Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop G
Sequence Number 4
Notes
Date Text
2007-02-17 17:14:28PASSED/PROVISO
  
 GAS RISER DIAGRAM SHOWS 128' FROM GENERATOR TO LAST
 FUTURE GENERATOR. THIS SCALES OUT TO ABOUT 30' ON THE
 PLANS. THE PIPING SHALL BE SIZED FOR 200' MAXIMUM. A
 REVISION WILL BE REQUIRED SHOWING THE CORRECT DISTANCE
 FROM THE FIRST GENERATOR TO THE LAST.--THE MANUF.
 SPECIFICATIONS SHALL BE REQUIRED SHOWING THE MAXIMUM
 BTU LOAD AT 100% CAPACITY WHEN APPLYING FOR THE
 REQUIRED GAS PERMIT.