2007-09-18 15:09:12 | CITY HALL/ CITY CENTER REVISION# 11 |
| |
| BUILDING PLAN REVIEW |
| PERMIT: 06100574 |
| ADD: 401 CLEMATIS ST. |
| CONT: CATALFUMO |
| TEL: (561)307-4746 |
| |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVISION # 11 |
| |
| ACTION: DENIED |
| |
| |
| NOTES SHEET A8-0.2 FOOTNOTE D DOOR SHALL HAVE |
| CLOSER |
| FOOTNOTE E SMOKE |
| AND DRAFT CONTROL ASSEMBLY W/ ARTIFICIAL BOTTOM SEAL |
| |
| INSTALLED ACROSS THE FULL WIDTH OFTHE BOTTOM OF THE |
| DOOR ALL |
| |
| IN COMPLIANCE WITHUL 1784. |
| |
| 1) SHEET A1-1.1: |
| 1A) DOOR A1-120A IS MISSING FOOTNOTE "D & E" |
| 1B) DOOR A1-201A IS MISSING FOOTNOTE "E" |
| 1C) SECURITY DESKA 1 HR RATED WALL IN FRONT OF DESK, |
| PLEASE SEE A9.3.1 DETAIL# 4, NOW IS MISSING RATED WALL |
| AND DOORWAY |
| 1D) RECEPTION DESK A 1 HR RATED WALL PLEASE SEE A9-3.1 |
| DETAIL# 3 NOW HAS BY PASS WINDOWS, 1 HR RATED? |
| |
| 2) SHEET A1-2.1 |
| 2A) DOOR A2-008-A 1 HR RATED DOOR MISSING FOOTNOTE |
| "D&E" |
| 2B) DOOR A2-001-A1 HR RATED DOOR MISSING FOOTNOTE |
| "D&E" |
| |
| 3)SHEET A1-3.2 : |
| 3A)DOOR C3-105-A, 1 HR RATED DOOR IS MISSING FOOTNOTE |
| "D&E" |
| 3B) DOOR C3-106-A , 1 HR RATED DOOR IS MISSING FOOTNOTE |
| "D&E" |
| 3C) DOOR C3-107-A, 1 HR RATED DOOR ISMISSING FOOTNOTE |
| "D&E" |
| 3D)DOOR C3-108-A, 1 HR RATED DOOR IS MISSING FOOTNOTE |
| "D&E" |
| 3E)DOOR C3-109-A, 1 HR RATED DOOR IS MISSING FOOTNOTE |
| "D&E" |
| |
| NOTE MEETING AT CONSTRUCTION SITE 9-18-07 : |
| |
| 1) DISCUSSED THE NEED FOR CUT SECTIONS OF THE |
| STAIRTOWER# 10 THIRD FLOOR INDICATING A 2 HR RATING |
| BETWEEN THE A/C DUCT AND |
| STAIRWELL AS WELL AS THE MOVING THE FIRE DAMPERS FROM |
| WITHIN THE STAIRTOWER WALLS TO ALLOW FOR ACCESS PANELS |
| OUTSIDE OF THE STAIR TOWER. |
| |
| 2) STIAR WAY # 11 DISCUSSED THE NEED OF A CUT SECTION |
| THROUGH THE STAIRWAY INDICATING THE PLACEMENT OF THE |
| MEZZANINE FLOOR THAT WILL KEEP THE DUCTWORK FROM |
| ENTERING STAIRTOWER #7. |
| |
| 3) THE THIRD ISSUE THAT WAS ALSO BROUGHT UP THAT NO |
| SHAFT WALL WILL BE NECESSARY IN THE MEZZANINE STAIRWAY |
| SINCE IT IS WITHIN THE STORY. THERE ARE CONCERNS ON THE |
| REQUIRED WIDTH OF THE STAIR! |
| |
| 4) SHEET A8-0.1DOORS MISSING FOOTNOTE :1 HR RATED |
| DOOR MISSING FOOTNOTE "D&E" |
| A1-120-A |
| A1-201-A |
| A2-008-A |
| A2-001-A |
| |
| 5) SHEET A8-0.2 DOORS MISSING FOOTNOTE: 1 HR RATED DOOR |
| MISSING FOOTNOTE "D&E" |
| C3-105-A |
| C3-106-A |
| C3-107-A |
| C3-108-A |
| C3-110-A |
| |
| 6)SHEET A9-3.1 COMMENT 1C & 1D. |
| |
| 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| REQUIREMENT, THE SPECIFIC |
| REQUIREMENT SHALL BE APPLICABLE. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |