Plan Review Notes For Permit 06100574 |
Permit Number |
06100574 |
|
Review Stop |
G |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-01-31 11:04:09 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | FROM PREVIOUS REVIEWS: | | | | 39B. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING | | INFORMATION IS REQUIRED FOR THE GAS PERMIT: | | | | A. OK | | B. OK | | C. OK | | D. OK | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | ****RESPONSE NOTED, BUT NOT ADDRESSED. ******RESPONSE | | NOTED, BUT THE SIZING OF THE PIPE SHALL BE TO THE MOST | | REMOTE APPLIANCE/GENERATOR. PLEASE INDICATE THE TOTAL | | DEVELOPED LENGTH TO THE MOST REMOTE FUTURE GENERATOR. | | | | F. OK | | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | ****RESPONSE NOTED, BUT NO MANUF. SHEETS FOR THE | | GENERATOR HAS BEEN SUBMITTED. - ALSO SUBMIT THE MANUF. | | SPECIFICATION SHEETS FOR THE GAS REGULATORS. INDICATE | | MODEL NUMBER. LISTING INFORMATION REQUIRED. | | ******RESPONSE NOTED, BUT THE BTU LOAD FOR THE NATURAL | | GAS @ 100% LOAD IS NOT INDICATED ON THE MANUF. | | SPECIFICATION SHEETS. THIS SHALL BE SHOWN TO VERIFY | | PIPE SIZING. | | | | H. NA | | I. NA | | |
|