Plan Review Notes For Permit 06100574 |
Permit Number |
06100574 |
|
Review Stop |
P |
Sequence Number |
34 |
|
Notes |
Date |
Text |
2009-03-31 09:34:19 | REVISION PASSED/PROVISO: | | | | ***REVISION REQUIRED*** | | | | | | 1. SHTS P2-1.0U P3-1.0 THE MOP SINK SHALL CONNECT TO | | THE GREASE SYSTEM, NOT THE SANITARY SYSTEM. SECTION | | 1003.3.1. -- ALSO THE MOP SINK SHALL NOT DRAIN THRU THE | | WET VENT FOR THE BATHROOM FIXTURES PER SECTION 909.1. | | -- PLANS RED LINED WITH REVISION TO FOLLOW. | | | | | | | | |
|