Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2007-01-26 13:36:281. SIAMESE CONNECTION DISPLAYED ON PAGE FP1-1.2 IS NOT
 NEEDED AND SHOULD BE STRICKEN FROM THE PLANS. THE PLAN
 REVIEW PERMIT RESPONSES INCLUDE NOW THREE SIAMSE
 CONNECTIONS INSTEAD OF THE FIVE PREVIOUSLY SHOWN. 2. NO
 FIRE ALARM EQUIPMENT SHOWN IN MACHINE ROOM A6.102 ON
 PAGE FA1-6.0. THIS IS AN EXISTING COMMENT.
 3. ONLY TWO FIRE ALARM STROBES ARE PRESENT IN THE
 GARAGE ON PAGE FA1-6.0. THIS IS ALSO AN EXISTING
 COMMENT.
 4. SMOKE DETECTOR STILL MISISNG IN VOICE DATA CLOSET
 C3.104 ON PAGE FA1-3.0. THIS IS AN EXISTING COMMENT. 5.
 A VISUAL REPRESENTATION OF THE SMOKE CONTROL PANEL
 SHALL BE SUBMITTED AT TIME OF SHOP DRAWING SUBMITTAL.
 THIS SMOKE CONTROL PANEL SHALL DISPLAY A GRAPHIC
 REPRESENTATION OF THE BUILDING SYSTEM TO INCLUDE HAND,
 ON, AND AUTO CONTROLS.
 6. ITEMS # 9, 11, 12, 20, 23, COULD NOT BE CLEARED FRON
 LIST. SOME ITEMS CAN BE PICKED UP AT SHOP DRAWING
 SUBMITAL TIME SO LONG AS THEY ARE PROPERLY IDENTIFIED.
 7. ALL ELECTRICAL PLAN REVIEW COMMENTS ARE TO BE
 PROPERLY SATISFIED WITH THE ELECTRICAL PLAN REVIEWER.
 8. PLEASE REMEMBER THAT THE ELVATION OF FLOOR LEVELS ON
 BOTH SIDES OF AN EXIT DOOR CANNOT EXCEED 1/2 ".
  
 PLANS WILL BE APPROVED PROVISO AND ALL WORK AT THE SITE
 IS SUBJECT TO FIELD INSPECTION AND APPROVAL. THIS
 APPROVAL DOES NOT RELLIEVE RESPONSIBLE PERSONS OR FIRMS
 FROM OBTAINING ANY OTHER GOVERNMENTAL REVIEWS OR
 APPROVALS.