2008-07-10 17:09:13 | ** DENIEDREVIEW OF REVISIONS ** |
| |
| REV 17A |
| |
| 1) NOTE: PLEASE PROVIDE REVISED LIGHTING PLANS FOR |
| AREAS WHICH WILL BE OCCUPIED UNDER EMERGENCY |
| CONDITIONS. ANY LOCATIONS SUCH AS CALL CENTER, IT |
| TRAINING, IT ROOM ETC NEEDS TO CONTAIN BATTERY BACK UP |
| FIXTURES OF SOME TYPE TO MEET 1FT CANDLE MINIMUM UNDER |
| EGRESS CONDITIONS. |
| LS 101 7.8, 7.9 |
| |
| 2) NOTE: PLEASE BE SURE THE LAYERS FOR SITE LIGHTING ON |
| ALL SHEETS ARE ON TO SHOW REVISED CIRCUITING. SEVERAL |
| FIXTURES WERE RELOCATED WHICH IS OK, HOWEVER COULD NOT |
| LOCATE ANY OF THE NEW CIRCUITING ALONG WITH |
| COORDINATION OF PANEL SCHEDULES. |
| 408.4. |
| FBC 106.1.2, 106.1.1 FOR ADDITIONAL INFORMATION AND |
| CLARITY OF PLANS. |
| |
| 3) NOTE: PLEASE SEE E1-1.1 WHICH INDICATES RECEPTACLES |
| IN THE FIRE COMMAND ROOM TO A PANEL 1LEG.HOWEVER NO |
| PANEL 1LEG WAS SHOWN ON SUBMITTED. THIS MAY BE A |
| MISPRINT FOR ANOTHER PANEL. |
| NEC 408.4, 310.16 ETC |
| FBC 106.1.1 |
| |
| 4) NOTE: PLEASE COMPLETE THE TRANSFORMER LEGEND FOR THE |
| NEW 30KVA UNITS NOW ON PLANS. NO PRIMARY OR SECONDARY |
| CONDUCTORS ARE NOTED OR SHOWN. SEE OTHER COMMENTS BELOW |
| FOR OTHER NEW PANELS. |
| 310.16, 240.4, 240.21 ETC |
| FBC 106.1.1 |
| |
| 5) NOTE: PLEASE SEE THE RISER WHICH INDICATES NEW |
| TRANSFORMERS HOWEVER THEY DO NOT INDICATE NAY GROUNDING |
| ELECTRODE SYSTEM FOR SEPARATELY DERIVED SYSTEMS AS PART |
| OF THE EXISTING GROUNDING RISER. |
| PLEASE REVISE AND ALSO INDICATE CONDUCTOR SIZES. |
| 250.20,250.30,250.66,250.58 |
| FBC 106.1.1, 106.1.2 |
| |
| 6) NOTE: PLEASE SEE THE RISER SHEET WHICH INDICATES NO |
| LOADS ON THE EMERGENCY SYSTEMS. THESE ARE ACTUALLY |
| SHOWN BLANK WITH XXX. PLEASE EXPLAIN HOW THE LOADS |
| UNDER EMERGENCY ARE DIFFERENT THAN THE LOADS UNDER |
| NORMAL AS SHOWN ON PREVIOUS PLANS. WHAT LOAD SHEDDING |
| IS PROVIDED TO REDUCE LOADS? |
| 220, 700,701,702 |
| FBC106.1.2, 106.1.1 |
| |
| 7) NOTE: PLEASE SEE PANEL 1TV WHICH INDICATES THIS |
| BEING FED FROM 1DPHEA, HOWEVER BASED ON REVISED PLANS, |
| PANELS ETC THIS SHOULD INDICATE BEING FED FROM |
| 1DPHE-OP. PLEASE ADJUST |
| FBC 106.1.1, |
| NEC 408.4 |
| |
| 8) NOTE: PLEASE SEE 1TV WHICH INDICATES BRANCH AS |
| EMERGENCY/ LIFE SAFETY. PLEASE ADJUST AS THIS IS AN |
| OPTIONAL STAND-BY PANEL. |
| 702, 408 |
| FBC 106.1.1 |
| |
| 9) NOTE: PLEASE SEE PANEL 1TV WHICH IS SHOWN AS 100AMP |
| YET THE CIRCUIT SHOWN ON 1DPHE-OP SHOWS A 150AMPS |
| BREAKER FEED. |
| THIS OVER CURRENT PROTECTION EXCEEDS THE RATING OF |
| PANEL. |
| |
| 10) NOTE: PLEASE SEE 1TV WHICH AS NOTED ABOVE IS SHOWN |
| AS A 100AMP PANEL YET THE RISER SHOWS THIS SAME PANEL |
| AS 225AMP. |
| PLEASE COORDINATE. |
| NEC 408, 215, 240 ETC |
| FBC 106.1.1 |
| |
| 11) NOTE: PLEASE SEE 1DPHE-OP AS THE PANEL SCHEDULE IS |
| BLANK FOR CONDUCTORS. PLEASE COMPLETE AS THERE ARE |
| SEVERAL ITEMS WHICH NEED TO BE REVIEWED FOR CODE |
| COMPLIANCE. PLEASE BE SURE TO SEE OTHER COMMENTS WITH |
| RESPECT TO TRANSFORMER CONDUCTORS ON THE PRIMARY SIDE. |
| 240.21, 240.4, 310.16, ETC |
| FBC 106.1.1 |
| |
| 12) NOTE: PLEASE SEE PANEL 1DPHE-OP WHICH INDICATES A |
| LOAD OF 58AMP/20.9 KVA FOR 1LEDCC. HOW IS THIS AMPERAGE |
| THE SAME AS SHOWN ON PANEL 1LEDCC WHEN THE VOLTAGE ON |
| 1LEDCC IS ACTUALLY 120/208 AND THE VOLTAGE ON 1DPHE-OP |
| IS 277/480V? |
| PLEASE COORDINATE AND ADJUST. |
| FBC 106.1.1 |
| NEC 220, 408.4 ETC |
| |
| 13) NOTE: PLEASE SEE PANEL SCHEDULE FOR 1LEDCC WHICH |
| INDICATES BEING FED FROM 1HEE, YET THE PANEL 1HEE DOES |
| NOT FEED THIS PANEL. SEE NOTE #12 ABOVE AS THIS PANEL |
| IS FED FROM 1-DPHE-OP. |
| 408, 220 ETC |
| FBC 106.1.1 |
| |
| 14) NOTE: PLEASE SEE PANEL 1HEE AS THE OVER CURRENT |
| PROTECTION WHICH IS SHOWN ON PANEL TO FEED PANEL 1HED |
| IS SHOWN AS 100AMP YET THE FEEDERS ARE ONLY SHOWN AS |
| #8. THE #8 CONDUCTORS AS SHOWN ARE ONLY RATED FOR |
| 55AMPS BASED ON 310.16, 110.14 |
| |
| 15) NOTE: PLEASE SEE PANELS 1LETD, 2LETD, 1GHEE, 4IT2, |
| 1GLEE ETC WHICH ALL INDICATE THE PANELS BEING LOCATED |
| ON THE FIRST FLOOR AND ALL LOCATED IN THE CALL CENTER. |
| THE ELECTRICAL POWER PLANS CLEARLY ONLY SHOW ONE |
| PANEL. |
| PLEASE KNOW AS THE REVISED ELECTRICAL ROOMS HAVE NOT |
| YET BEEN SUBMITTED REVIEW FOR CODE COMPLIANCE FOR |
| LOCATIONS CAN NOT BE REVISED AT THIS TIME. |
| PLEASE COORDINATE PANEL SCHEDULES WITH ACTUAL |
| LOCATIONS. |
| PLEASE SUBMIT REVISED PLANS TO SHOW THE LOCATIONS OF |
| ALL PANELS. |
| 110.26, 240.24 ETC |
| FBC 106.1.1 |
| |
| 16) NOTE: PLEASE SEE CALL CENTER A1.111 WHICH INDICATES |
| CIRCUIT 1LED-33 YET THE PANEL SCHEDULE IS BLANK FOR |
| THIS SAME CIRCUIT. |
| REVISION 15A WHICH IS A SINGLE SHEET HAS THIS SAME ITEM |
| HOWEVER WILL BE REDLINED. WILL NEED TO BE REVISED. |
| 408.4, 310.16, 240.4, 220. |
| FBC 106.1.2, 106.1.1 |
| |
| 17) NOTE: PLEASE SEE 1HED WHICH THE SCHEDULE INDICATES |
| THIS PANEL BEING FROM 1DPHEA YET 1DPHEA DOES NOT LIST |
| THIS PANEL. |
| PLEASE SEE 1HEE!! |
| PLEASE COORDINATE. |
| FBC 106.1.1 |
| NEC 408.4 |
| |
| 18) NOTE: PLEASE SEE SHEET 6-7.0 WHICH INDICATES A |
| PANELLCP1D YET THE PANEL SHOWN IS 1LS1 |
| PLEASE COORDINATE PANELS, PLANS. |
| NEC 408, |
| FBC 106.1.1 |
| |
| 19) NOTE: PLEASE SEE 1GHEA WHICH IS SHOWN WITH TAPPED |
| CONDUCTORS FROM ATS3 YET THE PANEL SCHEDULE FOR THIS |
| PANEL 1GHEA INDICATES THIS PANEL AS MLO (MAIN LUG |
| ONLY). THIS MAY NOT BE A MLO PANEL. PLEASE SEE 240.21, |
| 408.36, 240.4, 310.16 AS TAPPED CONDUCTORS ARE REQUIRED |
| TO TERMINATE INTO OVER CURRENT PROTECTION. |
| PLEASE REVISE AND ADJUST. |
| FBC 106.1.1 |
| |
| 20) NOTE: PLEASE SEE PANEL SCHEDULE FOR 4IT WHICH |
| INDICATES THIS AS AN EMERGENCY/LIFE SAFETY PANEL. |
| PLEASE REVISE AND ADJUST. |
| 408.4, 700.1,701,702 |
| FBC 106.1.1 FOR COORDINATION. |
| |
| 21) NOTE: PLEASE SEE PANEL 4IT WHICH INDICATES THIS |
| PANEL BEING FED FROM 1HEE YET 1HEE DOES NOT LIST THIS |
| PANEL. |
| APPEARS TO BE A MISPRINT, PLEASE COORDINATE PLANS, |
| PANELS ETC |
| FBC 106.1.1 |
| NEC 408.4 |
| |
| 22) NOTE: PLEASE SEE CIRCUITING FOR LIGHTING IN TICKET |
| BOOTH ROOM IN GARAGE WHICH ISMISSING A CIRCUIT. |
| PLEASE SEE ONE CIRCUIT WHICH APPEARS TO BE NOTED TO ONE |
| FIGURE IN ROOM IS 1GHA-22 YET THIS CIRCUIT ACTUALLY IS |
| SHOWN ON THE PLANS AND PANEL SCHEDULE FOR CANOPY |
| LIGHTS. |
| PLEASE COORDINATE. |
| 408.4 |
| FBC 106.1.1 |
| |
| 23) NOTE: PLEASE VERIFY THE ACTUAL WORDING NOTED IN |
| OCTAGONAL NOTE #1 FOR GARAGE ENTRANCE LIGHTS. THE NOTE |
| MENTIONS LIGHTS TO BE OFF AT DUSK. SHOULD THIS NOT READ |
| *ON* AT DUSK? |
| PLEASE PROVIDE INFORMATION FOR INTENT. |
| FBC106.1.1 FOR CLARITY AND 106.1.2 FOR ADDITIONAL |
| INFORMATION. |
| |
| 24) NOTE: AS NOTED ABOVE PLEASE INCLUDED LOCATIONS OF |
| PANELS AND ALL NEW EQUIPMENT ON PLANS. PANELS SUCH AS |
| 1LETD, 2LETD, TAPPED CONDUCTORS ETC NEED TO BE VERIFIED |
| FOR CODE COMPLIANCE. |
| FBC 106.1.1 FOR CLARITY |
| 110.26, 240.24 ETC |
| |
| 25) NOTE: PLEASE SEE E1-3.1 WHICH INDICATES REVISED |
| CIRCUITS TO A PANEL 2LEDT WHICH APPEARS TO BE A |
| MISPRINT FOR WHAT SHOULD BE PANEL 2LETD. |
| PLEASE SEE ROOMS A3.116, A4.3.14 |
| |
| 26) NOTE: PLEASE LABEL NEW CU (CONDENSING UNITS) ON |
| ROOF. |
| CU#1, CU#2 ETC. |
| FBC 106.1.1 FOR CLARITY ON PLANS AND 106.1.2 FOR |
| ADDITIONAL INFORMATION. |
| |
| 27) NOTE: PLEASE REVISE AND COMPLETE ALL PANEL |
| SCHEDULES FOR CIRCUITS TO SPECIFIC ROOMS AND |
| LOCATIONS. |
| PLEASE KNOW THAT LISTING *STAIRWELL LIGHTING*IN LIEU |
| OF STAIRWELL #1, STAIRWELL #5, #7 ETC WAS PERMITTED AND |
| OK ON INITIAL PLANS AS CIRCUITS WOULD BE REVISED ALONG |
| THE PROJECT. HOWEVER PLEASE KNOW THAT ALL PANEL |
| SCHEDULES NEED TO BE REVISED FOR THESE CIRCUITS AS WELL |
| AS OTHERS WHICH LIST ONLY A GENERIC DESIGNATION. THE |
| DESIGNATION MAY BE ALPHA OR NUMERIC HOWEVER THIS |
| DESIGNATION NEEDS TO BE THE ACTUAL DESIGNATION ON |
| PLANS. |
| 408.4 **SEE HANDBOOKS WHICH STATES GENERIC *LIGHTS* OR |
| *RECEPTACLES* IS NOT ACCEPTABLE. |
| FBC 106.1.1, 106.1.2, 106.5 |
| |
| 28) NOTE: PLEASE VERIFY HOW REVISION 15A IS ACTUALLY A |
| REVISION WHICH IS AFTER REVISION 17.REVISION 15 |
| SHEETS HAVE BEEN REDLINED AND NEED TO HAVE REVISION |
| NUMBERS COORDINATED. |
| |
| |
| ** THE SHEETS FOLLOWING ARE LISTED AT THIS TIME AS OK, |
| HOWEVER BASED ON NOTES ABOVE FOR BACK UP LIGHTING NEED |
| ETC SOME OF THESE SHEETS MAY NEED TO BE REVISED. |
| PLEASE KNOW THAT ANY OF THESE SHEETS WHICH MAY NOT NEED |
| TO BE REVISED SHOULD BE TURNED BACK IN WITH OTHER |
| REVISED SHEETS WHICH ARE ADDRESSING COMMENTS ABOVE. |
| |
| ** IF THERE ARE ANY QUESTIONS ON HOW THIS NEEDS TO TAKE |
| PLACE, PLEASE DO NOT HESITATE IN CONTACTING THIS |
| OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |