Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop M
Sequence Number 3
Notes
Date Text
2007-01-27 11:01:42PROVISO:
  
 1.NON-HABITABLE ROOMS (I.E., STORAGE, ELECTRICAL,
 ETC.)ARE NOT REQUIRED TO COMPLY WITH 2004 FMC 601.4
 EXCEPTION #3.PLEASE ALSO NOTE, RETURN AIR GRILLES ARE
 INDICATED IN THESE ROOMS AND THE ARCHITECTURAL PLANS
 INDICATE NO CEILING.PLEASE REMOVE R/A GRILLES FROM
 THESE AREAS.
  
 2.PUMP ROOM A1.112 INDICATES A TRANSFER FROM THE PUMP
 ROOM INTO THE FILE ROOM.PER 2004 FMC 502.1.3,
 EQUIPMENT ROOMS THAT HOUSE SOURCES OF FUMES, ODERS OR
 NOXIOUS GASES SHALL BE DESIGNED TO AND CONSTRUCTED SO
 AS TO PREVENT SPREADING OF SUCH CONTAMINANTS TO OTHER
 OCCUPIED PARTS OF THE BUILDING.
  
 3.PLEASE PROVIDE DUCT SIZES TO VAV'S.
  
 4.MANY OF THE NON-HABITABLE ROOMS INDICATE RETURN AIR
 GRILLES TO THE PLENUM.ACCORDING TO THE ARCHITECTURAL
 DRAWINGS THESE ROOMS HAVE NO CEILING.PLEASE REMOVE
 RETURN AIR GRILLES FROM THESE AREAS IF IN FACT THEY DO
 NOT GO INTO THE RETURN AIR PLENUM.
  
 5.ADDITIONAL PERMITS REQUIRED FOR FUEL PIPING.
  
 PLEASE SEE ELECTRICAL COMMENTS FOR SIZING OF THE DIESEL
 FUEL TANKS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT HAROLD MOSER
 AT (561)805-6732 OR E-MAIL [email protected].