Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop E
Sequence Number 4
Notes
Date Text
2007-02-18 13:31:522007-02-18 13:31:52
  
 *** PROVISO/REVISION ***
  
  
 ** THE FOLLOWING *PROVISO* WAS SET UP WITH CONDITIONS
 THAT ALL OF THE FOLLOWING BE REVISED, UPDATED AND
 SUBMITTED FOR REVIEW WITHIN 60 DAYS FROM ISSUANCE OF
 PERMIT.
 PLEASE SEE THAT MANY OF THE ITEMS BELOW BESIDES CODE
 RELATED ITEMS ARE MOSTLY BASED ON COORDINATION RELATED
 ISSUES.
 PLEASE SEE SOME OF THE NOTES ARE NEW AS SOME THINGS
 HAVE BEEN ADDED TO THESE PLANS WHICH WERE NOT ON
 PREVIOUS REVIEWED PLANS.
 THE SECTION OF THE FBC 106.1.2 MADE IN NOTES BELOW IS
 FROM THE 2004 FBC ADMINISTRATIVE SECTION AS ADOPTED BY
 THE CITY OF WEST PALM BEACH FOR * ADDITIONAL
 INFORMATION*.
 ** MANY OF THESE WILL NOT ONLY REQUIRE THE PARTIAL FOR
 EACH FLOOR, BUT ALSO THE *OVERALL* FLOOR SHEETS TO BE
 REVISED.
  
  
 1) NOTE: PLEASE SUBMIT THE WIND LOAD CALCULATIONS FOR
 SITE LIGHT POLES FOR COURTYARD AND ROOF TOP AREAS.
 THESE SHALL CONTAIN THE ORIGINAL SIGNATURE, DATE AND
 SEAL FROM THE ENGINEER OF RECORD. FS 471.025 AND TITLE
 BLOCKS ON EACH SHEET PER 61G15-23.002.
  
 2) NOTE: PLEASE SEE THAT THERE MAY BE POSSIBLE STAIRS
 TO THE ROOF ON THE SOUTH SIDE OF THE BARREL ROOF FROM
 THE FOURTH LEVEL. THIS IS A BUILDING CODE REQUIREMENT
 AND PENDING ANY DECISION FROM THE CBA, LIGHTING,
 PHOTO-METRICS ETC WILL BE REQUIRED TO BE SUBMITTED AND
 REVISED FOR THOSE SHEETS AFFECTED BY THIS.
 THIS WOULD INVOKE LS 101 7.8 AND 7.9.
  
 3) NOTE: PLEASE SEE THERE ARE MANY LOCATIONS WHERE
 BATTERY BACK UP TYPE FIXTURES ARE BEING SHOWN WITH OC
 DEVICES OR SWITCHING.
 PLEASE SEE PREVIOUS NOTES WHICH REQUESTED BATTERY BACK
 UP FIXTURES OF SOME SORT IN MANY ROOMS; HOWEVER PLANS
 WERE REVISED IN MANY ROOMS TO INCLUDE A ZE FIXTURES,
 WHICH IF CONTROLLED AS SHOWN (SWITCHED) THEN THE LIGHT
 FIXTURE WHICH IS BATTERY BACK UP WOULD COME ON EACH
 TIME THE SWITCH OR DEVICE TURNS LIGHTING OFF. PLEASE
 SEE MOST ELECTRICAL ROOMS, ELEVATOR EQUIPMENT ROOMS,
 MECHANICAL ROOMS ETC.
 PLEASE SEE THE FOLLOWING LOCATIONS WILL BE REQUIRED TO
 CONTAIN A BATTERY BACK UP FIXTURE, HOWEVER THESE
 LOCATION ARE NOT TO HAVE LIGHTING REMAIN *ON* AS NL
 (NIGHT LIGHTS) 24 HRS A DAY.
 THESE LOCATIONS WHICH WILL REQUIRE A BATTERY BACK UP
 FIXTURE, BUT NOT FOR FIXTURES TO BE SWITCHED OR ON AS
 NL SHALL BE THE *MAIN ELECTRICAL ROOM IN GARAGE, MAIN
 MECHANICAL ROOM IN GARAGE, ALL ELEVATOR EQUIPMENT
 ROOMS, IT ROOM, FIRE PUMP ROOMS, BOTH MEZZANINE
 MECHANICALROOMS, THE MECHANICAL ROOM ON ROOF AND FIRE
 COMMAND ROOM. PLEASE SEE ALL OTHER SMALLER ELECTRICAL
 ROOMS WHICH CONTAIN ZE OR ZE2 FIXTURES ARE NOT REQUIRED
 TO CONTAIN A BATTERY BACK FIXTURE, BUT MAY. IF THEY DO
 CONTAIN A BATTERY BACK UP THESE SHALL NOT BE SWITCHED
 AND SHALL NOT BE ON 24/7. (700.12E).
 PLEASE GO OVER ALL OF THESE LOCATIONS ON PLANS AS MANY
 ROOMS DO SHOW THESE TYPE FIXTURES, HOWEVER NOT ALL.
 (PLEASE SEE REDLINED PLANS AS MANY OF THESE HAVE BEEN
 HIGH-LIGHTED BUT NOT ALL).
 PLEASE SEE DOME ROOM ABOVE THE ROOF TOP MECHANICAL ROOM
 DOES NEED A BATTERY BACK UP FIXTURE FOR EGRESS (STAIRS)
 HOWEVER SHOULD NOT CONTAIN NL FOR 24/7 OPERATION. MANY
 OF THESE WOULD CREATE A DIRECT CONFLICT WITH 700.12E OF
 THE NEC AND CHAPTER 13 OF THE FLORIDA ENERGY CODE.
 ** PLEASE CALL TO GO OVER OR TO COME IN AND GO THROUGH
 PLANS**
  
 4) NOTE: PLEASE SEE MANY LOCATIONS ON PLANS WHICH
 INDICATE NIGHT LIGHTS (NL). THE AMOUNT OF THESE
 FIXTURES SHOULD BE REVIEWED AS THE AMOUNT IS OVER IN
 MANY LOCATIONS FOR THAT WHICH IS REQUIRED FOR LS 101
 7.8 AND 7.9. PLEASE SEE SOME AREAS WHICH CONTAIN NL
 WHICH ARE STILL BEING SHOWN SWITCHED FROM LOCAL
 SWITCHES.
 PLEASE SEE FOR EXAMPLE A.5.06.
 PLEASE SEE MANY LOCATIONS WHICH THESE NIGHT LIGHTS DO
 NOT SHOW ANY CONTROL OR CIRCUITING AND OR ARE IN
 CONFLICT AS THERE ARE OTHER FIXTURES WHICH ARE SHOWN ON
 THE NIGHT LIGHT CIRCUITS WHICH DO NOT CORRELATE WITH
 THE TYPE OF FIXTURES ON LEGENDS.
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE STAIRS WHICH ONLY CONTAIN CONTROL
 FOR LIGHT AT ONE LOCATION EITHER AT THE TOP OR AT THE
 BOTTOM OF STAIRS.
 PLEASE SEE STAIR 12, STAIR 13. (PLEASE SEE STAIR 11 FOR
 EXAMPLE WHICH SHOWS BATTERY BACK UP FIXTURES BEING
 SWITCHED. (AS NOTED ABOVE.
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE THE ELECTRICAL CIRCUITING WHICH HAS
 NOW BEEN ADDED TO THE ELEVATOR EQUIPMENT ROOM ON ROOF
 TOP. PLEASE SEE THE DEDICATED CIRCUITS AS REQUIRED PER
 620.23 ARE THE SAME CIRCUITS AS SHOWN FOR THE FIRST
 FLOOR ELEVATOR EQUIPMENT ROOMS WHICH NOW HAVE CIRCUITS
 SHOWN FOR LIGHTING.
 PLEASE ALSO SEE THAT TWO SETS OF THE PLANS WHICH
 INDICATE THESE CIRCUITS TO PANEL 1-HEE DO NOT SHOW
 THESE CIRCUITS OR LOADS ADDED TO PANEL.
 PLEASE SEE ONE OF THE SETS OF PLANS DO SHOW THESE
 CIRCUITS ADDED TO PANEL SCHEDULE; HOWEVER NOT TO
 LOADS.
 PLEASE CORRELATE AND REVISE. PLEASE ALSO SEE NEXT
 NOTE.
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE THE NEW ELECTRICAL FOR EQUIPMENT
 ADDED FOR THE ROOF TOP ELEVATOR EQUIPMENT ROOM WHICH
 WAS ADDED TO THESE PLANS AND TO PANEL 5-LEB ARE SHOWN
 ON PANEL SCHEDULE BUT THE LOAD CALCULATIONS WERE NOT
 REVISED OR ADJUSTED FOR THESE NEW LOADS.
 PLEASE ALSO SEE 620.23 AS THE NEW CIRCUIT 16 FOR THIS
 SAME PANEL FOR THE RECEPTACLE CIRCUIT SHOULD BE LABELED
 FOR THIS ELEVATOR EQUIPMENT ROOM AND NOT GENERAL
 RECEPTACLE CIRCUITS.
 FBC 106.1.2.
  
 8) NOTE: PLEASE SEE THE LIGHTING POWER DENSITIES SHEETS
 1 OF 14 AND 14 OF 14 WHICH DID NOT CORRELATE FOR 6TH
 AND 7TH LEVELS AND LIGHTING. THESE ITEMS WERE CHANGED
 IN MEETING WITH ENGINEER.
 PLEASE ALSO SEE THE SHEET 4 OF THE FLORIDA ENERGY CODE
 INPUT DATA REPORT WHICH SHOWS *MANUAL CONTROLS FOR TWO
 AREAS.
 PLEASE SE THIS WAS ALSO CHANGED BY THE ENGINEER IN
 MEETING.
 THESE SHEETS SHOULD BE REVISED FOR THESE ITEMS AND FOR
 ANY AND ALL CHANGES MADE FOR FIXTURES IN MANY ROOMS AS
 NOTED ABOVE IN OTHER NOTES.
 FBC 106.1.2
 FBC 13-415.1.AB.1, 13-415.2
  
 9) NOTE: PLEASE SEE FIRST FLOOR CITY HALL SECTION WHICH
 SEEMS TO BE MISSING A 3-WAY SWITCH FOR MAIL/RECEIVING
 ROOM.
  
 10) NOTE: PLEASE SEE 3-WAY SHOWN ON E 2-2.2 WHICH IS
 NOT SHOWN ON E2-1.4 FOR THE SAME LOCATION. (REDLINED)
  
 11) NOTE: PLEASE SEE AS NOTED ABOVE A BATTERY BACK UP
 FIXTURE WILL BE REQUIRED IN THE IT ROOM OF SOME SORT.
 LS 101 7.8, 7.9.
 FBC 106.1.2
  
 12) NOTE: PLEASE SEE THAT MANY OF THE REVISED LIGHTING
 PLANS DO NOT CORRELATE WITH THE REVISED PHOTO-METRICS
 OR MANY OF PHOTO-METRICS SHEETS WERE NOT REVISED.
 PLEASE SEE STAIR 12, WHICH SHOWS DIFFERENT LIGHTS AND
 LOCATIONS ON LIGHTING PLANS THAN THAT OF THE SAME STAIR
 ON BOTH THE NORMAL AND EMERGENCY PHOTO-METRICS. PLEASE
 SEE THE PHOTO-METRICS SHOULD COORDINATE WITH ALL OTHER
 FIXTURES, TYPES ETC.
 PLEASE SEE PREVIOUSLY NOTED DOUBLE LIGHT FIXTURES IN
 STAIRS.
 FBC 106.1.2
  
 13) NOTE:AS PREVIOUSLY NOTED PLEASE CORRELATE AND
 REVISE ALL PHOTO-METRICS FOR STAIR DESIGNATIONS. PLEASE
 SEE THERE ARE MANY SHEETS WHICH STILL INDICATE THE OLD
 DESIGNATIONS. PLEASE SEE SOME SHEETS SHOW THE TABLES
 SHOW ONE DESIGNATION AND THE PLANS SHOW ANOTHER. PLEASE
 SEE SOME TABLES SHOW DESIGNATION, AND THEN THE SHEETS
 FOR THOSE STAIRS ARE BLANK?
 PLEASE SEE MISSING STAIR 6 FOR BOTH NORMAL AND
 EMERGENCY.
 PLEASE SEE TWO OF THE SETS FOR PHOTO-METRICS ARE
 DIFFERENT FROM THE THIRD SET WHERE SOME OTHER
 DESIGNATIONS WERE REVISED, BIT THE OTHER TWO SETS
 CONTAIN SOME SHEETS WHICH WERE REVISED AND SOME WHICH
 WERE NOT. PLEASE SEE THAT EVEN SOME OF THE REVISED
 SHEETS FOR DESIGNATIONS DO NOT CORRELATE.
 PLEASE SEE SHEETS 9-3.0 AND 9-3.2 WHICH BOTH APPEAR TO
 BE THE SAME SHEET. THE SHEET 9-3.2 SHOULD BE THE
 PARTIAL FOR AREA.
 ** PLEASE SEE THAT MANY OF THESE AREAS ARE REDLINED AND
 HIGH-LIGHTED ON PLANS.
 ** PLEASE SEE TWO SETS WHICH THIS IS AN ISSUE FOR
 SHEETS 9-5.0 AND 9-5.2
 FBC 106.1.2
  
 14) NOTE: PLEASE SEE REDLINED DIVISION 16 SPECS FOR
 COLOR CODING FOR 277/480V SYSTEM.
 * BROWN, PURPLE, YELLOW*
  
 15) NOTE: IF THE FIXTURE DESIGNATIONS ARE GOING TO BE
 SHOWN ON PHOTO-METRICS, THEN PLEASE CORRELATE WITH THE
 LIGHTING PLANS. THERE ARE NUMEROUS FIXTURES WHICH DO
 NOT CORRELATE.
 FBC 106.1.2
  
 16) NOTE: LIGHTNING PROTECTION WILL BE UNDER SEPARATE
 PERMIT, HOWEVER MAY USE THESE PLANS TO REFERENCE.
  
 17) NOTE: PLEASE SEE THE FUTURE BUILD OUT FOR IT WILL
 BE UNDER A SEPARATE PERMIT WHICH WILL REQUIRE
 SUBMITTALS FOR ALL EQUIPMENT BEING INSTALLED IN THIS
 ROOM ALONG WITH PLANS, PERMIT APPLICATIONS AND FEES.
  
 18) NOTE: PLEASE SEE THE LOW VOLTAGE SYSTEMS ARE UNDER
 A SEPARATE PERMIT, PLANS AND FEES. PLANS ARE TO BE
 SUBMITTED AT A LATER DATE BEFORE INSTALLATION BEGINS.
 THESE PLANS REFLECT CONDUIT LOCATIONS ONLY.
  
  
 ** PLEASE KNOW AS MANY OF THESE ITEMS ARE REDLINED OR
 HIGHLIGHTED ON PLANS, THIS IS IN NO WAY ALL POSSIBLE
 LOCATIONS. PLEASE REVIEW SAID PLANS.
  
 ** PLEASE CALL TO SET UP A TIME TO GO OVER SOME
 POSSIBLE ALTERNATIVES FOR SOME OF THE ITEMS ABOVE.
  
 IF THERE ARE ANY QUESTIONS OR IF THE NOTES TYPED ARE
 NOT CLEAR IN ANY WAY, PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 ** ALL PLANS, ALL SETS, ALL SUBMITTALS, SPEC BOOKS
 STAMPED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-02-18 08:14:172007-02-18 08:14
 CONTINUING TO PROCESS, NOTES TO FOLLOW.
2007-02-16 07:01:132007-02-16 07:01:13
 IN REVIEW
2007-02-15 21:14:222007-02-15 21:14:22
 ** REVIEW TO CONTINUE ON 2/16, PROVISO NOTES TO FOLLOW.