2007-01-26 13:36:28 | 1. SIAMESE CONNECTION DISPLAYED ON PAGE FP1-1.2 IS NOT |
| NEEDED AND SHOULD BE STRICKEN FROM THE PLANS. THE PLAN |
| REVIEW PERMIT RESPONSES INCLUDE NOW THREE SIAMSE |
| CONNECTIONS INSTEAD OF THE FIVE PREVIOUSLY SHOWN. 2. NO |
| FIRE ALARM EQUIPMENT SHOWN IN MACHINE ROOM A6.102 ON |
| PAGE FA1-6.0. THIS IS AN EXISTING COMMENT. |
| 3. ONLY TWO FIRE ALARM STROBES ARE PRESENT IN THE |
| GARAGE ON PAGE FA1-6.0. THIS IS ALSO AN EXISTING |
| COMMENT. |
| 4. SMOKE DETECTOR STILL MISISNG IN VOICE DATA CLOSET |
| C3.104 ON PAGE FA1-3.0. THIS IS AN EXISTING COMMENT. 5. |
| A VISUAL REPRESENTATION OF THE SMOKE CONTROL PANEL |
| SHALL BE SUBMITTED AT TIME OF SHOP DRAWING SUBMITTAL. |
| THIS SMOKE CONTROL PANEL SHALL DISPLAY A GRAPHIC |
| REPRESENTATION OF THE BUILDING SYSTEM TO INCLUDE HAND, |
| ON, AND AUTO CONTROLS. |
| 6. ITEMS # 9, 11, 12, 20, 23, COULD NOT BE CLEARED FRON |
| LIST. SOME ITEMS CAN BE PICKED UP AT SHOP DRAWING |
| SUBMITAL TIME SO LONG AS THEY ARE PROPERLY IDENTIFIED. |
| 7. ALL ELECTRICAL PLAN REVIEW COMMENTS ARE TO BE |
| PROPERLY SATISFIED WITH THE ELECTRICAL PLAN REVIEWER. |
| 8. PLEASE REMEMBER THAT THE ELVATION OF FLOOR LEVELS ON |
| BOTH SIDES OF AN EXIT DOOR CANNOT EXCEED 1/2 ". |
| |
| PLANS WILL BE APPROVED PROVISO AND ALL WORK AT THE SITE |
| IS SUBJECT TO FIELD INSPECTION AND APPROVAL. THIS |
| APPROVAL DOES NOT RELLIEVE RESPONSIBLE PERSONS OR FIRMS |
| FROM OBTAINING ANY OTHER GOVERNMENTAL REVIEWS OR |
| APPROVALS. |