2007-01-22 10:07:222007-01-22 10:07:22
  
 ** UNSAT **
  
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEW STILL NEED TO
 BE ADDRESSED.
  
 ** PLEASE SEE THE NOTES BELOW WILL AFFECT NUMEROUS
 SHEETS WHICH WILL BE REQUIRED TO BE REVISED.
  
 ** PLEASE SEE PREVIOUS NOTES WHICH MENTIONED SOME OF
 THE COMMENTS WERE *REDLINED* ON PLANS; HOWEVER WERE IN
 NO WAY ALL LOCATIONS OR ITEMS. PLEASE SEE ONCE AGAIN
 THE PLANS CONTAIN CIRCLES AROUND AREAS IN WHICH
 COMMENTS ARE MADE.
 PLEASE SEE COMMENTS AS MANY OF THE OLD SHEETS WERE
 SUBMITTED BACK IN SETS WITHOUT BEING REVISED.
  
  
 1) NOTE: PLEASE CORRELATE FP SHEETS WITH THE
 SUBMITTALS. PLEASE SEE THE FP SHEET STILL INDICATES AN
 ELECTRIC FIRE PUMP FOR ONE OF THE PUMPS. THIS IS THE
 6TH TIME THIS COMMENT HAS BEEN MADE. THIS COMMENT WAS
 MADE ON THE 50%, 90%, 1ST 100%,2ND 100%(FIRST UNDER
 PERMIT) AND 2ND SUBMITTAL UNDER PERMIT AND NOW THIS
 REVIEW.
 PLEASE SEE THE SIZES OF THE FIRE PUMPS ON PLANS DO NOT
 CORRELATE WITH THE SUBMITTALS.
 PLEASE SEE THE SIZE OF ONE OF THE TANKS FOR ONE OF THE
 FIRE PUMPS HAS NOW CHANGED TO A *00*SIZE TANK. PLEASE
 SEE THE HP RATING OF ONE OF THE PUMPS HAS NOW CHANGED
 AND DOES NOT CORRELATE WITH THE SUBMITTALS. PLEASE SEE
 THE TYPE AND MANUFACTURE OF THE FIRE PUMP CONTROLLERS
 STILL DO NOT CORRELATE.
 PLEASE SEE THE SUBMITTAL BOOKS CONTAIN MULTIPLE SPECS
 FOR THE TANKS. PLEASE KNOW IF NEW TANKS AND SIZES ARE
 GOING TO BE USED, DO NOT LEAVE THE OLD SUBMITTALS IN,
 IF THEY ARE INDEED OLD.
 PLEASE CORRELATE ALL OF THE ABOVE AND PLEASE CORRECT
 FP0-1.0.
 90.7, 110.3, 695 NEC.
 2003 NFPA-20 CHAPTER 9 AND 10.
 FBC ADMIN SECTION 106.1, 106.1.2, 106.3.5.1.2
  
  
 2) NOTE: PLEASE SEE THE PREVIOUS REVIEW COMMENT WHICH
 STATED THE SIGNATURES ON THE FP SHEETS FROM OTHER THAN
 MR. JAMES MINDUR DID NOT CORRELATE. PLEASE SEE ALL THE
 NEW SHEETS SEEM TO CONTAIN THE SAME SIGNATURE AS SHOWN
 ON THE NEW PLUMBING AND MECHANICAL SHEETS. PLEASE SEE
 THE OLD/NOT REVISED FP SHEETS DO NOT CONTAIN THIS NEW
 SIGNATURE. PLEASE SUBMIT A SIGNED, SEALED, DATED AND
 NOTARIZED LETTER FOR LEGAL SIGNATURE VERIFICATION. THIS
 WILL BE PLACED IN OUR SIGNATURE FILE FOR ANY FUTURE
 REFERENCE.
  
 3) NOTE: PLEASE SEE THE SPEC SUBMITTED FOR THE MTS
 CONTAIN A COVER SHEET FOR AN ATS.
 PLEASE CORRELATE.
 110.3, 90.7, 702.6 NEC.
 FBC 106.1.2, 106.3.5.1.2
  
 4) NOTE: PLEASE SEE THE PLANS IN SOME PLACES STILL
 INDICATE A SMALLER GENERATOR THAN THAT ON OTHER SHEETS
 OF THE PLANS. PLEASE SEE SOME SHEETS AS THEY WERE NOT
 REVISED OR UPDATED FOR OTHER COMMENTS OR FOR THE
 GENERATOR WHICH ARE THE SAME SHEETS FROM THE PREVIOUS
 REVIEWED PLANS.
 PLEASE SEE THE SUBMITTALS FOR THE GENERATOR DO NOT
 CORRELATE. (PLEASE SEE SOME ARE FOR A *KATOLIGHT* UNIT
 WHICH IS A DIFFERENT MANUFACTURE AND DIFFERENT SIZE
 ETC.
 PLEASE CORRELATE ALL OF THE EQUIPMENT.
 110.3, 90.7, 445 NEC.
 NFPA-110 2002 CHAPTERS 5, 6 AND 7.
  
 5) NOTE: PLEASE SEE E0-1.0 FOR MAXIMUM TIMES ON DIMMER
 DEVICE.
 FBC 2004 13-415.1.ABC.1.1 AND .1.2.
  
 6) NOTE: PLEASE SEE LOBBY AREAS/SEPARATE SPACES WHICH
 DO NOT INDICATE OVER RIDE CONTROLS AS GONE OVER IN
 PREVIOUS REVIEW AND IN MEETING. THE RESPONSE LETTER
 MENTIONS THE LOBBIES WERE DONE, HOWEVER NOT ALL. PLEASE
 SEE OTHER AREAS OF BUILDING WHICH DO NOT INDICATE
 CONTROLS FOR SEPARATE SPACES.
 PLEASE KNOW THE REDLINED PLANS WHICH WERE REMOVED FROM
 13-415.1.ABC.1.1, .1.2, .1.3.
  
 7) NOTE: PLEASE SEE THE ENERGY CALCULATIONS STILL DO
 NOT SEEM TO CORRELATE FOR EXTERIOR FIXTURES. THE PLANS
 INDICATE A SUBSTANTIAL AMOUNT OF FIXTURES; HOWEVER
 THESE CALCULATIONS DO NOT SEEM TO CORRELATE. PLEASE SEE
 13-415.1.AB.1.1, 13-415.2.ABC.1.3 ETC
  
 8) NOTE: PLEASE SEE ALL SHEETS IN SETS WHICH ARE THE
 *OVERALL* SHEETS FOR FLOORS ETC WHICH WERE NOT REVISED.
 PLEASE SEE THEY ARE THE SAME SHEETS FROM THE PREVIOUS
 REVIEW.
 PLEASE CLARIFY HOW THE PLANS CONTAIN TWO SEPARATE
 LAYOUTS. ????
 FBC 106.1.2, 106.3.5.1.2
  
 9) NOTE: PLEASE SEE THE LIGHT POLE SUBMITTALS WHICH DO
 NOT ADDRESS PREVIOUS REVIEW COMMENTS. PLEASE SEE THESE
 DO NOT CONTAIN WIND LOAD INFORMATION AND NO
 CALCULATIONS FOR FIXTURES ON POLES OR POLES AND THE
 EFFECTIVE PROJECTED AREA COULD BE LOCATED. AS
 PREVIOUSLY STATED, THIS COULD BE DONE AS A PROVISO AND
 THIS INFORMATION COULD BE SUBMITTED AT A LATER DATE.
 106.1.2
  
 10) NOTE: PLEASE SEE STAIRS 11 AND 12 ARE NOT COMPLETE
 (SEE LATER NOTES FOR STAIR 13).
 PLEASE SEE MISSING LIGHTING FOR EMERGENCY EGRESS OR
 LIGHTING UNDER NORMAL FOR STAIR 12. PLEASE SEE
 PHOTO-METRICS WHICH ARE ALSO STILL MISSING UNDER NORMAL
 AND UNDER EMERGENCY.
 PLEASE SEE LS 101 7.8.1.3, 7.9.2.2 ETC
 PLEASE SEE THAT ALL SHEETS AND ALL OVER-LAYS NEED TO
 CORRELATE AND PLEASE SEE THAT THESE SECTIONS FOR
 MEZZANINE LEVELS ARE NOT COMPLETE.
 FBC 106.1.2
 *PLEASE SEE BUILDING REVIEW NOTES FOR POSSIBLE CONFLICT
 FOR DOOR SWINGS (IF APPLICABLE).
  
 11) NOTE: PLEASE SEE STAIR AREA FOR STAIR (8) ON
 E2-5.0.0. PLEASE SEE THE LIGHTING WAS NOT CHANGED.
 PLEASE SEE THAT ALL SHEETS AND OVER-LAYS NEED TO
 CORRELATE. FBC 106.1
  
 12) NOTE: PLEASE SEE LIGHTING ON E1-6.3 WAS NOT UPDATED
 FOR STAIRS 4 AND 5. PLEASE ALSO SEE NOTES FOR
 PHOTO-METRICS. NFPA-101 7.8, 7.9
 FBC 106.1.2,
  
 13) NOTE: PLEASE SEE THAT THE LIGHTING POWER DENSITY
 CALCULATIONS STILL DO NOT CORRELATE WITH ALL OF THE
 AREA AND ROOM DESIGNATIONS ON PLANS.
 PLEASE SEE UPPER LEVELS, MISSING ALL OF A-6
 DESIGNATIONS.
 FBC 13-415.2
 FBC 106.1.2, 106.3.5.1.2
  
 14) NOTE: PLEASE SEE E2-1.2 WHICH CONTAINS MISSING
 CIRCUITING FOR ROOMS FOR MECHANICAL EQUIPMENT. PREVIOUS
 NOTES REQUESTED ALL ROOM DESIGNATIONS TO BE COORDINATED
 ETC.
 PLEASE SEE THESE ARE ROOMS WHICH ARE ELEVATOR EQUIPMENT
 ROOMS WHICH DO NOT CONTAIN THE DEDICATED CIRCUITS AS
 REQUIRED PER 620.23.
 PLEASE SEE DESIGNATIONS FOR ELEVATOR EQUIPMENT ROOMS
 SHOULD BE ON PLANS AS LIGHTING IN THESE ROOMS IS BEING
 SHOWN FEEDING OTHER AREAS.
 ROOMS FOR ELEVATORS 6,7,8, AND 9.
 PLEASE SEE NOTES WITH RESPECT TO UPPER EQUIPMENT
 ROOM(S).
  
 15) NOTE: PLEASE SEE PLANS FOR UPPER EQUIPMENT ROOMS
 ARE NOT COMPLETE. THIS WAS GONE OVER IN MEETING,
 HOWEVER THE SAME SHEETS WERE SUBMITTED BACK IN FOR
 REVIEW.
 PLEASE CLARIFY THE AREA/ROOM DESIGNATIONS FOR THE
 ELEVATOR EQUIPMENT FOR UNITS 1, 2 AND 3.
 WHERE IS THIS ELEVATOR EQUIPMENT ROOM? PLEASE SEE IF
 THIS IS THE ROOM LOCATED ON UPPER FLOORS POWER PLANS
 E1-6, E1-6.1 WHERE IS THE EQUIPMENT AND THE DEDICATED
 BRANCH CIRCUITS ETC. PLEASE ALSO SEE LIGHTING PLANS.
 PLEASE SEE 620.22, .23, .24, 51 ETC.
  
 16) NOTE: PLEASE LIGHTING AND POWER PLANS FOR THE SAME
 FLOOR/AREA AS THE LIGHTING AND CONTROLS STILL INDICATE
 SWITCHING OUTSIDE STAIR WALL? PLEASE SEE THE SAME PLANS
 WERE SUBMITTED WITH OUT CHANGES TO THE UPPER DOME AREA
 FOR LIGHTING CONTROL, EGRESS LIGHTING ETC.
 PLEASE SEE THE UPPER AREA PLANS NEED TO BE COORDINATED
 AND COMPLETE.
 NFPA-101 7.8,7.9, FBC 13-415.1.ABC.1.1, ETC, NEC 620,
 408, 310.16, 240.4 ETC
 FBC 106.1.2, 106.3.5.1.2 ** PLEASE CALL TO GO OVER
 THESE SHEETS.
  
 17) NOTE: PLEASE SEE STILL MISSING BATTERY BACK LIGHT
 FIXTURES OF SOME KIND ON MECHANICAL EQUIPMENT ROOMS,
 ELEVATOR EQUIPMENT ROOMS.THIS IS FOR MULTIPLE ROOMS
 LS 101 7.8, 7.9, NEC 700.16, 700.12E ETC.
 PLEASE SEE REDLINED SHEETS.
  
 18) NOTE: PLEASE STILL MISSING THE MANUFACTURES
 SPECS/CUT SHEETS FOR THE TANK LESS WATER HEATERS.
 110.3, 90.7. THIS COULD BE DONE AS A *PROVISO* ALTHOUGH
 IT WAS ALSO STATED IN PLUMBING REVIEW COMMENTS.
  
 19) NOTE: PLEASE SEE PHOTO-METRICS. PLEASE CORRELATE
 ALL STAIRS AND AREAS FOR EGRESS. PLEASE SEE PREVIOUS
 NOTE ABOVE WHICH MENTIONS TO COMPLETE STAIRS 11, 12
 ETC.
 PLEASE SEE THERE ARE SEVERAL SHEETS WHICH THE
 TABLE/INFORMATION IS NOT PRINTED.
 PLEASE SEE SHEETS E8-5.1 THRU 8-6.4 WHICH STILL
 INDICATE LIGHTING PHOTO-METRIC INFORMATION STILL
 PENDING.
 PLEASE SEE SHEETS E9-5.1 THRU 9-5.2 WHICH ALSO INDICATE
 INFORMATION STILL PENDING.
 PLEASE COMPLETE AT THIS TIME AS REQUESTED.
  
 20) NOTE: PLEASE SEE STAIRS ARE STILL BEING NUMBERED
 WITH NUMERICAL DESIGNATIONS WHICH DO NOT CORRELATE WITH
 THE PLANS. STAIR 1, STAIR 4, STAIR 8, ETC.
 106.1, 106.1.2, 106.3.5.1.2
 LS 101
 PLEASE CLARIFY.
  
 21) NOTE: PLEASE SEE SOME BATHROOMS STILL MISSING
 BATTERY TYPE BACK UP LIGHT. PLEASE SEE LIBRARY MEN?S
 AND WOMEN?S ON E2-1.2
  
 22) NOTE: PLEASE SEE STAIR 1 ON OVER ALL PLANS ON
 E2-5.0 AND 2-5.1 FIXTURE TYPE, WHERE IS THE E2? PLEASE
 ALSO CLARIFY WHERE THIS STAIR CONTINUES UP.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-22 06:31:132007-01-22 06:31:13
 IN PROGRESS
2007-01-21 19:09:402007-01-21 19:09:40
 ELECTRICAL REVIEW COMPLETED.
 THE PLANS WILL BE GOING INTO A "F" STATUS AND NOTES ARE
 TO FOLLOW ONCE THEY ARE COMPLETED.