Plan Review Notes For Permit 06100574 |
Permit Number |
06100574 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-01-27 11:01:42 | PROVISO: | | | | 1.NON-HABITABLE ROOMS (I.E., STORAGE, ELECTRICAL, | | ETC.)ARE NOT REQUIRED TO COMPLY WITH 2004 FMC 601.4 | | EXCEPTION #3.PLEASE ALSO NOTE, RETURN AIR GRILLES ARE | | INDICATED IN THESE ROOMS AND THE ARCHITECTURAL PLANS | | INDICATE NO CEILING.PLEASE REMOVE R/A GRILLES FROM | | THESE AREAS. | | | | 2.PUMP ROOM A1.112 INDICATES A TRANSFER FROM THE PUMP | | ROOM INTO THE FILE ROOM.PER 2004 FMC 502.1.3, | | EQUIPMENT ROOMS THAT HOUSE SOURCES OF FUMES, ODERS OR | | NOXIOUS GASES SHALL BE DESIGNED TO AND CONSTRUCTED SO | | AS TO PREVENT SPREADING OF SUCH CONTAMINANTS TO OTHER | | OCCUPIED PARTS OF THE BUILDING. | | | | 3.PLEASE PROVIDE DUCT SIZES TO VAV'S. | | | | 4.MANY OF THE NON-HABITABLE ROOMS INDICATE RETURN AIR | | GRILLES TO THE PLENUM.ACCORDING TO THE ARCHITECTURAL | | DRAWINGS THESE ROOMS HAVE NO CEILING.PLEASE REMOVE | | RETURN AIR GRILLES FROM THESE AREAS IF IN FACT THEY DO | | NOT GO INTO THE RETURN AIR PLENUM. | | | | 5.ADDITIONAL PERMITS REQUIRED FOR FUEL PIPING. | | | | PLEASE SEE ELECTRICAL COMMENTS FOR SIZING OF THE DIESEL | | FUEL TANKS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT HAROLD MOSER | | AT (561)805-6732 OR E-MAIL [email protected]. |
|