2008-10-20 09:08:35WEST PALM BEACH
 CITY CENTER- CITY HALL
 PERMIT# 0610.0574
 ADDRESS: 401 CLEMATIS ST.
  
  
 ARCHITECT: SONG & ASSOCIATES
 ENGINEER: THORNTON- TOMASETTI
  
 NOTE: THIS REVIEW WILL BE COMPLETED UNDER 2004 FLORIDA
 BUILDING CODE,
 (*) MEANS CHAPTER 1 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS
  
 REVIEW: SHEET A0-D.1 REVISION# 16B
  
 ACTION: DENIED
  
 1) STAIR SECTION THE HANDRAILIS ONLY 1'-6 INCHES LONG
 THIS IS THE DIMENSION TO BE USED FOR EXTENSIONS FOR
 RAMPS. 11-4.9.4(2) IF HANDRAILS ARE NOT CONTINUOUS,
 THEY SHALL EXTEND AT LEAST 12 INCHES (305 MM) BEYOND
 THE TOP RISER AND AT LEAST 12 INCHES (305 MM) PLUS THE
 WIDTH OF ONE TREAD BEYOND THE BOTTOM RISER. AT THE TOP,
 THE EXTENSION SHALL BE PARALLEL WITH THE FLOOR OR
 GROUND SURFACE. AT THE BOTTOM, THE HANDRAIL SHALL
 CONTINUE TO SLOPE FOR A DISTANCE OF THE WIDTH OF ONE
 TREAD FROM THE BOTTOM RISER; THE REMAINDER OF THE
 EXTENSION SHALL BE HORIZONTAL [SEE FIGURE 19 (C) AND
 FIGURE 19 (D)]. HANDRAIL EXTENSIONS SHALL COMPLY WITH
 SECTION 11-4.4 .
  
 2) THE CONTINIOUS HANDRAIL EXTENSIONS FOR BOTH STAIRS
 AND HANDRAILS STATE IN SECTION 11-4.9.4 (2) WILL NEED
 TO COMPLY WITH SECTION 11-4.4.THE BOTTOM PART OF THE
 EXTENSION MUST BE NO HIGHER THAN27 INCHES.
  
 3) THE RAMP DOES NOT INDICATE HOW EDGE PROTECTION WILL
 BE MET 11-4.8.7.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved