Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop B
Sequence Number 22
Notes
Date Text
2007-09-18 15:09:12CITY HALL/ CITY CENTER REVISION# 11
  
 BUILDING PLAN REVIEW
 PERMIT: 06100574
 ADD: 401 CLEMATIS ST.
 CONT: CATALFUMO
 TEL: (561)307-4746
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION # 11
  
 ACTION: DENIED
  
  
 NOTES SHEET A8-0.2 FOOTNOTE D DOOR SHALL HAVE
 CLOSER
 FOOTNOTE E SMOKE
 AND DRAFT CONTROL ASSEMBLY W/ ARTIFICIAL BOTTOM SEAL
  
 INSTALLED ACROSS THE FULL WIDTH OFTHE BOTTOM OF THE
 DOOR ALL
  
 IN COMPLIANCE WITHUL 1784.
  
 1) SHEET A1-1.1:
 1A) DOOR A1-120A IS MISSING FOOTNOTE "D & E"
 1B) DOOR A1-201A IS MISSING FOOTNOTE "E"
 1C) SECURITY DESKA 1 HR RATED WALL IN FRONT OF DESK,
 PLEASE SEE A9.3.1 DETAIL# 4, NOW IS MISSING RATED WALL
 AND DOORWAY
 1D) RECEPTION DESK A 1 HR RATED WALL PLEASE SEE A9-3.1
 DETAIL# 3 NOW HAS BY PASS WINDOWS, 1 HR RATED?
  
 2) SHEET A1-2.1
 2A) DOOR A2-008-A 1 HR RATED DOOR MISSING FOOTNOTE
 "D&E"
 2B) DOOR A2-001-A1 HR RATED DOOR MISSING FOOTNOTE
 "D&E"
  
 3)SHEET A1-3.2 :
 3A)DOOR C3-105-A, 1 HR RATED DOOR IS MISSING FOOTNOTE
 "D&E"
 3B) DOOR C3-106-A , 1 HR RATED DOOR IS MISSING FOOTNOTE
 "D&E"
 3C) DOOR C3-107-A, 1 HR RATED DOOR ISMISSING FOOTNOTE
 "D&E"
 3D)DOOR C3-108-A, 1 HR RATED DOOR IS MISSING FOOTNOTE
 "D&E"
 3E)DOOR C3-109-A, 1 HR RATED DOOR IS MISSING FOOTNOTE
 "D&E"
  
 NOTE MEETING AT CONSTRUCTION SITE 9-18-07 :
  
 1) DISCUSSED THE NEED FOR CUT SECTIONS OF THE
 STAIRTOWER# 10 THIRD FLOOR INDICATING A 2 HR RATING
 BETWEEN THE A/C DUCT AND
 STAIRWELL AS WELL AS THE MOVING THE FIRE DAMPERS FROM
 WITHIN THE STAIRTOWER WALLS TO ALLOW FOR ACCESS PANELS
 OUTSIDE OF THE STAIR TOWER.
  
 2) STIAR WAY # 11 DISCUSSED THE NEED OF A CUT SECTION
 THROUGH THE STAIRWAY INDICATING THE PLACEMENT OF THE
 MEZZANINE FLOOR THAT WILL KEEP THE DUCTWORK FROM
 ENTERING STAIRTOWER #7.
  
 3) THE THIRD ISSUE THAT WAS ALSO BROUGHT UP THAT NO
 SHAFT WALL WILL BE NECESSARY IN THE MEZZANINE STAIRWAY
 SINCE IT IS WITHIN THE STORY. THERE ARE CONCERNS ON THE
 REQUIRED WIDTH OF THE STAIR!
  
 4) SHEET A8-0.1DOORS MISSING FOOTNOTE :1 HR RATED
 DOOR MISSING FOOTNOTE "D&E"
 A1-120-A
 A1-201-A
 A2-008-A
 A2-001-A
  
 5) SHEET A8-0.2 DOORS MISSING FOOTNOTE: 1 HR RATED DOOR
 MISSING FOOTNOTE "D&E"
 C3-105-A
 C3-106-A
 C3-107-A
 C3-108-A
 C3-110-A
  
 6)SHEET A9-3.1 COMMENT 1C & 1D.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  