Date |
Text |
2007-01-30 17:59:39 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| FROM PREVIOUS REVIEW: |
| FROM PREVIOUS REVIEW: |
| |
| 1. OK |
| 2. OK |
| |
| 3. SHT P1-1.1 PUMP ROOM A1-112. RPZV BACKFLOW SHALL BE |
| INSTALLED A MAXIMUM OF 4' ABOVE THE FLOOR FOR |
| CERTIFICATION AND SERVICE. |
| ****RESPONSE NOTED, HEIGHT TO BE INDICATED FOR THE |
| BACKFLOWS TO BE A MAXIMUM OF 4' ABOVE THE FLOOR. |
| ****RESPONSE NOTED, BUT PLANS INDICATE MINIMUM 4' ABOVE |
| THE FLOOR. THE REQUIREMENT IS FOR MAXIMUM 4' ABOVE THE |
| FLOOR. |
| ******RESPONSE NOTED, BUT THE MINIMUM IS STILL |
| INDICATED. |
| |
| 4. OK |
| 5. OK |
| 6.OK |
| 7.OK |
| 8.OK |
| 9.OK |
| 10. OK |
| 11. OK |
| 12. OK |
| 13. OK |
| 14. OK |
| 15. OK |
| 16. OK (SHOWN ON SHT P2-1.0U) |
| 17. OK |
| 18. OK |
| 19. OK |
| 20. OK |
| 21. OK |
| 22. OK |
| 23. OK |
| 24. OK |
| 25. OK |
| 26. OK |
| 27. OK |
| 28. OK |
| 29. OK |
| 30. OK |
| 31. OK |
| 32. OK |
| 33. OK |
| 34. OK |
| 35. OK |
| |
| 36. SUBMIT A SANITARY HORIZONTAL RISER ISOMETRIC AND |
| VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, TRAPS, |
| VENTS, CLEANOUTS, OFFSETS, RISER NUMBERS AND DFU'S AS |
| THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3. |
| ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN, |
| ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND DFU'S ARE NOT |
| SHOWN AS THEY ACCUMULATE IN THE SYSTEM. ALSO INDICATE |
| ON THE FIRST FLOOR WHERE ALL RISERS BEGIN IN THE |
| SYSTEM. |
| ****RESPONSE NOTED, BUT SHT P3-1.0 RISER 1, LAVS DO NOT |
| REFLECT THE FLOOR PLAN 2ND FLOOR C2-1.03. - DOES NOT |
| REFLECT THE FLOOR PLAN C4.103/C4.104 DRINKING FOUNTAINS |
| SHOW 3, FLOOR PLAN SHOWS 2. - CLEANOUT NOT SHOWN AT THE |
| BASE OF P/1. - NOT ALL PIPE SIZES SHOWN.-SHT P3-2.0 |
| RISER P/2 CLEANOUT DOWNSTREAM OF JANITOR SINK IN ROOM |
| C4.101 NOT INSTALLED PER SECTION 706.3. SECOND CLEANOUT |
| AT THE BASE OF P/2 NOT REQUIRED AS IT DOES NOT CLEANOUT |
| THE BASE OF THE STACK, NOR DOES IT REFLECT THE FLOOR |
| PLAN. - FLOOR DRAIN PIPING IN ROOM D1.101 AS INDICATED |
| IS BEING INSTALLED ABOVE THE FLOOR. - EACH DRINKING |
| FOUNTAIN SHALL HAVE ITS OWN TRAP. SAFE WASTE FOR THE |
| FIXTURES IS NOT APPROVED.(SEE ROOMS D1.101, D1.108, |
| AND A3.111). -CLEANOUTS ARE REQUIRED AT THE BASE OF |
| STACKS P/4 & P/10. - CLEANOUT FOR P/7 NOT INSTALLED AT |
| THE BASE OF P/7. -THE NEW SANT. PIPING TO TOILET ROOM |
| D2.105 NOT SHOWN ON THE FLOOR PLAN. -SHOW ALL TOILET |
| ROOM NUMBERS ON THE RISER DIAGRAM. - SHOW ALL PIPE |
| SIZES. THE PIPE SIZES ARE NOT SHOWN ON MANY PIPES.- |
| SHT P3-3.0A TWO WAY CLEANOUT IS REQUIRED NEAR THE |
| JUNCTION OF THE BUILDING DRAIN AND THE BUILDING SEWER. |
| (DETAIL 1).-THE RISER DIAGRAM DOES NOT REFLECT THE |
| FLOOR PLAN FOR A1.05 & A1.106. AN EXTRA FLOOR DRAIN IS |
| INDICATED THAT IS NOT SHOWN ON THE FLOOR PLAN.- |
| A3.102 & A3.103 ONLY SHOWS 2 LAVS ON THE RISER AND THE |
| FLOOR PLAN SHOWS 4.-A4.103 & A4.104TWO W/C'S ARE |
| MISSING FROM THE RISER THAT ARE SHOWN ON THE FLOOR |
| PLAN.-A4.105NO FLOOR DRAIN AND A SECOND SINK ARE |
| SHOWN ON THE FLOOR PLAN THAT ARE NOT SHOWN ON THE RISER |
| DIAGRAM. (JANITOR ROOM).-A5.105 SHOWS THE BRANCH |
| LINE CONNECTING NEAR THE DRINKING FOUNTAINS ON THE |
| FLOOR PLAN, BUT CONNECTING DOWNSTREAM OF THE NEXT |
| FIXTURES ON THE RISER DIAGRAM.-A CLEANOUT IS |
| REQUIRED AT THE BASE OF RISER P/8-ALL RISER |
| DIAGRAMS,CHECK ALL PIPE SIZES, MAKE SURE THE RISER |
| DIAGRAMS REFLECT THE FLOOR PLAN FOR BOTH THE SANITARY |
| AND THE VENTING.SECTIONS106.1.1, 106..1.2, 706.3, |
| 708.3.4, 708.3.5, 100.2.1. |
| ******RESPONSE NOTED, BUT NOW THE FLOOR PLAN SHOWS 3 |
| DRINKING FOUNTAINS & THE SANT. RISER SHOW 2. PLEASE |
| CORRELATE.--D1.108 STILL SHOWS A SAFE WASTE AT THE |
| CENTER DRINKING FOUNTAIN. |
| |
| 37. OK |
| 38. OK |
| 39. OK |
| |
| 40. ALL PME & FIRE PROTECTION SHEETS. PLANS SHALL BE |
| SIGNED, SEALED, AND DATED. SECTION 106.1. ALL TITLE |
| BLOCK INFORMATION REQUIRED BY FAC 61G1-23.002 AND FS |
| 471.025 SHALL BE SUBMITTED ON EACH SHEET. ****RESPONSE |
| NOTED, BUT THE SEAL USED IS NOT APPROVED. NEW SEALS |
| SHALL INDICATE THE WORD "LICENSE" IN THE SEAL. (SEE |
| ATTACHED SHEET FROM THE FLORIDA BOARD OF PROFESSIONAL |
| ENGINEERS). |
| ****RESPONSE NOTED, BUT THE SEALS OF SOME MECH. AND |
| PLUMBING SHEETS ARE STILL THE OLD SEAL. - ALSO THERE |
| SEEMS TO BE TWO SETS OF SIGNATURES FOR THE ENGINEER OF |
| RECORD. PLEASE SUBMIT A SIGNED, SEALED, DATED, |
| NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE OF THE |
| ENGINEER OF RECORD FOR OUR FILES. ONE SET OF PLANS |
| SHALL BE RETAINED FOR POSSIBLE REVIEW BY THE FLORIDA |
| BOARD OF PROFESSIONAL ENGINEERS. |
| ******RESPONSE NOTED, BUT THERE ARE STILL SOME SEALS |
| WITH "CERTIFICATE" ON THE MECHANICAL SHEETS. |
| |
| **************NEW COMMENTS************** |
| |
| 1B. SHTS P1-1.0U, P1-1.1U, P1-1.1 & P1-2.1. RWL-4 DOES |
| NOT REFLECT THE SQUARE FOOTAGE SHOWN ON RISER DIAGRAM |
| OR ROOF PLAN. PLEASE CORRELATE RISER, FLOOR PLAN, & |
| ROOF PLAN. SECTION 106.1.1. |
| ****RESPONSE NOTED. WILL RECHECK AFTER THE CALCULATIONS |
| FOR THE ROOF DRAINS HAS BEEN RESUBMITTED WITH |
| CORRECTIONS. |
| ******RESPONSE NOTED, BUT SOME SHEETS SHOW A DIFFERENT |
| SQUARE FOOTAGE THAN SHOWN ON THE ROOF PLAN & RISER. |
| PLEASE CORRELATE ALL SHEETS. |
| |
| 2B. OK |
| 3B. OK |
| 4B. OK |
| 5B. OK |
| |
| 6B. SHTS P1-1.2U, ASSOCIATED RISER DIAGRAMS, AND |
| ENLARGED FLOOR PLANS. INDICATE HOW THE STACKS P/1 & |
| P/10 CAN DRAIN INTO THE TOILET GROUP FIXTURE BRANCH. |
| SUBMIT A DETAIL SHOWING THE 4" CLEANOUT TEE, THE 4" |
| CROSS FOR THE FIXTURE BRANCH, AND THE 4" DOUBLE |
| Y/EIGHTH BEND FITTINGS STACKED ON TOP OF EACH OTHER. |
| WILL THEY BE AT THE RIGHT HEIGHT FOR THE W/C'S?SEE |
| SECTION 908.3 ALSO. SECTION 106.1.1. (STACKS SHOULD |
| CONNECT TO THE BUILDING DRAIN AND FIXTURE GROUPS SHOULD |
| CONNECT TO THE STACK SO THAT THE STACK DOES NOT RUN |
| THRU THE MIDDLE OF THE FIXTURE GROUP). ****RESPONSE |
| NOTED, BUT C/O'S ARE REQUIRED AT THE BASE OF EACH |
| STACK. COMMENT HAS NOT BEEN ADDRESSED. ******RESPONSE |
| NOTED, BUT NOW THE VENTING TO THE W/C'S IS NOT SHOWN ON |
| THE 1ST FLOOR STACK P-10. |
| |
| 7B. SHTS P1-1.3U, P1-2.0, P1-2.3, P1-3.3, & P1-4.3 |
| RWL-6 DOES NOT REFLECT THE SQUARE FOOTAGE SHOWN ON THE |
| RISER DIAGRAM, NOR ON THE ROOF PLAN. PLEASE CORRELATE |
| INFORMATION. SECTION 106.1.1 & TABLE 1106.3. |
| ****RESPONSE NOTED, BUT THE COMMENT WAS NOT ADDRESSED |
| ON SHTS P1-3.3, & P1-4.3. |
| ******RESPONSE NOTED, BUT THE SQUARE FOOTAGE ON SHTS |
| P1-2.0 & P1-2.3 IS INDICATED AS 5,584SF. PLEASE |
| CORRELATE ALL SHEETS. |
| |
| 8B. OK |
| 9B. OK |
| 10B. OK |
| 11B. OK |
| 12B. OK |
| 13B. OK |
| 14B. OK |
| |
| 15B. SHT P1-6.0 SHOW THE LOCATIONS FOR ALL VTR'S. - |
| INDICATE THE RWL EACH ROOF DRAIN IS CONNECTED TO. |
| SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT VTR'S 1, 3, 9 & 10 ARE NOT |
| SHOWN. |
| ******RESPONSE NOTED, BUT THE VTR FOR THE TOILET ROOM |
| IN THE GARAGE IS NOT INDICATED PAST THE 1ST FLOOR. |
| PLEASE SHOW THE VENT ON THE 2ND, 3RD, 4TH, 5TH & AT THE |
| ROOF LEVEL OF THE GARAGE. |
| |
| 16B. OK |
| 17B. OK |
| 18B. OK |
| 19B. OK |
| 20B. OK |
| 21B. OK |
| 22B. OK |
| 23B. OK |
| 24B. OK |
| 25B. OK. |
| 26B. OK |
| 27B. OK |
| 28B. OK |
| 29B. OK |
| 30B. OK |
| 31B. OK |
| 32B. OK |
| 33B. OK |
| |
| 34B. SHT P3.1.0 SANT RISER DIAGRAM, TRAPS ARE REQUIRED |
| ON ALL DRINKING FOUNTAINS. SECTION 1002.1. - 1ST FLOOR |
| LAVS PIPING DOES NOT REFLECT THE FLOOR PLAN. - FLOOR |
| DRAINS DOWNSTREAM OF RISER P/1 ARE NOT VENTED. SECTION |
| 901.2.1. - A C/O IS REQUIRED AT THE BASE OF STACK P/1 |
| SECTION 708.3.4 - SHOW THE CONNECTION DETAIL AT THE |
| BASE OF STACK P/1 WITH A 4" CLEANOUT, A 4" CROSS, AND |
| 4" WYE FITTINGS INDICATING THE HEIGHT OF THE W/C |
| STUBOUT. - W/C-1 AT THE BASE OF STACK IS NOT VENTED. |
| SECTION 901.2.1. -W/C ON 2ND FLOOR IS NOT VENTED. |
| SECTION 901.2.1. - LAV ON 3RD FLOOR NOT VENTED. SECTION |
| 901.2.1. - INDICATE HOW/WHERE PIPING FOR LAVS & FLOOR |
| DRAINS CONNECT TO THE RISER/BRANCH ON THE 2ND, 3RD, & |
| 4TH FLOORS. THE FITTINGS INDICATE THAT THE PIPING IS |
| SLOPED TO THE LAVS. PLEASE CLARIFY. - MEN C4.104 DOES |
| NOT REFLECT ROOM NUMBER ON THE FLOOR PLAN. - PIPING FOR |
| FLOOR DRAINS & LAVS 4TH FLOOR DOES NOT REFLECT THE |
| FLOOR PLAN. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT 1ST FLOOR LAVS PIPING DOES NOT |
| REFLECT THE FLOOR PLAN. -A C/O IS REQUIRED AT THE |
| BASE OF STACK P/1 SECTION 708.3.4 - SHOW THE CONNECTION |
| DETAIL AT THE BASE OF STACK P/1 WITH A 4" CLEANOUT, A |
| 4" CROSS, AND 4" WYE FITTINGS INDICATING THE HEIGHT OF |
| THE W/C HOW THE CONNECTION DETAIL AT THE BASE OF STACK |
| P/1 WITH A 4" CLEANOUT, A 4" CROSS, AND 4" WYE FITTINGS |
| INDICATING THE HEIGHT OF THE W/C STUBOUT. - MEN C4.104 |
| DOES NOT REFLECT ROOM NUMBER ON THE FLOOR PLAN. - |
| PIPING FOR FLOOR DRAINS & LAVS 4TH FLOOR DOES NOT |
| REFLECT THE FLOOR PLAN. SECTION 106.1.1. THESE ITEMS |
| HAVE NOT BEEN ADDRESSED. |
| ******RESPONSE NOTED, BUT MEN'S C4.104 STILL DOES NOT |
| REFLECT THE ROOM NUMBER ON THE FLOOR PLAN.--NOW NO |
| SANITARY PIPING OR HOT WATER PIPING IS SHOWN ON THE |
| FLOOR PLAN OF THE ENLARGED FLOOR PLAN. PLEASE CLARIFY. |
| |
| 35B. ALL RISER DIAGRAMS, ALL FLOOR PLANS FOR ALL |
| SYSTEMS. INDICATE THE PIPE SIZE. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT MANY PIPE SIZES ARE NOT SHOWN |
| ON THE RISER DIAGRAMS. |
| ******RESPONSE NOTED, BUT THERE ARE MANY SECTIONS OF |
| SANITARY PIPING THAT HAVE NO PIPE SIZES. TABLES |
| 710.1(1) & 710.1(2). |
| |
| 36B. SHT P3-2.0 JANITOR ROOM PIPING DOES NOT REFLECT |
| THE FLOOR PLAN. - TRAPS REQUIRED ON ALL DRINKING |
| FOUNTAINS. SECTION 1002.1. - CLEANOUTS REQUIRED AT THE |
| BASE OF ALL STACKS. 708.3.4. - PIPING TO FLOOR DRAIN |
| SHOWN ABOVE THE FLOOR IN ROOM D1.101. PLEASE CLARIFY. - |
| PIPING AT THE BASE OF RISER P/2 DOES NOT REFLECT THE |
| FLOOR PLAN. - PIPING TO FD-2 AT THE LOADING D1.106 DOES |
| NOT REFLECT THE FLOOR PLAN. - PIPING FOR A1.108/A1.109 |
| DOES NOT REFLECT THE FLOOR PLAN. - ROOM D2.103 IS |
| INDICATED AS D2.104 ON THE FLOOR PLAN. CORRELATE |
| INFORMATION. - ALL VENTING AT RISER P/10 STOPS AT LEVEL |
| 2. SECTION 903.3 VTR REQUIRED. - TOILET ROOM A2.708 IS |
| INDICATED AS A2.706 ON THE FLOOR PLAN. CORRELATE |
| INFORMATION. - BATHROOM RISER DOES NOT REFLECT THE |
| FLOOR PLAN. (NO FD). - PIPING TO ROOM A4.414 DOES NOT |
| REFLECT THE FLOOR PLAN. - CLEANOUT PIPING DOWNSTREAM OF |
| C4.101 IS NOT APPROVED AS PIPED. SECTION 706.3. - |
| PIPING ON RISER DOES NOT REFLECT THE FLOOR PLAN |
| UPSTREAM OF C3.105. - JANITOR SINK C3.105 IS NOT |
| VENTED. SECTION 901.2.1. - FLOOR DRAIN CONNECTION AT |
| BRANCH LINE 4TH FLOOR DOES NOT REFLECT THE FLOOR PLAN. |
| - PIPING AT A2.107 DOES NOT REFLECT THE FLOOR PLAN. (NO |
| F.D. PIPING). - PIPING AT ROOM A3.111 DOES NOT REFLECT |
| THE FLOOR PLAN AT THE LAVS. - ROOM A3.111 SUBMIT A |
| DETAIL FOR FITTING TO W/C & LAVS. - ROOM D2.105 SHOWN |
| AS D2.106/D2.107 ON FLOOR PLANS. CORRELATE INFORMATION. |
| - ROOM C3.410/C3.412 FLOOR DRAIN FITTING ARE SHOWN TO |
| BE INSTALLED AGAINST THE FLOW. SECTION 706.3. - SECTION |
| 106.1.1. |
| ****RESPONSE NOTED, BUT SOME COMMENTS WERE NOT |
| ADDRESSED. SEE THE FOLLOWING: JANITOR ROOM PIPING DOES |
| NOT REFLECT THE FLOOR PLAN. - TRAPS REQUIRED ON ALL |
| DRINKING FOUNTAINS. SECTION 1002.1. - CLEANOUTS |
| REQUIRED AT THE BASE OF ALL STACKS. 708.3.4. - PIPING |
| TO FLOOR DRAIN SHOWN ABOVE THE FLOOR IN ROOM D1.101. |
| PLEASE CLARIFY.- PIPING AT THE BASE OF RISER P/2 DOES |
| NOT REFLECT THE FLOOR PLAN. - PIPING FOR A1.108/A1.109 |
| DOES NOT REFLECT THE FLOOR PLAN. - ROOM D2.103 IS |
| INDICATED AS D2.104 ON THE FLOOR PLAN. CORRELATE |
| INFORMATION.- TOILET ROOM A2.708 IS INDICATED AS |
| A2.706 ON THE FLOOR PLAN. CORRELATE INFORMATION. - |
| PIPING TO ROOM A4.414 DOES NOT REFLECT THE FLOOR PLAN. |
| - CLEANOUT PIPING DOWNSTREAM OF C4.101 IS NOT APPROVED |
| AS PIPED. SECTION 706.3. - PIPING AT ROOM A3.111 DOES |
| NOT REFLECT THE FLOOR PLAN AT THE LAVS. - ROOM A3.111 |
| SUBMIT A DETAIL FOR FITTING TO W/C & LAVS. - ROOM |
| D2.105 SHOWN AS D2.106/D2.107 ON FLOOR PLANS. CORRELATE |
| INFORMATION. |
| ******RESPONSE NOTED, BUT THE JANITOR ROOM PIPING DOES |
| NOT REFLECT THE FLOOR PLAN.--TOILET ROOM A2.708 IS |
| STILL INDICATED AS A2.706 ON THE FLOOR PLAN. CORRELATE |
| ROOM NUMBERS.--PIPING TO ROOM A4.414 DOES NOT |
| REFLECT THE FLOOR PLAN. RISER IS SHOWN AS A TRAVELING |
| OFFSET. FLOOR PLAN SHOWS THIS AS A STRAIGHT RISER. |
| PLEASE CLARIFY. |
| |
| 37B. SHT P3-3.0 PIPING TO A3.304 & DOWNSTREAM DOES NOT |
| REFLECT THE FLOOR PLAN. - VENT PIPING FROM S-1 SINK |
| DOES NOT REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN. - |
| TRAPS REQUIRED ON ALL DRINKING FOUNTAINS. SECTION |
| 1002.1. - S-1 SINK SHALL NOT DRAIN THRU THE WET VENT OF |
| THE TOILET ROOM A1.303. SINK SHALL DISCHARGE DOWNSTREAM |
| OF THE W/C & LAV. SECTION 909.1. - INDICATE P/8 WITH |
| P/6 AT THE BASE OF THE STACK WHERE IT BEGINS. - PIPING |
| TO ROOMS A1.105/A1.106 DOES NOT REFLECT THE FLOOR PLAN. |
| FLOOR DRAIN PIPING IS SHOWN AS ABOVE THE FLOOR. - P/5 & |
| P/9 BEGIN AT THE BASE OF THE STACK. PLEASE INDICATE ON |
| RISER DIAGRAM. - PIPING FOR A3.102/A3.103 DOES NOT |
| REFLECT THE FLOOR PLAN. - CLEANOUT REQUIRED AT THE BASE |
| OF P/9 STACK. - PIPING TO FLOOR DRAINS IN ROOMS |
| A3.102/A3.103 ARE ABOVE THE FLOOR. -W/C AT THE BASE |
| OF STACK NOT VENTED. SECTION 901.2.1. - INDICATE WHERE |
| LINES TO FLOOR DRAINS IN ROOMS A4.103/A4.104 & |
| A5.103/A5.104 ARE CONNECTING TO THE BRANCH/STACK. - |
| PIPING FOR A4.103/A4.104 DOES NOT REFLECT THE FLOOR |
| PLAN. - W/C AT RISER STACK A4.103 IS NOT VENTED. |
| SECTION 901.2.1. - PIPING FOR A4.105 DOES NOT REFLECT |
| THE FLOOR PLAN. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT |
| ADDRESSED:-PIPING TO A3.304 & DOWNSTREAM DOES NOT |
| REFLECT THE FLOOR PLAN. - VENT PIPING FROM S-1 SINK |
| DOES NOT REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN. - |
| PIPING TO ROOMS A1.105/A1.106 DOES NOT REFLECT THE |
| FLOOR PLAN. FLOOR DRAIN PIPING IS SHOWN AS ABOVE THE |
| FLOOR. -PIPING FOR A4.103/A4.104 DOES NOT REFLECT THE |
| FLOOR PLAN. - W/C AT RISER STACK A4.103 IS NOT VENTED. |
| SECTION 901.2.1. - PIPING FOR A4.105 DOES NOT REFLECT |
| THE FLOOR PLAN. SECTION 106.1.1. |
| ******RESPONSE NOTED, BUT THE PIPING TO A3.304 & |
| DOWNSTREAM DOES NOT REFLECT THE FLOOR PLAN. CORRELATE |
| RISER & FLOOR PLAN.--VENT PIPING FROM S-1 SINK |
| STILL DOES NOT REFLECT THE FLOOR PLAN. CORRELATE RISER |
| AND FLOOR PLAN. |
| |
| 38B. OK |
| |
| 39B. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING |
| INFORMATION IS REQUIRED FOR THE GAS PERMIT: |
| |
| A. OK |
| B. OK |
| C. OK |
| D. OK |
| |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| ****RESPONSE NOTED, BUT NOT ADDRESSED. ******RESPONSE |
| NOTED, BUT THE SIZING OF THE PIPE SHALL BE TO THE MOST |
| REMOTE APPLIANCE/GENERATOR. PLEASE INDICATE THE TOTAL |
| DEVELOPED LENGTH TO THE MOST REMOTE FUTURE GENERATOR. |
| |
| F. OK |
| |
| G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| ****RESPONSE NOTED, BUT NO MANUF. SHEETS FOR THE |
| GENERATOR HAS BEEN SUBMITTED. - ALSO SUBMIT THE MANUF. |
| SPECIFICATION SHEETS FOR THE GAS REGULATORS. INDICATE |
| MODEL NUMBER. LISTING INFORMATION REQUIRED. |
| ******RESPONSE NOTED, BUT THE BTU LOAD FOR THE NATURAL |
| GAS @ 100% LOAD IS NOT INDICATED ON THE MANUF. |
| SPECIFICATION SHEETS. THIS SHALL BE SHOWN TO VERIFY |
| PIPE SIZING. |
| |
| H. NA |
| I. NA |
| |
| 40B. SHT P3-5.0 NO HOT WATER LINE SHOWN IN 1ST THRU 4TH |
| FLOOR TOILET ROOMS OFF WATER RISER W/1. - WATER RISER |
| DOES NOT REFLECT THE FLOOR PLAN AT THE LAVS. - FULL |
| OPEN VALVES ARE REQUIRED ON ALL WATER DOWN-FEED LINES. |
| SECTION 606.1(4). - RISER DOES NOT REFLECT THE FLOOR |
| PLAN AT ROOMS C2.102/C2.103. (2 LAVS SHOWN EACH TOILET |
| ROOM). - PIPE SIZE SUPPLYING ROOMS D1.101/D1.102, |
| JANITOR ROOM D1.110, TOILET ROOMS A1.108/A1.109. - |
| INDICATE THAT RISERS W/4, W/5, & W/8 RISERS START WITH |
| RISER W/2 ON THE 1ST FLOOR. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT |
| ADDRESSED: - WATER RISER DOES NOT REFLECT THE FLOOR |
| PLAN AT THE LAVS. - FULL OPEN VALVES ARE REQUIRED ON |
| ALL WATER DOWN-FEED LINES. SECTION 606.1(4). (MANY |
| LAVS, TOILET ROOMS, SINKS ETC MISSING VALVES).- RISER |
| DOES NOT REFLECT THE FLOOR PLAN AT ROOMS C2.102/C2.103. |
| (2 LAVS SHOWN EACH TOILET ROOM). - PIPE SIZE SUPPLYING |
| ROOMS D1.101/D1.102, JANITOR ROOM D1.110, TOILET ROOMS |
| A1.108/A1.109. (2" SHOWN ON FLOOR PLAN, 1-1/2" ON |
| RISER. 3/4" ON FLOOR PLAN, 1/2" ON RISER.SOME LAVS |
| SHOW SEPARATE DROPS TO EACH LAV ON THE FLOOR PLAN, BUT |
| SINGLE DROPS ON THE RISER). - INDICATE THAT RISERW/8 |
| STARTS WITH RISER W/2 ON THE 1ST FLOOR. SECTION |
| 106.1.1. |
| ******RESPONSE NOTED, BUT THE SIZE OF THE SUPPLY PIPING |
| TO THE JANITOR ROOM D1.110 DOES NOT REFLECT THE FLOOR |
| PLAN, AS WELL AS THE PIPE SIZE SUPPLYING TOILET ROOMS |
| A1.108/A1.109. PLEASE CORRELATE THE RISER AND FLOOR |
| PLAN. |
| |
| 41B. SHT P3-6.0 RISERS 4, 5 & 8 ARE NOT INDICATED ON |
| THE 1ST FLOOR. - RISER DOES NOT REFLECT THE FLOOR PLAN |
| ROOMS C3.107/C3.108 AT JAN. SINK, ROOMS C3.410/C3.412, |
| AE.111, A4.103/A4.104, A4.105 AND THE TOP OF RISER W/4 |
| TO ROOM A5.105, PIPE SIZE AT ROOM A2.209 & SUPPLY TO |
| TOILET ROOM ADJACENT, PIPE SIZE SUPPLYING RISER W/8 & |
| RISER, SUPPLY LINE TO ROOMS D2.102/D2.103. - W/2 NOT |
| FOUND ON 4TH FLOOR AS INDICATED ON RISER. SECTION |
| 106.1.1. |
| ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT |
| ADDRESSSED: RISER 8 STILL NOT INDICATED ON THE 1ST |
| FLOOR. - RISER DOES NOT REFLECT THE FLOOR PLAN ROOMS |
| C3.410/C3.412,A4.103/A4.104, (FLOOR PLAN INDICATES |
| OVER-HEAD SUPPLY WITH DROPS, BUT RISER INDICATES SUPPLY |
| RUN IN THE WALL OFF WATER RISER. TWO W/C'S MISSING ON |
| RISER).-PIPE SIZE AT ROOM A2.209, (SHOWS 1" ON THE |
| FLOOR PLAN), - PIPE SIZE SUPPLYING RISER W/8 & RISER, ( |
| 1" ON FLOOR PLAN, 2" ON RISER - 1-1/2" ON THE FLOOR |
| PLAN, BUT 2" ON THE RISER). -W/2 NOT FOUND ON 4TH OR |
| 5TH FLOORS AS INDICATED ON RISER. SECTION 106.1.1. |
| PLEASE CORRELATE RISER AND FLOOR PLANS. ******RESPONSE |
| NOTED, BUT THE RISER STILL DOES NOT REFLECT THE FLOOR |
| PLAN, NOR DOES IT REFLECT THE PIPE SIZING FOR THE HOT |
| SUPPLY TO TOILET ROOMS C3.410/C3.412.--TOILET ROOMS |
| A4.103/A4.104 WATER PIPING STILL DOES NOT REFLECT THE |
| FLOOR PLAN.--PIPE SIZE SUPPLYING RISER W/8 STILL |
| DOES NOT REFLECT THE FLOOR PLAN. CHECK PIPING |
| DOWNSTREAM OF RISER W/8 AND CORRELATE PIPING BETWEEN |
| THE RISER AND THE FLOOR PLAN. |
| |
| 42B. SHT P3-7.0 SIZE ALL PIPE PER SECTION 1106.3, AND |
| SHOW ALL PIPE SIZES ON THE RISER. - RISER DOES NOT |
| REFLECT THE FLOOR PLAN TOP FLOORS RWL/6 & RWL/7. - |
| RISERS INDICATE A 5TH FLOOR, BUT FLOOR PLAN DOES NOT |
| SHOW A 5TH FLOOR. - RISER SHOWS TRENCH DRAINS ON TWO |
| FLOORS, BUT ONLY SHOW TRENCH DRAINS ON 1 FLOOR, (ROOF |
| LEVEL), ON THE FLOOR PLAN. -RWL'S 9 THRU 14 SHOW OFFSET |
| PIPING FOR ROOF DRAINS IN THE 4TH FLOOR CEILING, BUT |
| INDICATE THE ROOF DRAINS TO BE ON THE 4TH LEVEL. PLEASE |
| CLARIFY. - PIPE SIZING IS INCORRECT AT 8"/11,715SF, |
| 6"/5077SF, 6"/6657SF. TABLE 1106.3. - RWL/9 INDICATES |
| PIPING IN 3RD FLOOR CEILING, BUT ROOF DRAINS ARE TO BE |
| ON THE 3RD LEVEL. PLEASE CLARIFY. - RWL/15 DOES NOT |
| REFLECT THE FLOOR PLAN TO 4" ROOF DRAINS. - PIPING AT |
| THE 1ST FLOOR CEILING CONNECTING TO ROOF DRAINS ON THE |
| 1ST LEVEL. PLEASE CLARIFY. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT SOME COMMENTS THE FOLLOWING |
| COMMENTS WERE NOT ADDRESSED:- RISER DOES NOT REFLECT |
| THE FLOOR PLAN TOP FLOORS RWL/6 & RWL/7. - RISERS |
| INDICATE A 5TH FLOOR, BUT FLOOR PLAN DOES NOT SHOW A |
| 5TH FLOOR. - RISER SHOWS TRENCH DRAINS ON TWO FLOORS, |
| BUT ONLY SHOW TRENCH DRAINS ON 1 FLOOR, (ROOF LEVEL), |
| ON THE FLOOR PLAN. - PIPE SIZING IS INCORRECT AT |
| 8"/11,715SF, 6"/5077SF, 6"/6657SF. TABLE 1106.3. |
| ******RESPONSE NOTED, BUT I STILL HAVE QUESTIONS AS TO |
| THE TRENCH DRAINS. IT SEEMS ON THE RISER DIAGRAM THAT |
| THE UPPER TRENCH DRAINS ARE SHOWN AT THE WRONG |
| ELEVATIONS. THERE IS NO LEVEL ABOVE THE 5TH LEVEL FOR |
| RWL 7 & THE AREA DRAINS FOR THE ROOF ON RWL 6COLLECT |
| THE ROOF AREA. SHOULDN'T THE TRENCH DRAINS BE AT THE |
| BOTTOM OF THE RAMPS BELOW THE ROOF AREAS. PLEASE |
| CLARIFY. |
| |
| 43B. SHTS 1,2,3 OF 3 ARE NOT SIGNED, SEALED, & DATED AS |
| REQUIRED PER FS 472.025(1). ALSO SEE SHT 1 WHICH STATES |
| "NOT VALID UNLESS SEALED WITH SURVEYOR'S EMBOSSED SEAL |
| AND SIGNATURE" |
| ****NO RESPONSE, NOT ADDRESSED. |
| ******RESPONSE NOTED, BUT SHTS 2 & 3 ARE NOT SIGNED, |
| SEALED, DATED. IF THE DESIGN PROFESSIONAL IS AN |
| ARCHITECT OR ENGINEER LEGALLY RESISTERED UNDER THE LAWS |
| OF THIS STATE REGULATING THE PRACTICE OF ARCHITECTURE |
| AS PROVIDED FOR IN CHAPTER 481, FLORIDA STATUTES, PART |
| I,OR ENGINEERING AS PROVIDED FOR IN CHAPTER 471, |
| FLORIDA STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA AS REQUIRED BY |
| FLORIDA STATUTES. SECTION 106.1. |
| |
| 44B. SHTS C1, C5 THRU C22 ENGINEERING CERTIFICATE OF |
| AUTHORIZTION IS REQUIRED IN THE TITLE BLOCK. |
| 61G15-23.002(2) & FS 471.025. - AN EMBOSSED SEAL IS |
| REQUIRED TO IMPRESS REQUIRED INFORMATION ON EACH SHEET. |
| UNABLE TO GLEAN ALL INFORMATION REQUIRED FROM SEAL. |
| PLEASE RESEAL PLANS. |
| ****NO RESPONSE, NOT ADDRESSED. |
| ******NO RESPONSE, NOT ADDRESSED. |
| |
| 45B. OK |
| 46B. OK |
| 47B. OK |
| 48B. OK |
| |
| 49B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 3RD |
| FLOOR DRINKING FOUNTAINS SHOW ONLY 3 ARE REQUIRED. PER |
| TABLE 403.1, 4 DRINKING FOUNTAINS ARE REQUIRED. PLEASE |
| UPDATE FIXTURE COUNT. |
| ****NO RESPONSE, NOT ADDRESSED. |
| *****RESPONSE NOTED, NO CHANGE NOTED, NOT ADDRESSED |
| |
| 50B. OK |
| |
| 51B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 1ST |
| FLOOR DRINKING FOUNTAINS 2 REQUIRED PER TABLE 403.1, |
| BUT READS 1 REQUIRED. PLEASE CORRECT FIXTURE COUNT |
| REQUIRED. |
| ****NO RESPONSE, NOT ADDRESSED. |
| ******RESPONSE NOTED, NO CHANGE, NOT ADDRESSED. |
| |
| 52B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 3RD |
| FLOOR DRINKING FOUNTAINS 4 REQUIRED PER TABLE 403.1, |
| BUT READS 2 REQUIRED. PLEASE CORRECT FIXTURE COUNT |
| REQUIRED. - SHOWS 2 PROVIDED, BUT 4 ARE REQUIRED. |
| PLEASE CORRECT INFORMATION. |
| ****NO RESPONSE, NOT ADDRESSED. |
| ******RESPONSE NOTED, NOW SHOWS 3 REQUIRED, 4 DRINKING |
| FOUNTAINS ARE REQUIRED. NOT ADDRESSED. |
| |
| 53B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 4TH |
| FLOOR LAVS REQUIRED 2, INDICATED AS 1. PLEASE CORRECT |
| THE FIXTURE COUNT. TABLE 403.1. |
| ****NO RESPONSE, NOT ADDRESSED. |
| ******RESPONSE NOTED, NO CHANGE, NOT ADDRESSED. |
| |
| 54B. OK |
| |
| 55B. SHT LSO.0 INDICATES ASSEMBLY OCCUPANCY FOR THE |
| CITY HALL AND LIBRARY/MUSEUM. POTTY PARITY IS REQUIRED |
| PER SECTION 403.1.1 AND HAS BEEN INDICATED IN THE 50% |
| REVIEW BY PAUL SCHMITZ. THIS HAS NOT BEEN ADDRESSED. |
| PLEASE SHOW COMPLIANCE WITH THIS REQUIREMENT. ****NO |
| RESPONSE, NOT ADDRESSED. |
| ******RESPONSE NOTED, BUT POTTY PARITY HAS NOT BEEN |
| ADDRESSED, THERE IS NO 3:2 RATIO AS REQUIRED. THERE IS |
| A 1:1 RATIO. THE SECTION OF THE CODE REFERENCED DOES |
| NOT SAY THAT IF THERE IS A DIFFERENCE OF 2 OR MORE |
| WATER CLOSETS FOR WOMEN PARITY IS AUTOMATICALLY |
| ACHIEVED.IT STATES "UNLESS THERE ARE 2 OR FEWER |
| FIXTURES FOR MEN". THIS MEANS THAT IF THE OCCUPANCY IS |
| SMALL ENOUGH TO ONLY REQUIRE 2 FIXTURES FOR THE MEN, |
| THEN POTTY PARITY IS NOT REQUIRED. NO MENTION OF POTTY |
| PARITY FOR CITY HALL ASSEMBLY HAS BEEN MENTIONED IN THE |
| RESPONSE. PLEASE INDICATE HOW POTTY PARITY WILL BE |
| COMPLIED WITH. |
| |
| 56B. OK |
| 57B. OK |
| 58B. OK |
| 59B. OK |
| 60B. OK |
| 61B. OK |
| 62B. OK |
| |
| 63B. SHT A6-1.1 DETAIL 7, ACCESSIBLE W/C SHALL BE 1'6" |
| OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG. |
| 11-28. (SHOWS 2'2"). |
| ****NO RESPONSE, NOT ADDRESSED. |
| ******RESPONSE NOTED, NO CHANGE, NOT ADDRESSED |
| |
| 64B. OK |
| 65B. OK |
| 66B. OK |
| 67B. OK |
| 68B. OK |
| 69B. OK |
| |
| 70B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS |
| C1.105, C1.106, A2.705, A2.706, A2.210, A2.211, A3.111, |
| A3.114, C3.410, AND C3.412 ALL INDICATE THE WALLS TO BE |
| PAINTED. PLEASE INDICATE HOW THIS COMPLIES WITH THE |
| REQUIREMENT FOR "SMOOTH, HARD, NONABSORBENT WALLS AS |
| REQUIRED IN SECTION 1210.2. |
| ****NO RESPONSE, NOT ADDRESSED. |
| ******RESPONSE NOTED, BUT EPOXY DOES NOT COMPLY WITH |
| THE REQUIREMENT FOR THE SURFACE TO BE HARD.--PLEASE |
| INDICATE WHAT PNT-5, CT 2-5 MEANS. THE FLOOR AND BASE |
| HAVE BEEN INDICATE AS CT. DOES THE CT 2-5 MEAN THAT THE |
| CERAMIC TILE WILL START AT 2' AND EXTEND UP TO 5'? IF |
| SO, WILL THE BASE BE 2' WIDE? PLEASE CLARIFY AS THERE |
| IS NO FINISH LEGNED WITH THE NUMBER DESIGNATIONS AFTER |
| THE MATERIAL. (PNT-5 OR CT 2-5). |
| |
| 71B. OK |
| |
| 72B. SHT A9-4.1 INDICATE THE ROOM NUMBERS THAT THE |
| DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE |
| FOLLOWING: |
| A. 11-4.18.4 FLUSH CONTROLS |
| B. 11-4.19.2 CLEARANCES |
| C. 11-4.19.4 EXPOSED PIPES & CLEARANCES |
| ****NO RESPONSE, NOT ADDRESSED. |
| ******RESPONSE NOTED, BUT THE CONTROL HEIGHT FOR THE |
| URINAL IS NOT INDICATED. |
| |
| 73B. SHT A9-4.2 INDICATE THE ROOM NUMBERS THAT THE |
| DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE |
| FOLLOWING: |
| DETAIL #1 |
| A. 11-4.18.4 FLUSH CONTROLS |
| B. 11-4.19.2 CLEARANCES |
| C. 11-4.19.4 EXPOSED PIPES & CLEARANCES |
| ****NO RESPONSE, NOT ADDRESSED. |
| ******RESPONSE NOTED, BUT THE CONTROL HEIGHT FOR THE |
| URINAL IS NOT INDICATED. |
| |
| DETAIL #2 |
| A. 11-4.18.4 FLUSH CONTROLS |
| B. 11-4.19.2 CLEARANCES |
| C. 11-4.19.4 EXPOSED PIPES & CLEARANCES |
| ****NO RESPONSE, NOT ADDRESSED. |
| ******RESPONSE NOTED, BUT THE CONTROL HEIGHT FOR THE |
| URINAL IS NOT INDICATED. |
| |
| 74B. OK |
| |
| 75B. SHT A9-4.5 DETAILS (1) & (2), SHOW THE FOLLOWING |
| FOR COMPLIANCE:A. 11-4.19.2 CLEARANCES |
| B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| C. 11-4.19.5 FAUCETS |
| D. 11-4.21.5 CONTROLS |
| E. 11-4.21.7 CURBS |
| ****NO RESPONSE, NOT ADDRESSED. |
| ******RESPONSE NOTED, BUT THE HEIGHT FOR THE CONTROLS |
| IN THE SHOWER ARE NOT INDICATED. |
| |
| 76B. SHTS A1.307, A1.709, A2.209, A2.315, A2.407, |
| A3.109, C3.409, C3.310, A5.504 - SHOW COMPLIANCE WITH |
| THE FOLLOWING |
| A. 11-4.24.4 SINK DEPTH |
| B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH |
| REQUIRED) |
| C. 11-4.24.6 EXPOSED PIPES & SURFACES |
| D. 11-4.24.7 FAUCETS |
| ****NO RESPONSE, NOT ADDRESSED. |
| ******RESPONSE NOTED, BUT THE FAUCETS WERE NOT |
| ADDRESSED. |
| |
| *************NEW COMMENTS************* |
| |
| 1C. SHTA9-4.6 DETAILS 1 & 2 SHOW COMPLIANCE WITH THE |
| FOLLOWING: |
| A. 11-4.18.4 FLUSH CONTROLS |
| B. 11-4.19.2 CLEARANCES |
| C. 11-4.19.4 EXPOSED PIPES & SURFACES ******RESPONSE |
| NOTED, BUT THE SHEET NUMBER WAS A TYPO. THIS IS |
| REQUIRED ON SHT A9-4.6. |
| |
| 2C. SHT A9-4.7 DETAILS 1, 2, & 3 SHOW COMPLIANCE WITH |
| THE FOLLOWING: |
| A. 11-4.18.4 FLUSH CONTROLS |
| B. 11-4.19.2 CLEARANCES |
| C. 11-4.19.4 EXPOSED PIPES & SURFACES ******RESPONSE |
| NOTED, BUT THE SHEET NUMBER WAS A TYPO. THIS IS |
| REQUIRED ON SHT A-04.7. |
| |
| 3C. SHT P1-6.0 THE FOLLOWING VENTS ARE NOT SHOWN ON THE |
| ROOF. P1, P2, P3, & P10. PLEASE SHOW ON THIS SHEET OR |
| INDICATE WHERE THEY ARE SHOWN. SECTION 106.1.1. |
| ******RESPONSE NOTED, BUT VTR P2 IS NOT INDICATED AND |
| SHOULD BE LOCATED AT OR NEAR COL. LINE H/2 AS THE RISER |
| DIAGRAM INDICATES THE VENT WITH NO OFFSETS. |
| |
| **************NEW COMMENTS************* |
| |
| 1D. SHT P3-2.0, 1ST FLOOR VENTING FOR THE WATER CLOSETS |
| AT THE BASE OF RISER P10 IS NOT SHOWN. SECTION |
| 901.2.1. |
| |
| 2D. SHT P2-1.0 DETAILS 1 THRU 5. THE SANITARY PIPING IS |
| NOT SHOWN ON THE ENLARGED PLANS. ALSO CHECK FOR BOTH |
| HOT AND COLD WATER LINES. SECTION 106.1.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. SUBMITTING THE RED |
| LINED SET OF PLUMBING SHEETS WHEN RESUBMITTING FOR |
| REVIEW WILL HELP EXPEDITE THE PERMIT ALSO. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| |