2009-01-08 16:13:47 | ***** REVISIONS SUBMITTED 12/18/08 |
| |
| 1) NOTE: LOADS FOR NEW PANELS HAVE NOT BEEN INCREASED |
| IN SEVERAL LOCATIONS. |
| FOR EXAMPLE: NEW PANELS FOR 1HD, 2HDR, 2LDR ETC ALL THE |
| WAY TO MSB1. |
| THIS REQUIRES A MINIMUM FOR SPACE WHICH IS NOW KNOWN TO |
| BE FUTURE OFFICE SPACE. SEE 220.12,220.14 ETC |
| PLEASE SEE OTHER EQUIPMENT FOR EXAMPLE 1-DPHC WHICH HAS |
| NOT BEEN REVISED SINCE REVISION 12A. IF IT HAS BEEN |
| REVISED IT HAS NOT BEEN SUBMITTED. |
| |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |