLANK. |
| |
| 55) NOTE: PLEASE SEE C1.102 AS THERE IS NO CIRCUIT |
| LISTED OR SHOWN FOR LIGHTING. WHERE DOES THIS |
| INTERCONNECT AND WITH WHICH CIRCUIT? |
| |
| 56) NOTE: PLEASE SEE 2HA-12 WHICH IS NOT SPECIFIC TO |
| ROOMS AND AREAS. |
| |
| 57) NOTE: PLEASE SEE 2HA-19 WHICH IS ON PLANS, ON PANEL |
| SCHEDULE HOWEVER LCP IS BLANK AND DOES NOT INDICATE. |
| |
| 58) NOTE: PLEASE SEE A2.210 AND .211 ROOMS. WHERE DO |
| THE LIGHTS IN THESE TWO ROOMS CONNECT? THE PLANS APPEAR |
| TO MAYBE CONNECT TO 2HA-47 HOWEVER BASED ON THE PANEL |
| SCHEDULE THESE TWO ROOMS ARE NOT LISTED. |
| |
| 59) NOTE: PLEASE SEE 3HA-16 WHICH IS SHOWN ON PLANS, |
| YET THERE IS NOTHING ON PANEL SCHEDULE OR LCP. |
| |
| 60) NOTE: PLEASE SEE 3HA-6 STATES ON THE PANEL SCHEDULE |
| THIS FEEDS A3.009 AND A3.402 YET THE PLANS INDICATE |
| A3.402 BEING FED FROM 3HA-8. PLEASE SEE OTHER LOCATIONS |
| NOT SPECIFIC. |
| |
| 61) NOTE: PLEASE 3HA-8 WHICH IS NOT SPECIFIC. |
| |
| 62) NOTE: PLEASE COMPLETE PLANS WITH CIRCUITING, LOADS |
| AND LIGHTING FOR STAGE AREA LIGHTING. PLANS SHOW *TO BE |
| BY OTHERS* HOWEVER THAT WAS WHEN NONE OF THAT |
| INFORMATION WAS KNOWN. THIS IS THE END OF THE BUILDING |
| ALL OF THE LIGHTING, CIRCUITING, LOADS ETC ARE KNOWN AT |
| THIS TIME WHICH NEEDS TO BE COMPLETE ON PLANS. |
| 220,13-415.1.ABC.1.1, .1.3 ETC |
| |
| 63) NOTE: PLEASE SEE AREAS C3.110,.109,0309 ETC. THE |
| NORMAL LIGHTING IN THIS AREA DOES NOT HAVE ANY CIRCUIT |
| NOTED OR SHOWN. |
| |
| 64) NOTE: PLEASE SEE E2-4.1, LIGHTS IN CORRIDOR A4.009 |
| WHICH DOES NOT INDICATE ANY CIRCUITING FOR NORMAL |
| LIGHTING?? |
| |
| 65) NOTE: PLEASE SEE 4HC-12 WHICH IS LISTED ON THE LCP |
| HOWEVER NOT ON PANEL SCHEDULE. |
| |
| 66) NOTE: PLEASE SEE 4HC-2 WHICH IS ON SCHEDULE FOR |
| LIGHTING IN ELEVATOR LOBBY 5 AND 6; HOWEVER THIS SAME |
| LOBBY AREA DOES NOT HAVE ANY CIRCUIT FOR THE LIGHTING |
| ON PLANS. IN FACT THE LIGHTING ON PLANS IS ALL SHOWN AS |
| EMERGENCY CIRCUITED LIGHTING HOWEVER NO CIRCUIT OR |
| CONNECTION TO OTHER CIRCUITS IS SHOWN. |
| THE CIRCUIT 4HC-2 ON PLANS IS ONLY FEEDING THE C4.105 |
| ROOM AND ALSO THE TWO BATHROOMS C4.102,.103 WHICH DOES |
| NOT COORDINATE WITH THE PANEL SCHEDULE. |
| |
| 67) NOTE: PLEASE SEE 4HC-10 WHICH IS ON PANEL SCHEDULE |
| HOWEVER ON LCP. |
| |
| 68) NOTE: PLEASE SEE 5HA-3 WHICH IS LISTED ON THE LCP |
| HOWEVER IT IS NOT ON THE PANEL SCHEDULE. ** PLEASE SEE |
| THIS SHEET OF PLANS. E2-5.1, GO OVER PLANS. SEE |
| COMMENTS BELOW. |
| |
| 69) NOTE: PLEASE SEE 5HA-17 WHICH STATES * OPEN WORK |
| AREA A5.404 HOWEVER ON THE PLANS THIS IS COMPLETELY |
| SEPARATE. A5.112,.104,.103. |
| |
| 70) NOTE: PLEASE SEE AREAS OF NORMAL LIGHTING A5.507, |
| .506, .504,.501,.528,.503,.505,.508 ETC WHICH DO NOT |
| SHOW ANY CIRCUITING ON PLANS. |
| |
| 71) NOTE: PLEASE SEE 5HB-5 WHICH IS SHOWN ON PLANS, YET |
| THIS IS SHOWN AS A SPARE ON PANEL SCHEDULE. |
| |
| 72) NOTE: FEE BALANCE OF $1160.00 IS DUE BEFORE PICKING |
| UP PLANS AND RESUBMITTING NEW REVISIONS. |
| |
| |
| **** THIS IS NOT AN EXHAUSTED LIST OF ALL POSSIBLE |
| ITEMS. THESE HAVE BEEN GIVEN AS EXAMPLES ONLY! THESE |
| ARE NOT ALL ITEMS. |
| |
| |
| |
| |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |