2008-11-17 10:57:12 | REVISION DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| |
| 1. SHT P1-1.0U REVISION INDEX & FLOOR PLAN FROM |
| PREVIOUS SHEET SIGNED, SEALED & DATED ON 9-17-08 |
| INDICATES REVISION 193R3 DATED 9-16-08. NEW REVISIED |
| SHEET SUBMITTED DELETED REVISION 193R3 AND NOW SHOWS |
| REVISION 193R4 DATED 10-30-08 BUT NO CLOUD FOR NEW |
| REVISION. PER SECTION 106.1.3 COMPLETE REVISION RECORD |
| IS REQUIRED AND ALL NEW REVISIONS SHALL BE INDIDCATED |
| WITH A CLOUD AND REVISION NUMBER SHOWING WHERE THE NEW |
| REVISION CAN BE LOCATED. |
| |
| 2. SHT P1-1.0U 2-WAY CLEANOUTS ARE REQUIRED AS THE |
| GREASE LINE EXITS THE BUILDING AND BEFORE THE INLET OF |
| THE GREASE INTERCEPTOR AND ON THE OUTLET OF THE GREASE |
| INTERCEPTOR. THE GREASE INTERCEPTOR PRIOR TO THE GREASE |
| INTERCEPTOR OUTLET CAN BE USED FOR BOTH THE INLET |
| REQUIREMENT AND THE REQUIREMENT AS THE GREASE LINE |
| EXITS THE BUILDING. SECTION 708.3.5 & UTILITY DEPT |
| GREASE INTERCEPTOR STANDARD. |
| |
| 3. SHT 1-1.0U 2-WAY CLEANOUTS ARE REQUIRED ON THE INLET |
| AND OUTLET OF THE GREASE INTERCEPTOR. UTILITY DEPT |
| GREASE INTERCEPTOR STANDARD. |
| |
| 4. SHT P1-1.0 REVISION INDEX & FLOOR PLAN FROM PREVIOUS |
| SHEET SIGNED, SEALED & DATED ON 9-17-08 INDICATES |
| REVISION 193R3 DATED 9-16-08. NEW REVISIED SHEET |
| SUBMITTED DELETED REVISION 193R3 AND NOW SHOWS REVISION |
| 193R4 DATED 10-30-08 BUT NO CLOUD FOR NEW REVISION. PER |
| SECTION 106.1.3 COMPLETE REVISION RECORD IS REQUIRED |
| AND ALL NEW REVISIONS SHALL BE INDIDCATED WITH A CLOUD |
| AND REVISION NUMBER SHOWING WHERE THE NEW REVISION CAN |
| BE LOCATED. |
| |
| 5. SHT P1-1.0 CHANGES TO THE CONDENSATE HAVE BEEN FOUND |
| WITHOUT CLOUDS OR INDICATED BY REVISION NUMBERS. SHOW |
| ALL CHANGES WITH CLOUDS AND REVISION NUMBERS. SECTION |
| 106.1.3. PLEASE INDICATE ALL CHANGES/REVISIONS ON THE |
| SHEET WITH A CLOUD AND A REVISION NUMBER. |
| |
| 6. SHT P1-1.2U 2-WAY CLEANOUTS ARE REQUIRED ON THE |
| INLET AND OUTLET OF THE GREASE INTERCEPTOR. UTILITY |
| DEPT GREASE INTERCEPTOR STANDARD. |
| |
| 7. SHT P1-1.2 THE 2" GOOSENECK VENT FOR THE GREASE |
| INTERCEPTOR IS NOT REQUIRED AS THE INLET LINE TO THE |
| INTERCEPTOR IS A VENTED LINE. IF THE VENT IS INSTALLED |
| IT SHALL BE TERMINATED PER SECTIONS 904.5 & 904.6. |
| |
| 8. SHT P2-1.0 DETAIL 5 SHOWS CHANGES WITH NO CLOUDS OR |
| REVISION NUMBERS INDICATING THE LOCATION OF THE |
| REVISIONS. REVISIONS 1 & 2 WERE DELETED AND A REVISION |
| DATED 12-06-07 IS INDICATED WITHOUT A REVISION NUMBER. |
| PLEASE CLARIFY. SECTION 106.1.3. PLEASE INDICATE ALL |
| CHANGES/REVISIONS ON THE SHEET WITH A CLOUD AND A |
| REVISION NUMBER. |
| |
| 9. SHT P2-1.0U DETAIL 5 SHOWS CHANGES WITH NO CLOUDS OR |
| REVISION NUMBERS INDICATING THE LOCATION OF THE |
| REVISIONS. REVISIONS 1 & 2 WERE DELETED PLEASE CLARIFY. |
| SECTION 106.1.3. PLEASE INDICATE ALL CHANGES/REVISIONS |
| ON THE SHEET WITH A CLOUD AND A REVISION NUMBER. |
| |
| 10. SHT P3-1.0 A CLEANOUT IS REQUIRED NEAR THE JUNCTION |
| OF THE BUILDING GREASE DRAIN AND THE BUILDING SEWER |
| GREASE PER SECTION 708.3.5. PLEASE SHOW ON THE RISER |
| DIAGRAM. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |