Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop P
Sequence Number 4
Notes
Date Text
2007-02-20 12:09:22PASSED/PROVISO
  
 SHT P3.2.0 RISER P/2 SHOWS 3 DRINKING FOUNTAINS AT
 TOILET ROOMS C3.107 & C3.108. THE FLOOR PLAN ONLY SHOWS
 2. REVISION REQUIRED TO CORRELATE RISER WITH FLOOR
 PLAN.
  
 SHT P1.60 REVISION REQUIRED. VENT NOT ALLOWED IN THE
 STAIRWELL, AND DOES NOT REFLECT THE RISER DIAGRAM.
  
 SHT P1.60 REVISION REQUIRED. SHOW THE TRENCH DRAINS AT
 THE BOTTOM OF THE RAMPS.
  
 SHT LSO.0 PLUMBING FIXTURE COUNT TO BE CORRECTED FOR
 DRINKING FOUNTAINS. 2 REQUIRED, READS 1 REQUIRED,
 REVISION REQUIRED.
  
 SHT LSO.0 PLUMBING FIXTURE COUNT TO BE CORRECTED FOR
 DRINKING FOUNTAINS. 4 REQUIRED, READS 2 REQUIRED.
 REVISION REQUIRED.
  
 SHT A9-0.2 TOILET ROOMS C1.05 & C1.106 FINISH OF EPOXY
 PAINT NOT APPROVED. SECTION 1210.2. REVISION REQUIRED.
  
 PLEASE SUBMIT ALL REVISIONS REQUESTED WITHIN 60 DAYS
 AFTER ISSUANCE OF PERMIT.