Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop B
Sequence Number 26
Notes
Date Text
2008-04-18 12:20:17CITY HALL/ CITY CENTER REVISION# 14D
  
 BUILDING PLAN REVIEW
 PERMIT: 06100574
 ADD: 401 CLEMATIS ST.
 CONT: CATALFUMO
 TEL: (561)307-4746
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION # 14D
  
 ACTION: DENIED
  
 1) SHEET A1-1.1 COMMISION CHAMBERS NOW ARE SHOWN AS A 1
 HRRATED WALL BUT WINDOWS G-10 & G-11ON SHEET A8-2.1
 INDICATES WINDOWS NOT RATED, SEE TABLE 715.3 OPENING
 PROTECTION.
  
 2)SEE PLANS THERE ARE (3) AREAS THAT ARE MISSING 1 HR
 RATING IN THE 1 HR RATED WALL AROUND THE CORRIDOR.
  
 3) A1-1.2 W4-8/ 1 HR WALL RATING IS SHOWN AT THE
 LOADING DOCK WALL BUT THERE IS NO WALL TAGS SHOWN ON
 SHEET A5-D.1.
  
 4) A1-1.2 W4-8/ 1 HR LOADING DOCK/ CORRIDOR WALL SHOULD
 INDICATE AS A FIRE-SMOKE DESIGNATION.
  
 5) A1-1.2 TRASH ROOM/ CALL CENTER W4-8 NO WALL TYPE THE
 MECH AND LS BOTH INDICATE AS SUCH.
  
 6) A1-1.2 COORIDOR D1.006 LS & MECHANICAL INDICATE
 SMOKE RATING WHILE LS INDICATES AN EXIT AT DOOR D1-004A
 WHICH IS A FIRE/ SMOKE RATED CORRIDOR, INACTED BY THE
 MUSEUM BEING A A-3 OCCUPANCY.
  
 7) A1-1.2 VESTIBULE D1.005 IS TRUELY A EXIT PASSAGEWAY
 NOT A VESTIBULE, THE COMMON WALL BILLING / VESTIBULE
 SHOULD BE A 2 HR RATED WALL, (EXIT PASSAGEWAY). SEE
 MECHANICAL COMMENTS DUCT PENETRATING EXIT.
  
 8) WALL TYPE P2-4 ON SHEET A5-D.1 DOES NOT INDICATE
 SMOKE RATING.
  
 9)A1-1.2 LOBBY C1.008 IT APPEARS 3 POSSIBLE BOOK
 RETURNS IN THE 1 HR RATED WALL, PLEASE PROVIDE
 ADDITIONAL DETAILS FOR FIRE RATING OF THIS AREA.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 10)A1-1.2 PLEASE REVIEW STORAGE AREAS ON MECH PLAN
 C1.403 & C1.404 INDICATE THE USE OF TRANSFER OPENINGS
 THERE ARE NO SMOKE DAMPERS PROVIDED 710.7.
  
 11) A1-2.1 MISSING A REVISION FOR THE ARCHITECTURAL
 SHEET, LS AND MECH PLANS INDICATE SMOKE PARTITIONS AT
 THE STORAGE A2.303
  
 12)A1-2.1 MISSING A REVISION FOR THE ARCHITECTURAL
 SHEET, SHAFT WALL COMMON TO THE MONUMENTAL STAIR DOES
 NOT INDICATE A 2HR FIRE RATING WALL TAG.
  
 13) A1-2.2 (2) ISSUES WITH 707.2 EXCEPTION# 3:
 13A) STAIR TO MEZZANINE THE DOOR AND WALL NOT RATED,
 SINCE THERE IS NO WALL RATING AT THE MEZZANINE WALL
 LEVEL THIS WILL CREATE THE FLOOR LEVEL FIRE RATING
 BETWEEN FLOORS.
 13B) THE SAME AREA WHERE THE SHAFT WALL COMES OUT OF
 THE MEZZANINE LEVEL WILL NEED A 1 HR RATED SHAFT WALL.
  
 14) A1-2.2PLEASE REVIEW THE DOOR LOCATION FOR THE
 ENTRY TO THE MEZZANINE LEVEL , REVIEW ARCHITECTURAL, LS
 BOTH THE OVERALL FLOOR PLAN AND THE MEZZANINE LEVEL
 CORRELATE.
  
 15) LS1-3.1 REVISIONS SUBMITTED BUT NO ARCHITECTURAL
 SHEETS.
  
 16) LS 1-3.1 / A1-3.1 & M1-3.1 MISSING ROOM I.D. BY
 CORRIDOR A3.604 & A3.115.
  
 17) LS1-3.2 THE PLANS DO NOT INDICATE WALL RATING
 BETWEEN THE PRE-FUNCTION AREA AND THE THE LOBBY C3.301
 ALTHOUGH THE DOORS INDICATE A 20 MINUTE RATING, THIS
 SHOULD BE PART OF THE 1 HOUR RATED DORRIDOR TABLE 1016,
 (A) OCCUPANCY > THAN 30.
  
 18) RESTROOM EXHAUST 1ST FLOOR THROUGH THE 4 TH FLOOR
 LIBRARY, 5TH FLOOR CITY HALL, ARE NOT INDICATED AS
 BEING IN 2 HR RATED SHAFTS. 716.6.
  
 19) SHEET LS1.2.2 & A1-2.2 EXIT ACCESS CORRIDOR ON GRID
 LINE COLUMN LINE J & 6 SHOULD HAVE A 1 HR FIRE RATING
 AND DOORS ADDED AGAIN THIS IS AN (A3) OCCUPANCY WITH AN
 OCCUPANT LOAD GREATER THAN 30. TABLE 1016.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.