Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop P
Sequence Number 24
Notes
Date Text
2008-11-17 10:57:12REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P1-1.0U REVISION INDEX & FLOOR PLAN FROM
 PREVIOUS SHEET SIGNED, SEALED & DATED ON 9-17-08
 INDICATES REVISION 193R3 DATED 9-16-08. NEW REVISIED
 SHEET SUBMITTED DELETED REVISION 193R3 AND NOW SHOWS
 REVISION 193R4 DATED 10-30-08 BUT NO CLOUD FOR NEW
 REVISION. PER SECTION 106.1.3 COMPLETE REVISION RECORD
 IS REQUIRED AND ALL NEW REVISIONS SHALL BE INDIDCATED
 WITH A CLOUD AND REVISION NUMBER SHOWING WHERE THE NEW
 REVISION CAN BE LOCATED.
  
 2. SHT P1-1.0U 2-WAY CLEANOUTS ARE REQUIRED AS THE
 GREASE LINE EXITS THE BUILDING AND BEFORE THE INLET OF
 THE GREASE INTERCEPTOR AND ON THE OUTLET OF THE GREASE
 INTERCEPTOR. THE GREASE INTERCEPTOR PRIOR TO THE GREASE
 INTERCEPTOR OUTLET CAN BE USED FOR BOTH THE INLET
 REQUIREMENT AND THE REQUIREMENT AS THE GREASE LINE
 EXITS THE BUILDING. SECTION 708.3.5 & UTILITY DEPT
 GREASE INTERCEPTOR STANDARD.
  
 3. SHT 1-1.0U 2-WAY CLEANOUTS ARE REQUIRED ON THE INLET
 AND OUTLET OF THE GREASE INTERCEPTOR. UTILITY DEPT
 GREASE INTERCEPTOR STANDARD.
  
 4. SHT P1-1.0 REVISION INDEX & FLOOR PLAN FROM PREVIOUS
 SHEET SIGNED, SEALED & DATED ON 9-17-08 INDICATES
 REVISION 193R3 DATED 9-16-08. NEW REVISIED SHEET
 SUBMITTED DELETED REVISION 193R3 AND NOW SHOWS REVISION
 193R4 DATED 10-30-08 BUT NO CLOUD FOR NEW REVISION. PER
 SECTION 106.1.3 COMPLETE REVISION RECORD IS REQUIRED
 AND ALL NEW REVISIONS SHALL BE INDIDCATED WITH A CLOUD
 AND REVISION NUMBER SHOWING WHERE THE NEW REVISION CAN
 BE LOCATED.
  
 5. SHT P1-1.0 CHANGES TO THE CONDENSATE HAVE BEEN FOUND
 WITHOUT CLOUDS OR INDICATED BY REVISION NUMBERS. SHOW
 ALL CHANGES WITH CLOUDS AND REVISION NUMBERS. SECTION
 106.1.3. PLEASE INDICATE ALL CHANGES/REVISIONS ON THE
 SHEET WITH A CLOUD AND A REVISION NUMBER.
  
 6. SHT P1-1.2U 2-WAY CLEANOUTS ARE REQUIRED ON THE
 INLET AND OUTLET OF THE GREASE INTERCEPTOR. UTILITY
 DEPT GREASE INTERCEPTOR STANDARD.
  
 7. SHT P1-1.2 THE 2" GOOSENECK VENT FOR THE GREASE
 INTERCEPTOR IS NOT REQUIRED AS THE INLET LINE TO THE
 INTERCEPTOR IS A VENTED LINE. IF THE VENT IS INSTALLED
 IT SHALL BE TERMINATED PER SECTIONS 904.5 & 904.6.
  
 8. SHT P2-1.0 DETAIL 5 SHOWS CHANGES WITH NO CLOUDS OR
 REVISION NUMBERS INDICATING THE LOCATION OF THE
 REVISIONS. REVISIONS 1 & 2 WERE DELETED AND A REVISION
 DATED 12-06-07 IS INDICATED WITHOUT A REVISION NUMBER.
 PLEASE CLARIFY. SECTION 106.1.3. PLEASE INDICATE ALL
 CHANGES/REVISIONS ON THE SHEET WITH A CLOUD AND A
 REVISION NUMBER.
  
 9. SHT P2-1.0U DETAIL 5 SHOWS CHANGES WITH NO CLOUDS OR
 REVISION NUMBERS INDICATING THE LOCATION OF THE
 REVISIONS. REVISIONS 1 & 2 WERE DELETED PLEASE CLARIFY.
 SECTION 106.1.3. PLEASE INDICATE ALL CHANGES/REVISIONS
 ON THE SHEET WITH A CLOUD AND A REVISION NUMBER.
  
 10. SHT P3-1.0 A CLEANOUT IS REQUIRED NEAR THE JUNCTION
 OF THE BUILDING GREASE DRAIN AND THE BUILDING SEWER
 GREASE PER SECTION 708.3.5. PLEASE SHOW ON THE RISER
 DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  