Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop E
Sequence Number 21
Notes
Date Text
2008-07-10 17:09:13** DENIEDREVIEW OF REVISIONS **
  
 REV 17A
  
 1) NOTE: PLEASE PROVIDE REVISED LIGHTING PLANS FOR
 AREAS WHICH WILL BE OCCUPIED UNDER EMERGENCY
 CONDITIONS. ANY LOCATIONS SUCH AS CALL CENTER, IT
 TRAINING, IT ROOM ETC NEEDS TO CONTAIN BATTERY BACK UP
 FIXTURES OF SOME TYPE TO MEET 1FT CANDLE MINIMUM UNDER
 EGRESS CONDITIONS.
 LS 101 7.8, 7.9
  
 2) NOTE: PLEASE BE SURE THE LAYERS FOR SITE LIGHTING ON
 ALL SHEETS ARE ON TO SHOW REVISED CIRCUITING. SEVERAL
 FIXTURES WERE RELOCATED WHICH IS OK, HOWEVER COULD NOT
 LOCATE ANY OF THE NEW CIRCUITING ALONG WITH
 COORDINATION OF PANEL SCHEDULES.
 408.4.
 FBC 106.1.2, 106.1.1 FOR ADDITIONAL INFORMATION AND
 CLARITY OF PLANS.
  
 3) NOTE: PLEASE SEE E1-1.1 WHICH INDICATES RECEPTACLES
 IN THE FIRE COMMAND ROOM TO A PANEL 1LEG.HOWEVER NO
 PANEL 1LEG WAS SHOWN ON SUBMITTED. THIS MAY BE A
 MISPRINT FOR ANOTHER PANEL.
 NEC 408.4, 310.16 ETC
 FBC 106.1.1
  
 4) NOTE: PLEASE COMPLETE THE TRANSFORMER LEGEND FOR THE
 NEW 30KVA UNITS NOW ON PLANS. NO PRIMARY OR SECONDARY
 CONDUCTORS ARE NOTED OR SHOWN. SEE OTHER COMMENTS BELOW
 FOR OTHER NEW PANELS.
 310.16, 240.4, 240.21 ETC
 FBC 106.1.1
  
 5) NOTE: PLEASE SEE THE RISER WHICH INDICATES NEW
 TRANSFORMERS HOWEVER THEY DO NOT INDICATE NAY GROUNDING
 ELECTRODE SYSTEM FOR SEPARATELY DERIVED SYSTEMS AS PART
 OF THE EXISTING GROUNDING RISER.
 PLEASE REVISE AND ALSO INDICATE CONDUCTOR SIZES.
 250.20,250.30,250.66,250.58
 FBC 106.1.1, 106.1.2
  
 6) NOTE: PLEASE SEE THE RISER SHEET WHICH INDICATES NO
 LOADS ON THE EMERGENCY SYSTEMS. THESE ARE ACTUALLY
 SHOWN BLANK WITH XXX. PLEASE EXPLAIN HOW THE LOADS
 UNDER EMERGENCY ARE DIFFERENT THAN THE LOADS UNDER
 NORMAL AS SHOWN ON PREVIOUS PLANS. WHAT LOAD SHEDDING
 IS PROVIDED TO REDUCE LOADS?
 220, 700,701,702
 FBC106.1.2, 106.1.1
  
 7) NOTE: PLEASE SEE PANEL 1TV WHICH INDICATES THIS
 BEING FED FROM 1DPHEA, HOWEVER BASED ON REVISED PLANS,
 PANELS ETC THIS SHOULD INDICATE BEING FED FROM
 1DPHE-OP. PLEASE ADJUST
 FBC 106.1.1,
 NEC 408.4
  
 8) NOTE: PLEASE SEE 1TV WHICH INDICATES BRANCH AS
 EMERGENCY/ LIFE SAFETY. PLEASE ADJUST AS THIS IS AN
 OPTIONAL STAND-BY PANEL.
 702, 408
 FBC 106.1.1
  
 9) NOTE: PLEASE SEE PANEL 1TV WHICH IS SHOWN AS 100AMP
 YET THE CIRCUIT SHOWN ON 1DPHE-OP SHOWS A 150AMPS
 BREAKER FEED.
 THIS OVER CURRENT PROTECTION EXCEEDS THE RATING OF
 PANEL.
  
 10) NOTE: PLEASE SEE 1TV WHICH AS NOTED ABOVE IS SHOWN
 AS A 100AMP PANEL YET THE RISER SHOWS THIS SAME PANEL
 AS 225AMP.
 PLEASE COORDINATE.
 NEC 408, 215, 240 ETC
 FBC 106.1.1
  
 11) NOTE: PLEASE SEE 1DPHE-OP AS THE PANEL SCHEDULE IS
 BLANK FOR CONDUCTORS. PLEASE COMPLETE AS THERE ARE
 SEVERAL ITEMS WHICH NEED TO BE REVIEWED FOR CODE
 COMPLIANCE. PLEASE BE SURE TO SEE OTHER COMMENTS WITH
 RESPECT TO TRANSFORMER CONDUCTORS ON THE PRIMARY SIDE.
 240.21, 240.4, 310.16, ETC
 FBC 106.1.1
  
 12) NOTE: PLEASE SEE PANEL 1DPHE-OP WHICH INDICATES A
 LOAD OF 58AMP/20.9 KVA FOR 1LEDCC. HOW IS THIS AMPERAGE
 THE SAME AS SHOWN ON PANEL 1LEDCC WHEN THE VOLTAGE ON
 1LEDCC IS ACTUALLY 120/208 AND THE VOLTAGE ON 1DPHE-OP
 IS 277/480V?
 PLEASE COORDINATE AND ADJUST.
 FBC 106.1.1
 NEC 220, 408.4 ETC
  
 13) NOTE: PLEASE SEE PANEL SCHEDULE FOR 1LEDCC WHICH
 INDICATES BEING FED FROM 1HEE, YET THE PANEL 1HEE DOES
 NOT FEED THIS PANEL. SEE NOTE #12 ABOVE AS THIS PANEL
 IS FED FROM 1-DPHE-OP.
 408, 220 ETC
 FBC 106.1.1
  
 14) NOTE: PLEASE SEE PANEL 1HEE AS THE OVER CURRENT
 PROTECTION WHICH IS SHOWN ON PANEL TO FEED PANEL 1HED
 IS SHOWN AS 100AMP YET THE FEEDERS ARE ONLY SHOWN AS
 #8. THE #8 CONDUCTORS AS SHOWN ARE ONLY RATED FOR
 55AMPS BASED ON 310.16, 110.14
  
 15) NOTE: PLEASE SEE PANELS 1LETD, 2LETD, 1GHEE, 4IT2,
 1GLEE ETC WHICH ALL INDICATE THE PANELS BEING LOCATED
 ON THE FIRST FLOOR AND ALL LOCATED IN THE CALL CENTER.
 THE ELECTRICAL POWER PLANS CLEARLY ONLY SHOW ONE
 PANEL.
 PLEASE KNOW AS THE REVISED ELECTRICAL ROOMS HAVE NOT
 YET BEEN SUBMITTED REVIEW FOR CODE COMPLIANCE FOR
 LOCATIONS CAN NOT BE REVISED AT THIS TIME.
 PLEASE COORDINATE PANEL SCHEDULES WITH ACTUAL
 LOCATIONS.
 PLEASE SUBMIT REVISED PLANS TO SHOW THE LOCATIONS OF
 ALL PANELS.
 110.26, 240.24 ETC
 FBC 106.1.1
  
 16) NOTE: PLEASE SEE CALL CENTER A1.111 WHICH INDICATES
 CIRCUIT 1LED-33 YET THE PANEL SCHEDULE IS BLANK FOR
 THIS SAME CIRCUIT.
 REVISION 15A WHICH IS A SINGLE SHEET HAS THIS SAME ITEM
 HOWEVER WILL BE REDLINED. WILL NEED TO BE REVISED.
 408.4, 310.16, 240.4, 220.
 FBC 106.1.2, 106.1.1
  
 17) NOTE: PLEASE SEE 1HED WHICH THE SCHEDULE INDICATES
 THIS PANEL BEING FROM 1DPHEA YET 1DPHEA DOES NOT LIST
 THIS PANEL.
 PLEASE SEE 1HEE!!
 PLEASE COORDINATE.
 FBC 106.1.1
 NEC 408.4
  
 18) NOTE: PLEASE SEE SHEET 6-7.0 WHICH INDICATES A
 PANELLCP1D YET THE PANEL SHOWN IS 1LS1
 PLEASE COORDINATE PANELS, PLANS.
 NEC 408,
 FBC 106.1.1
  
 19) NOTE: PLEASE SEE 1GHEA WHICH IS SHOWN WITH TAPPED
 CONDUCTORS FROM ATS3 YET THE PANEL SCHEDULE FOR THIS
 PANEL 1GHEA INDICATES THIS PANEL AS MLO (MAIN LUG
 ONLY). THIS MAY NOT BE A MLO PANEL. PLEASE SEE 240.21,
 408.36, 240.4, 310.16 AS TAPPED CONDUCTORS ARE REQUIRED
 TO TERMINATE INTO OVER CURRENT PROTECTION.
 PLEASE REVISE AND ADJUST.
 FBC 106.1.1
  
 20) NOTE: PLEASE SEE PANEL SCHEDULE FOR 4IT WHICH
 INDICATES THIS AS AN EMERGENCY/LIFE SAFETY PANEL.
 PLEASE REVISE AND ADJUST.
 408.4, 700.1,701,702
 FBC 106.1.1 FOR COORDINATION.
  
 21) NOTE: PLEASE SEE PANEL 4IT WHICH INDICATES THIS
 PANEL BEING FED FROM 1HEE YET 1HEE DOES NOT LIST THIS
 PANEL.
 APPEARS TO BE A MISPRINT, PLEASE COORDINATE PLANS,
 PANELS ETC
 FBC 106.1.1
 NEC 408.4
  
 22) NOTE: PLEASE SEE CIRCUITING FOR LIGHTING IN TICKET
 BOOTH ROOM IN GARAGE WHICH ISMISSING A CIRCUIT.
 PLEASE SEE ONE CIRCUIT WHICH APPEARS TO BE NOTED TO ONE
 FIGURE IN ROOM IS 1GHA-22 YET THIS CIRCUIT ACTUALLY IS
 SHOWN ON THE PLANS AND PANEL SCHEDULE FOR CANOPY
 LIGHTS.
 PLEASE COORDINATE.
 408.4
 FBC 106.1.1
  
 23) NOTE: PLEASE VERIFY THE ACTUAL WORDING NOTED IN
 OCTAGONAL NOTE #1 FOR GARAGE ENTRANCE LIGHTS. THE NOTE
 MENTIONS LIGHTS TO BE OFF AT DUSK. SHOULD THIS NOT READ
 *ON* AT DUSK?
 PLEASE PROVIDE INFORMATION FOR INTENT.
 FBC106.1.1 FOR CLARITY AND 106.1.2 FOR ADDITIONAL
 INFORMATION.
  
 24) NOTE: AS NOTED ABOVE PLEASE INCLUDED LOCATIONS OF
 PANELS AND ALL NEW EQUIPMENT ON PLANS. PANELS SUCH AS
 1LETD, 2LETD, TAPPED CONDUCTORS ETC NEED TO BE VERIFIED
 FOR CODE COMPLIANCE.
 FBC 106.1.1 FOR CLARITY
 110.26, 240.24 ETC
  
 25) NOTE: PLEASE SEE E1-3.1 WHICH INDICATES REVISED
 CIRCUITS TO A PANEL 2LEDT WHICH APPEARS TO BE A
 MISPRINT FOR WHAT SHOULD BE PANEL 2LETD.
 PLEASE SEE ROOMS A3.116, A4.3.14
  
 26) NOTE: PLEASE LABEL NEW CU (CONDENSING UNITS) ON
 ROOF.
 CU#1, CU#2 ETC.
 FBC 106.1.1 FOR CLARITY ON PLANS AND 106.1.2 FOR
 ADDITIONAL INFORMATION.
  
 27) NOTE: PLEASE REVISE AND COMPLETE ALL PANEL
 SCHEDULES FOR CIRCUITS TO SPECIFIC ROOMS AND
 LOCATIONS.
 PLEASE KNOW THAT LISTING *STAIRWELL LIGHTING*IN LIEU
 OF STAIRWELL #1, STAIRWELL #5, #7 ETC WAS PERMITTED AND
 OK ON INITIAL PLANS AS CIRCUITS WOULD BE REVISED ALONG
 THE PROJECT. HOWEVER PLEASE KNOW THAT ALL PANEL
 SCHEDULES NEED TO BE REVISED FOR THESE CIRCUITS AS WELL
 AS OTHERS WHICH LIST ONLY A GENERIC DESIGNATION. THE
 DESIGNATION MAY BE ALPHA OR NUMERIC HOWEVER THIS
 DESIGNATION NEEDS TO BE THE ACTUAL DESIGNATION ON
 PLANS.
 408.4 **SEE HANDBOOKS WHICH STATES GENERIC *LIGHTS* OR
 *RECEPTACLES* IS NOT ACCEPTABLE.
 FBC 106.1.1, 106.1.2, 106.5
  
 28) NOTE: PLEASE VERIFY HOW REVISION 15A IS ACTUALLY A
 REVISION WHICH IS AFTER REVISION 17.REVISION 15
 SHEETS HAVE BEEN REDLINED AND NEED TO HAVE REVISION
 NUMBERS COORDINATED.
  
  
 ** THE SHEETS FOLLOWING ARE LISTED AT THIS TIME AS OK,
 HOWEVER BASED ON NOTES ABOVE FOR BACK UP LIGHTING NEED
 ETC SOME OF THESE SHEETS MAY NEED TO BE REVISED.
 PLEASE KNOW THAT ANY OF THESE SHEETS WHICH MAY NOT NEED
 TO BE REVISED SHOULD BE TURNED BACK IN WITH OTHER
 REVISED SHEETS WHICH ARE ADDRESSING COMMENTS ABOVE.
  
 ** IF THERE ARE ANY QUESTIONS ON HOW THIS NEEDS TO TAKE
 PLACE, PLEASE DO NOT HESITATE IN CONTACTING THIS
 OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]