2008-11-10 14:31:17 | |
| |
| |
| ** DENIED REVISION ** |
| |
| 1) NOTE: PLEASE SUBMIT THE RIGHT OF WAY STREET LIGHTING |
| UNDER A SEPARATE PERMIT. THESE ARE NOT PART OF THE BASE |
| BUILDING LEGAL ADDRESS OR ELECTRICAL SYSTEMS. |
| PLEASE BE SURE THE FIXTURE INFORMATION ON PLANS IS |
| COMPLETE WITH THE TYPE OF FIXTURE, THE WATTAGE, THE |
| VOLTAGE ETC. THE PLANS CONTAIN NOTES WHICH STATE |
| RECEPTACLES ON POLE HOWEVER NO DETAIL IS SHOWN ON HOW |
| THESE WILL INSTALLED OR WIRED. ARE THESE APART OF THE |
| POLE FROM THE MANUFACTURE? |
| 215,300,310.16,110.3,240.4, ETC |
| FBC 105.1. |
| |
| 2) NOTE: THE PLANS WERE NOT ROUTED TO THE BUILDING PLAN |
| REVIEWER AS NO WIND LOAD INFORMATION/CALCULATIONS WERE |
| SUBMITTED FOR REVIEW. IN THE INTEREST OF TIME THIS |
| REVIEWER IS ONLY PLACING NOTES FOR INFORMATION WHICH |
| WILL BE NEEDED FOR THE STRUCTURAL REVIEW. THE WIND LOAD |
| CALCULATIONS NEED TO SHOW THE POLE, STRUCTURAL |
| COMPONENTS, THE EPA (EFFECTIVE PROJECTED AREA) OF THE |
| FIXTURE OR FIXTURES. THESE WILL NEED TO BE COMPLETE |
| WITH TITLE BLOCKS, ORIGINAL SIGNATURE, DATE AND RAISED |
| SEAL BY A FLORIDA LICENSED AND REGISTERED ENGINEER. |
| FBC TABLE 1609 |
| FS 471.025 |
| FAC 61G15-23.002 |
| |
| |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |