2007-04-05 10:12:41---------------DENIED------------------
  
 GARAGE REVISIONS (7) SUBMITTED 3/16/07
  
 1. NEW MECHANICAL SHEETS SUBMITTED ARE MODIFYING
 EXISTING SHEETS WHICH ALREADY COVER THE SCOPE OF
 MECHANICAL WORK IN THE PERMIT SET OF PLANS. PLEASE
 REVISE EXISTING SHEETS TO INCLUDE THE ADDED WORK OR
 SHOW THE FULL SCOPE OF WORK TO BE PERFORMED IN THESE
 AREAS ON NEW SHEETS WHICH WOULD REPLACE/SUPERCEDE
 EXISTING SHEETS.
  
 2. EQUIPMENT LOCATED IN PUBLIC GARAGES SHALL BE
 INSTALLED A MINIMUM OF 8 FEET ABOVE THE FLOOR, OR A
 MINIMUM OF 2 FEET HIGHER THAN THE HEIGHT OF THE TALLEST
 VEHICLE, OR PROTECTED FROM MOTOR VEHICLE IMPACT. FBC,M
 304.5
  
 3. PLEASE PROVIDE MANUFACTURER'S SUBMITTAL AND
 INSTALLATION INSTRUCTIONS FOR C.O. SYSTEM. FBC,M 304.1
  
 NOTE: A COMPLETE REVIEW OF THIS WORK CAN NOT BE
 PERFORMED PRIOR TO THE INCORPORATION OF ALL MECHANICAL
 WORK TO BE PERFORMED IN THESE AREAS AS STATED IN
 COMMENT #1.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]