Plan Review Notes For Permit 06100574 |
Permit Number |
06100574 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2007-02-20 12:09:22 | PASSED/PROVISO | | | | SHT P3.2.0 RISER P/2 SHOWS 3 DRINKING FOUNTAINS AT | | TOILET ROOMS C3.107 & C3.108. THE FLOOR PLAN ONLY SHOWS | | 2. REVISION REQUIRED TO CORRELATE RISER WITH FLOOR | | PLAN. | | | | SHT P1.60 REVISION REQUIRED. VENT NOT ALLOWED IN THE | | STAIRWELL, AND DOES NOT REFLECT THE RISER DIAGRAM. | | | | SHT P1.60 REVISION REQUIRED. SHOW THE TRENCH DRAINS AT | | THE BOTTOM OF THE RAMPS. | | | | SHT LSO.0 PLUMBING FIXTURE COUNT TO BE CORRECTED FOR | | DRINKING FOUNTAINS. 2 REQUIRED, READS 1 REQUIRED, | | REVISION REQUIRED. | | | | SHT LSO.0 PLUMBING FIXTURE COUNT TO BE CORRECTED FOR | | DRINKING FOUNTAINS. 4 REQUIRED, READS 2 REQUIRED. | | REVISION REQUIRED. | | | | SHT A9-0.2 TOILET ROOMS C1.05 & C1.106 FINISH OF EPOXY | | PAINT NOT APPROVED. SECTION 1210.2. REVISION REQUIRED. | | | | PLEASE SUBMIT ALL REVISIONS REQUESTED WITHIN 60 DAYS | | AFTER ISSUANCE OF PERMIT. |
|