2008-04-18 12:20:17 | CITY HALL/ CITY CENTER REVISION# 14D |
| |
| BUILDING PLAN REVIEW |
| PERMIT: 06100574 |
| ADD: 401 CLEMATIS ST. |
| CONT: CATALFUMO |
| TEL: (561)307-4746 |
| |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVISION # 14D |
| |
| ACTION: DENIED |
| |
| 1) SHEET A1-1.1 COMMISION CHAMBERS NOW ARE SHOWN AS A 1 |
| HRRATED WALL BUT WINDOWS G-10 & G-11ON SHEET A8-2.1 |
| INDICATES WINDOWS NOT RATED, SEE TABLE 715.3 OPENING |
| PROTECTION. |
| |
| 2)SEE PLANS THERE ARE (3) AREAS THAT ARE MISSING 1 HR |
| RATING IN THE 1 HR RATED WALL AROUND THE CORRIDOR. |
| |
| 3) A1-1.2 W4-8/ 1 HR WALL RATING IS SHOWN AT THE |
| LOADING DOCK WALL BUT THERE IS NO WALL TAGS SHOWN ON |
| SHEET A5-D.1. |
| |
| 4) A1-1.2 W4-8/ 1 HR LOADING DOCK/ CORRIDOR WALL SHOULD |
| INDICATE AS A FIRE-SMOKE DESIGNATION. |
| |
| 5) A1-1.2 TRASH ROOM/ CALL CENTER W4-8 NO WALL TYPE THE |
| MECH AND LS BOTH INDICATE AS SUCH. |
| |
| 6) A1-1.2 COORIDOR D1.006 LS & MECHANICAL INDICATE |
| SMOKE RATING WHILE LS INDICATES AN EXIT AT DOOR D1-004A |
| WHICH IS A FIRE/ SMOKE RATED CORRIDOR, INACTED BY THE |
| MUSEUM BEING A A-3 OCCUPANCY. |
| |
| 7) A1-1.2 VESTIBULE D1.005 IS TRUELY A EXIT PASSAGEWAY |
| NOT A VESTIBULE, THE COMMON WALL BILLING / VESTIBULE |
| SHOULD BE A 2 HR RATED WALL, (EXIT PASSAGEWAY). SEE |
| MECHANICAL COMMENTS DUCT PENETRATING EXIT. |
| |
| 8) WALL TYPE P2-4 ON SHEET A5-D.1 DOES NOT INDICATE |
| SMOKE RATING. |
| |
| 9)A1-1.2 LOBBY C1.008 IT APPEARS 3 POSSIBLE BOOK |
| RETURNS IN THE 1 HR RATED WALL, PLEASE PROVIDE |
| ADDITIONAL DETAILS FOR FIRE RATING OF THIS AREA. |
| 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| |
| 10)A1-1.2 PLEASE REVIEW STORAGE AREAS ON MECH PLAN |
| C1.403 & C1.404 INDICATE THE USE OF TRANSFER OPENINGS |
| THERE ARE NO SMOKE DAMPERS PROVIDED 710.7. |
| |
| 11) A1-2.1 MISSING A REVISION FOR THE ARCHITECTURAL |
| SHEET, LS AND MECH PLANS INDICATE SMOKE PARTITIONS AT |
| THE STORAGE A2.303 |
| |
| 12)A1-2.1 MISSING A REVISION FOR THE ARCHITECTURAL |
| SHEET, SHAFT WALL COMMON TO THE MONUMENTAL STAIR DOES |
| NOT INDICATE A 2HR FIRE RATING WALL TAG. |
| |
| 13) A1-2.2 (2) ISSUES WITH 707.2 EXCEPTION# 3: |
| 13A) STAIR TO MEZZANINE THE DOOR AND WALL NOT RATED, |
| SINCE THERE IS NO WALL RATING AT THE MEZZANINE WALL |
| LEVEL THIS WILL CREATE THE FLOOR LEVEL FIRE RATING |
| BETWEEN FLOORS. |
| 13B) THE SAME AREA WHERE THE SHAFT WALL COMES OUT OF |
| THE MEZZANINE LEVEL WILL NEED A 1 HR RATED SHAFT WALL. |
| |
| 14) A1-2.2PLEASE REVIEW THE DOOR LOCATION FOR THE |
| ENTRY TO THE MEZZANINE LEVEL , REVIEW ARCHITECTURAL, LS |
| BOTH THE OVERALL FLOOR PLAN AND THE MEZZANINE LEVEL |
| CORRELATE. |
| |
| 15) LS1-3.1 REVISIONS SUBMITTED BUT NO ARCHITECTURAL |
| SHEETS. |
| |
| 16) LS 1-3.1 / A1-3.1 & M1-3.1 MISSING ROOM I.D. BY |
| CORRIDOR A3.604 & A3.115. |
| |
| 17) LS1-3.2 THE PLANS DO NOT INDICATE WALL RATING |
| BETWEEN THE PRE-FUNCTION AREA AND THE THE LOBBY C3.301 |
| ALTHOUGH THE DOORS INDICATE A 20 MINUTE RATING, THIS |
| SHOULD BE PART OF THE 1 HOUR RATED DORRIDOR TABLE 1016, |
| (A) OCCUPANCY > THAN 30. |
| |
| 18) RESTROOM EXHAUST 1ST FLOOR THROUGH THE 4 TH FLOOR |
| LIBRARY, 5TH FLOOR CITY HALL, ARE NOT INDICATED AS |
| BEING IN 2 HR RATED SHAFTS. 716.6. |
| |
| 19) SHEET LS1.2.2 & A1-2.2 EXIT ACCESS CORRIDOR ON GRID |
| LINE COLUMN LINE J & 6 SHOULD HAVE A 1 HR FIRE RATING |
| AND DOORS ADDED AGAIN THIS IS AN (A3) OCCUPANCY WITH AN |
| OCCUPANT LOAD GREATER THAN 30. TABLE 1016. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |