Date |
Text |
2006-12-23 17:38:49 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| FROM PREVIOUS REVIEW: |
| FROM PREVIOUS REVIEW: |
| |
| 1. OK |
| 2. OK |
| |
| 3. SHT P1-1.1 PUMP ROOM A1-112. RPZV BACKFLOW SHALL BE |
| INSTALLED A MAXIMUM OF 4' ABOVE THE FLOOR FOR |
| CERTIFICATION AND SERVICE. |
| ****RESPONSE NOTED, HEIGHT TO BE INDICATED FOR THE |
| BACKFLOWS TO BE A MAXIMUM OF 4' ABOVE THE FLOOR. |
| ****RESPONSE NOTED, BUT PLANS INDICATE MINIMUM 4' ABOVE |
| THE FLOOR. THE REQUIREMENT IS FOR MAXIMUM 4' ABOVE THE |
| FLOOR. |
| |
| 4. OK |
| |
| 5. SHTS P1-1.1 THRU P1-1.3 CLEANOUTS REQUIRED BY |
| SECTIONS 708.3.1, 708.3.2, 708.3.4, 708.3.5 AND 11-8.1 |
| (FOR STORM) SHALL BE SHOWN ON THE PLANS. ****RESPONSE |
| NOTED, BUT COMMENT NOT ADDRESSED. MANY CLEANOUTS |
| REQUIRED ARE NOT INDICATED. MANY CLEANOUTS REQUIRED ARE |
| NOT SHOWN. CLEANOUTS AT THE BASE OF STACKS AS SHOWN ARE |
| INCORRECT. THEY DO NOT CLEANOUT THE BASE OF THE STACK. |
| ALSO SHOW THE CLEANOUTS REQUIRED ON THE RISER |
| DIAGRAMS. |
| ****RESPONSE NOTED, BUT THE CLEANOUT SHOWN ON P3-3.0 |
| DETAIL 1 AS SHOWN IS CORRECT, BUT IT'S NOT SHOWN ON THE |
| FLOOR PLAN. PLEASE CORRELATE INFORMATION ON ALL SHEETS. |
| ALSO SEE RISERS P/1, P/7 & P/8. |
| |
| 6.OK |
| 7.OK |
| 8.OK |
| 9.OK |
| 10. OK |
| 11. OK |
| 12. OK |
| 13. OK |
| |
| 14. SHT P1-6.0 SUBMIT CALCULATIONS FOR PRIMARY AND |
| SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF EACH |
| AREA, AND SHOW 1/2 AREA OF ALL VERTICAL WALLS, |
| INCLUDING PARAPETS, AS WELL AS ALL AREAS OF ROOFS |
| DRAINING ONTO THE ROOF FROM ABOVE IN THE CALCULATIONS. |
| SECTIONS 1106, AND 1107 WITH ALL SUBSECTIONS. SHOW THE |
| LOCATION OF ALL SECONDARY ROOF DRAINS AND OR EMERGENCY |
| OVERFLOW SCUPPERS. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT NO CALCULATIONS WERE |
| SUBMITTED. |
| ****RESPONSE NOTED, BUT THE CALCULATIONS ARE NOT |
| CORRECT. NO VERTICAL CONTRIBUTION IS SHOWN FOR THE |
| LOWER ROOFS. (A1 THRU A4, A7 THRU A9, E1 THRU E4, E7 |
| THRU E9, E1 THRU E4, & H1 THRU H4). THE WALL AT COL. |
| LINES 4&7 BETWEEN COL. LINES A&D, CALCULATIONS INDICATE |
| 7', WHICH IS SUPPOSED TO BE 1/2 THE WALL HEIGHT. BY |
| LOOKING AT A SECTION OF THE WALL, THE HEIGHT IS 20' AND |
| 1/2 THE WALL HEIGHT SHOULD BE 10'. (SEE A4-2.0WHICH |
| SHOW THE WALL TO BE 18', AND IF ITS SIMILAR TO DETAIL 3 |
| ON SHT A5-1.1 WILL HAVE A 2' PARAPET WALL ON TOP OF THE |
| ROOF LINE. PLEASE RECHECK ALL CALCULATIONS FOR THE ROOF |
| AREAS. |
| |
| 15. OK |
| 16. OK (SHOWN ON SHT P2-1.0U) |
| 17. OK |
| 18. OK |
| 19. OK |
| 20. OK |
| 21. OK |
| 22. OK |
| 23. OK |
| 24. OK |
| 25. OK |
| 26. OK |
| 27. OK |
| 28. OK |
| 29. OK |
| 30. OK |
| 31. OK |
| 32. OK |
| 33. OK |
| 34. OK |
| 35. OK |
| |
| 36. SUBMIT A SANITARY HORIZONTAL RISER ISOMETRIC AND |
| VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, TRAPS, |
| VENTS, CLEANOUTS, OFFSETS, RISER NUMBERS AND DFU'S AS |
| THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3. |
| ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN, |
| ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND DFU'S ARE NOT |
| SHOWN AS THEY ACCUMULATE IN THE SYSTEM. ALSO INDICATE |
| ON THE FIRST FLOOR WHERE ALL RISERS BEGIN IN THE |
| SYSTEM. |
| ****RESPONSE NOTED, BUT SHT P3-1.0 RISER 1, LAVS DO NOT |
| REFLECT THE FLOOR PLAN 2ND FLOOR C2-1.03. - DOES NOT |
| REFLECT THE FLOOR PLAN C4.103/C4.104 DRINKING FOUNTAINS |
| SHOW 3, FLOOR PLAN SHOWS 2. - CLEANOUT NOT SHOWN AT THE |
| BASE OF P/1. - NOT ALL PIPE SIZES SHOWN.-SHT P3-2.0 |
| RISER P/2 CLEANOUT DOWNSTREAM OF JANITOR SINK IN ROOM |
| C4.101 NOT INSTALLED PER SECTION 706.3. SECOND CLEANOUT |
| AT THE BASE OF P/2 NOT REQUIRED AS IT DOES NOT CLEANOUT |
| THE BASE OF THE STACK, NOR DOES IT REFLECT THE FLOOR |
| PLAN. - FLOOR DRAIN PIPING IN ROOM D1.101 AS INDICATED |
| IS BEING INSTALLED ABOVE THE FLOOR. - EACH DRINKING |
| FOUNTAIN SHALL HAVE ITS OWN TRAP. SAFE WASTE FOR THE |
| FIXTURES IS NOT APPROVED.(SEE ROOMS D1.101, D1.108, |
| AND A3.111). -CLEANOUTS ARE REQUIRED AT THE BASE OF |
| STACKS P/4 & P/10. - CLEANOUT FOR P/7 NOT INSTALLED AT |
| THE BASE OF P/7. -THE NEW SANT. PIPING TO TOILET ROOM |
| D2.105 NOT SHOWN ON THE FLOOR PLAN. -SHOW ALL TOILET |
| ROOM NUMBERS ON THE RISER DIAGRAM. - SHOW ALL PIPE |
| SIZES. THE PIPE SIZES ARE NOT SHOWN ON MANY PIPES.- |
| SHT P3-3.0A TWO WAY CLEANOUT IS REQUIRED NEAR THE |
| JUNCTION OF THE BUILDING DRAIN AND THE BUILDING SEWER. |
| (DETAIL 1).-THE RISER DIAGRAM DOES NOT REFLECT THE |
| FLOOR PLAN FOR A1.05 & A1.106. AN EXTRA FLOOR DRAIN IS |
| INDICATED THAT IS NOT SHOWN ON THE FLOOR PLAN.- |
| A3.102 & A3.103 ONLY SHOWS 2 LAVS ON THE RISER AND THE |
| FLOOR PLAN SHOWS 4.-A4.103 & A4.104TWO W/C'S ARE |
| MISSING FROM THE RISER THAT ARE SHOWN ON THE FLOOR |
| PLAN.-A4.105NO FLOOR DRAIN AND A SECOND SINK ARE |
| SHOWN ON THE FLOOR PLAN THAT ARE NOT SHOWN ON THE RISER |
| DIAGRAM. (JANITOR ROOM).-A5.105 SHOWS THE BRANCH |
| LINE CONNECTING NEAR THE DRINKING FOUNTAINS ON THE |
| FLOOR PLAN, BUT CONNECTING DOWNSTREAM OF THE NEXT |
| FIXTURES ON THE RISER DIAGRAM.-A CLEANOUT IS |
| REQUIRED AT THE BASE OF RISER P/8-ALL RISER |
| DIAGRAMS,CHECK ALL PIPE SIZES, MAKE SURE THE RISER |
| DIAGRAMS REFLECT THE FLOOR PLAN FOR BOTH THE SANITARY |
| AND THE VENTING.SECTIONS106.1.1, 106..1.2, 706.3, |
| 708.3.4, 708.3.5, 100.2.1. |
| |
| 37. SUBMIT A STORM HORIZONTAL RISER ISOMETRIC DIAGRAM & |
| VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, OFFSETS, |
| & CLEANOUTS AND INDICATE THE RISER NUMBERS. SHOW THE |
| SQUARE FOOTAGE AS IT ACCUMULATES IN THE SYSTEM. SECTION |
| 106.3.5.1.3. |
| ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN, |
| ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND SQUARE |
| FOOTAGE AS IT ACCUMULATES IN THE SYSTEM IS NOT |
| INDICATED. |
| ****RESPONSE NOTED, BUT THE GARAGE STORM INDICATES A |
| TOTAL OF 10,498SF. THE TOTAL AREA WITHOUT ANY VERTICAL |
| WALL/PARAPET CONTRIBUTION IS 23,663SF. PLEASE |
| RECALCULATE THE SQUARE FOOTAGE DRAINING INTO EACH |
| DRAIN. SHOW 1/2 AREA OF ALL VERTICAL WALL INCLUDING |
| PARAPETS, AS WELL AS ALL AREAS FROM ROOFS THAT DRAIN |
| ONTO THE ROOF FROM ABOVE, (SEE STAIRWELL ROOFS & |
| ELEVATOR), IN CALCULATIONS. -THE TRENCH DRAINS SHOW |
| NO SF CONTRIBUTING TO THE TOTAL SF. INDICATE THE |
| LOCATIONS OF THE DOWNSPOUTS FROM THE ROTUNDA/MECHANICAL |
| ROOF. IF THE LOCATION IS THE SAME AS SHOWN ON THE |
| ARCHITECTURAL PLANS, PLEASE EXPLAIN THE REASONING FOR |
| DIVIDING THE UPPER ROOF CONTRIBUTION TO TWO ROOF DRAINS |
| ON EACH SIDE OF THE BUILDING, WHEN ACTUALLY THE TOTAL |
| AREA WILL DRAIN TO ONE DRAIN ON EACH SIDE. THIS IS ALSO |
| A CONCERN FOR THE LOWER ROOF (FIRST STORY)ROOF DRAINS |
| ( 1736SF). PLEASE CLARIFY. |
| |
| 38. SUBMIT A WATER RISER ISOMETRIC DIAGRAM. SHOW ALL |
| PIPE SIZES, VALVES, WATER HAMMER ARRESTORS, BACKFLOW |
| PROTECTION ETC. SECTION 106.3.5.1.3. |
| ****RESPONSE NOTED, BUT NOT ALL PIPE SIZES ARE SHOWN, |
| NOT ALL REQUIRED VALVES ARE SHOWN, AND ALL WATER HAMMER |
| ARRESTORS REQUIRED BY SECTION 604.9, (ICE MAKERS, |
| DISHWASHERS, & WASH MACHINES IF FIXTURES ARE |
| PROVIDED). |
| ****RESPONSE NOTED, BUT THE VALVES ON ALL DOWN-FEED |
| WATER LINES ARE MISSING FROM MANY LAV SUPPLY LINES, |
| SOME TOILET ROOMS, SS, ETC. SECTION 106.1(4). |
| |
| 39. OK |
| |
| 40. ALL PME & FIRE PROTECTION SHEETS. PLANS SHALL BE |
| SIGNED, SEALED, AND DATED. SECTION 106.1. ALL TITLE |
| BLOCK INFORMATION REQUIRED BY FAC 61G1-23.002 AND FS |
| 471.025 SHALL BE SUBMITTED ON EACH SHEET. ****RESPONSE |
| NOTED, BUT THE SEAL USED IS NOT APPROVED. NEW SEALS |
| SHALL INDICATE THE WORD "LICENSE" IN THE SEAL. (SEE |
| ATTACHED SHEET FROM THE FLORIDA BOARD OF PROFESSIONAL |
| ENGINEERS). |
| ****RESPONSE NOTED, BUT THE SEALS OF SOME MECH. AND |
| PLUMBING SHEETS ARE STILL THE OLD SEAL. - ALSO THERE |
| SEEMS TO BE TWO SETS OF SIGNATURES FOR THE ENGINEER OF |
| RECORD. PLEASE SUBMIT A SIGNED, SEALED, DATED, |
| NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE OF THE |
| ENGINEER OF RECORD FOR OUR FILES. ONE SET OF PLANS |
| SHALL BE RETAINED FOR POSSIBLE REVIEW BY THE FLORIDA |
| BOARD OF PROFESSIONAL ENGINEERS. |
| |
| **************NEW COMMENTS************** |
| |
| 1B. SHTS P1-1.0U, P1-1.1U, P1-1.1 & P1-2.1. RWL-4 DOES |
| NOT REFLECT THE SQUARE FOOTAGE SHOWN ON RISER DIAGRAM |
| OR ROOF PLAN. PLEASE CORRELATE RISER, FLOOR PLAN, & |
| ROOF PLAN. SECTION 106.1.1. |
| ****RESPONSE NOTED. WILL RECHECK AFTER THE CALCULATIONS |
| FOR THE ROOF DRAINS HAS BEEN RESUBMITTED WITH |
| CORRECTIONS. |
| |
| 2B. SHTS P1-1.OU & P1-1.1U ALL RWL'S THAT CONNECT TO |
| RWL-4 TO BE INDICATED ON THE 1ST FLOOR. THIS WILL AID |
| IN TRACING THE RWL'S THROUGH THE BUILDING AND TO VERIFY |
| PIPE SIZES. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT ISSUE NOT ADDRESSED. |
| |
| 3B. SHTS P1-1.1U & P2-1.0U DETAIL #6 THE SINK SHALL NOT |
| DRAIN THRU THE WET VENT FOR THE TOILET ROOM. THE |
| DISCHARGE FOR THE SINK SHALL CONNECT DOWNSTREAM OF THE |
| TOILET ROOM FIXTURES. SECTION 909.1. |
| ****RESPONSE NOTED, BUT THE PIPING HAS NOT BEEN CHANGED |
| ON SHT P1-1.0U |
| |
| 4B. OK |
| |
| 5B. SHT P1-1.2U CLEANOUT REQUIRED AT THE BASE OF P/1 & |
| P/10 RISERS, NEAR THE JUNCTION OF THE BUILDING DRAIN |
| AND THE BUILDING SEWER, AND AT ALL CHANGES OF DIRECTION |
| OVER 45 DEGREES. PLEASE INDICATE ON PLANS. SECTIONS. |
| 708.3.3, 708.3.4, 708.3.5. |
| ****RESPONSE NOTED, BUT C/O'S ARE NOT SHOWN ON SHTS |
| P3-1.0 & P3-2.0. |
| |
| 6B. SHTS P1-1.2U, ASSOCIATED RISER DIAGRAMS, AND |
| ENLARGED FLOOR PLANS. INDICATE HOW THE STACKS P/1 & |
| P/10 CAN DRAIN INTO THE TOILET GROUP FIXTURE BRANCH. |
| SUBMIT A DETAIL SHOWING THE 4" CLEANOUT TEE, THE 4" |
| CROSS FOR THE FIXTURE BRANCH, AND THE 4" DOUBLE |
| Y/EIGHTH BEND FITTINGS STACKED ON TOP OF EACH OTHER. |
| WILL THEY BE AT THE RIGHT HEIGHT FOR THE W/C'S?SEE |
| SECTION 908.3 ALSO. SECTION 106.1.1. (STACKS SHOULD |
| CONNECT TO THE BUILDING DRAIN AND FIXTURE GROUPS SHOULD |
| CONNECT TO THE STACK SO THAT THE STACK DOES NOT RUN |
| THRU THE MIDDLE OF THE FIXTURE GROUP). ****RESPONSE |
| NOTED, BUT C/O'S ARE REQUIRED AT THE BASE OF EACH |
| STACK. COMMENT HAS NOT BEEN ADDRESSED. |
| |
| 7B. SHTS P1-1.3U, P1-2.0, P1-2.3, P1-3.3, & P1-4.3 |
| RWL-6 DOES NOT REFLECT THE SQUARE FOOTAGE SHOWN ON THE |
| RISER DIAGRAM, NOR ON THE ROOF PLAN. PLEASE CORRELATE |
| INFORMATION. SECTION 106.1.1 & TABLE 1106.3. |
| ****RESPONSE NOTED, BUT THE COMMENT WAS NOT ADDRESSED |
| ON SHTS P1-3.3, & P1-4.3. |
| |
| 8B. OK |
| 9B. OK |
| 10B. OK |
| 11B. OK |
| |
| 12B. SHT P1-4.1 SHOW RISER P/3 VTR. - NOTE STATES "SEE |
| 01 ON DRAWING P2-3.0". INFORMATION NOT SHOWN ON DETAIL |
| 01. PLEASE CLARIFY. - SHOW THE VENTING TO REFLECT THE |
| FLOOR PLAN FOR KINK S-1 CONNECTED TO RISER P/8. - 4" |
| SANITARY - 4" VTR AT COL. LINE E/8 IS SHOWN AS AN |
| OFFSET ON THE RISER DIAGRAM. PLEASE CORRELATE FLOOR |
| PLAN AND SANT. RISER DIAGRAM. SECTION 106.1.1. |
| ****RESPONSE NOTED. NOTE DELETED, BUT COMMENT NOT |
| ADDRESSED FOR OFFSETS AND VENTING. -VENTING ON ALL |
| RISERS SHALL REFLECT THE VENTING ON THE FLOOR PLAN. |
| (ALL VENTING NOT SHOWN ON THE FLOOR PLAN), AND ON THE |
| ENLARGED PLUMBING PLANS FLOOR PLAN. |
| |
| 13B. OK |
| 14B. OK |
| |
| 15B. SHT P1-6.0 SHOW THE LOCATIONS FOR ALL VTR'S. - |
| INDICATE THE RWL EACH ROOF DRAIN IS CONNECTED TO. |
| SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT VTR'S 1, 3, 9 & 10 ARE NOT |
| SHOWN. |
| |
| 16B. SHT P2-1.0U DETAIL 1, FLOOR DRAINS IN C1.104 ARE |
| NOT VENTED. SECTION 901.2.1. - THE PIPING AT THE LAVS |
| IN ROOM C1.103 DOES NOT REFLECT THE RISER DIAGRAM. |
| PLEASE CORRELATE. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT THE FLOOR DRAIN IN THE |
| ACCESSIBLE STALL HAS NOT CHANGED TO REFLECT THE CHANGE |
| IN THE RISER DIAGRAM. |
| |
| 17B. SHT P2-1.0U DETAIL 2 DOES NOT REFLECT THE PIPING |
| LAYOUT SHOWN ON P1-1.2U. - SUBMIT A DETAIL FOR THE |
| SANT. PIPING ARRANGEMENT FOR THE DRINKING FOUNTAINS, |
| SHOW HOW THE PIPING CONNECTS THROUGH THE SIDE OF THE |
| D.F. UNITS. - SUBMIT A DETAIL FOR THE FITTING |
| ARRANGEMENT WHERE THE TOILET ROOM FIXTURES CONNECT TO |
| THE BLDG. DRAIN. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT A DETAIL HAS NOT BEEN |
| SUBMITTED. ALSO EXPLAIN THE 3" SANT. LINE FROM THE |
| DRINKING FOUNTAINS TO THE MEN'S ROOM D1/101.-THE |
| FLOOR DRAIN PIPING APPEARS TO BE ABOVE THE SLAB. PLEASE |
| CLARIFY. |
| |
| 18B. OK |
| |
| 19B. SHT P2-1.0U DETAIL 6, SINK SHALL CONNECT |
| DOWNSTREAM OF THE WET VENTED FIXTURES IN THE TOILET |
| ROOM. SECTION 909.1. |
| ****RESPONSE NOTED. CORRECTED, BUT NOT CORRECTED ON SHT |
| P1-1.1U. PLEASE CORRECT TO REFLECT RISER AND DETAIL. |
| |
| 20B. OK |
| 21B. OK |
| |
| 22B. SHT P2-1.0 DETAIL 4 DOES NOT REFLECT THE FLOOR |
| PLAN. NO WATER TO WH'S & SHOWS 2" WATER SUPPLY. SECTION |
| 106.1.1. |
| ****RESPONSE NOTED, BUT STILL NO WATER SUPPLY TO WATER |
| HEATERS. |
| |
| 23B. OK |
| 24B. OK |
| 25B. OK. |
| |
| 26B. SHT P2-2.0 DETAIL 3, SUBMIT A DETAIL FOR SANT. |
| PIPING TO D.F.'S - INDICATE RISERS FOR COLD WATER |
| DOWNSTREAM OF LAST W/C'S. HOT WATER LINE NOT SHOWN THRU |
| BATHROOM FIXTURES. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT STILL SHOWS PIPING OUT THE SIDE |
| OF 1ST DF. |
| |
| 27B. OK |
| 28B. OK |
| 29B. OK |
| |
| 30B. SHT P2-3.0 DETAIL 1, INDICATE WHERE SANT. BRANCH |
| LINE CONNECTS TO THE SANT. RISER. - FLOOR DRAIN SHOWS |
| NO PIPING. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT RISER SHOWS P1 RISER BETWEEN |
| W/C'S & LAVS, WHEREAS THE FLOOR PLAN SHOW THE RISER |
| BETWEEN W/C'S. CORRELATE RISER AND FLOOR PLAN. |
| |
| 31B. OK |
| 32B. OK |
| 33B. OK |
| |
| 34B. SHT P3.1.0 SANT RISER DIAGRAM, TRAPS ARE REQUIRED |
| ON ALL DRINKING FOUNTAINS. SECTION 1002.1. - 1ST FLOOR |
| LAVS PIPING DOES NOT REFLECT THE FLOOR PLAN. - FLOOR |
| DRAINS DOWNSTREAM OF RISER P/1 ARE NOT VENTED. SECTION |
| 901.2.1. - A C/O IS REQUIRED AT THE BASE OF STACK P/1 |
| SECTION 708.3.4 - SHOW THE CONNECTION DETAIL AT THE |
| BASE OF STACK P/1 WITH A 4" CLEANOUT, A 4" CROSS, AND |
| 4" WYE FITTINGS INDICATING THE HEIGHT OF THE W/C |
| STUBOUT. - W/C-1 AT THE BASE OF STACK IS NOT VENTED. |
| SECTION 901.2.1. -W/C ON 2ND FLOOR IS NOT VENTED. |
| SECTION 901.2.1. - LAV ON 3RD FLOOR NOT VENTED. SECTION |
| 901.2.1. - INDICATE HOW/WHERE PIPING FOR LAVS & FLOOR |
| DRAINS CONNECT TO THE RISER/BRANCH ON THE 2ND, 3RD, & |
| 4TH FLOORS. THE FITTINGS INDICATE THAT THE PIPING IS |
| SLOPED TO THE LAVS. PLEASE CLARIFY. - MEN C4.104 DOES |
| NOT REFLECT ROOM NUMBER ON THE FLOOR PLAN. - PIPING FOR |
| FLOOR DRAINS & LAVS 4TH FLOOR DOES NOT REFLECT THE |
| FLOOR PLAN. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT 1ST FLOOR LAVS PIPING DOES NOT |
| REFLECT THE FLOOR PLAN. -A C/O IS REQUIRED AT THE |
| BASE OF STACK P/1 SECTION 708.3.4 - SHOW THE CONNECTION |
| DETAIL AT THE BASE OF STACK P/1 WITH A 4" CLEANOUT, A |
| 4" CROSS, AND 4" WYE FITTINGS INDICATING THE HEIGHT OF |
| THE W/C HOW THE CONNECTION DETAIL AT THE BASE OF STACK |
| P/1 WITH A 4" CLEANOUT, A 4" CROSS, AND 4" WYE FITTINGS |
| INDICATING THE HEIGHT OF THE W/C STUBOUT. - MEN C4.104 |
| DOES NOT REFLECT ROOM NUMBER ON THE FLOOR PLAN. - |
| PIPING FOR FLOOR DRAINS & LAVS 4TH FLOOR DOES NOT |
| REFLECT THE FLOOR PLAN. SECTION 106.1.1. THESE ITEMS |
| HAVE NOT BEEN ADDRESSED. |
| |
| 35B. ALL RISER DIAGRAMS, ALL FLOOR PLANS FOR ALL |
| SYSTEMS. INDICATE THE PIPE SIZE. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT MANY PIPE SIZES ARE NOT SHOWN |
| ON THE RISER DIAGRAMS. |
| |
| 36B. SHT P3-2.0 JANITOR ROOM PIPING DOES NOT REFLECT |
| THE FLOOR PLAN. - TRAPS REQUIRED ON ALL DRINKING |
| FOUNTAINS. SECTION 1002.1. - CLEANOUTS REQUIRED AT THE |
| BASE OF ALL STACKS. 708.3.4. - PIPING TO FLOOR DRAIN |
| SHOWN ABOVE THE FLOOR IN ROOM D1.101. PLEASE CLARIFY. - |
| PIPING AT THE BASE OF RISER P/2 DOES NOT REFLECT THE |
| FLOOR PLAN. - PIPING TO FD-2 AT THE LOADING D1.106 DOES |
| NOT REFLECT THE FLOOR PLAN. - PIPING FOR A1.108/A1.109 |
| DOES NOT REFLECT THE FLOOR PLAN. - ROOM D2.103 IS |
| INDICATED AS D2.104 ON THE FLOOR PLAN. CORRELATE |
| INFORMATION. - ALL VENTING AT RISER P/10 STOPS AT LEVEL |
| 2. SECTION 903.3 VTR REQUIRED. - TOILET ROOM A2.708 IS |
| INDICATED AS A2.706 ON THE FLOOR PLAN. CORRELATE |
| INFORMATION. - BATHROOM RISER DOES NOT REFLECT THE |
| FLOOR PLAN. (NO FD). - PIPING TO ROOM A4.414 DOES NOT |
| REFLECT THE FLOOR PLAN. - CLEANOUT PIPING DOWNSTREAM OF |
| C4.101 IS NOT APPROVED AS PIPED. SECTION 706.3. - |
| PIPING ON RISER DOES NOT REFLECT THE FLOOR PLAN |
| UPSTREAM OF C3.105. - JANITOR SINK C3.105 IS NOT |
| VENTED. SECTION 901.2.1. - FLOOR DRAIN CONNECTION AT |
| BRANCH LINE 4TH FLOOR DOES NOT REFLECT THE FLOOR PLAN. |
| - PIPING AT A2.107 DOES NOT REFLECT THE FLOOR PLAN. (NO |
| F.D. PIPING). - PIPING AT ROOM A3.111 DOES NOT REFLECT |
| THE FLOOR PLAN AT THE LAVS. - ROOM A3.111 SUBMIT A |
| DETAIL FOR FITTING TO W/C & LAVS. - ROOM D2.105 SHOWN |
| AS D2.106/D2.107 ON FLOOR PLANS. CORRELATE INFORMATION. |
| - ROOM C3.410/C3.412 FLOOR DRAIN FITTING ARE SHOWN TO |
| BE INSTALLED AGAINST THE FLOW. SECTION 706.3. - SECTION |
| 106.1.1. |
| ****RESPONSE NOTED, BUT SOME COMMENTS WERE NOT |
| ADDRESSED. SEE THE FOLLOWING: JANITOR ROOM PIPING DOES |
| NOT REFLECT THE FLOOR PLAN. - TRAPS REQUIRED ON ALL |
| DRINKING FOUNTAINS. SECTION 1002.1. - CLEANOUTS |
| REQUIRED AT THE BASE OF ALL STACKS. 708.3.4. - PIPING |
| TO FLOOR DRAIN SHOWN ABOVE THE FLOOR IN ROOM D1.101. |
| PLEASE CLARIFY.- PIPING AT THE BASE OF RISER P/2 DOES |
| NOT REFLECT THE FLOOR PLAN. - PIPING FOR A1.108/A1.109 |
| DOES NOT REFLECT THE FLOOR PLAN. - ROOM D2.103 IS |
| INDICATED AS D2.104 ON THE FLOOR PLAN. CORRELATE |
| INFORMATION.- TOILET ROOM A2.708 IS INDICATED AS |
| A2.706 ON THE FLOOR PLAN. CORRELATE INFORMATION. - |
| PIPING TO ROOM A4.414 DOES NOT REFLECT THE FLOOR PLAN. |
| - CLEANOUT PIPING DOWNSTREAM OF C4.101 IS NOT APPROVED |
| AS PIPED. SECTION 706.3. - PIPING AT ROOM A3.111 DOES |
| NOT REFLECT THE FLOOR PLAN AT THE LAVS. - ROOM A3.111 |
| SUBMIT A DETAIL FOR FITTING TO W/C & LAVS. - ROOM |
| D2.105 SHOWN AS D2.106/D2.107 ON FLOOR PLANS. CORRELATE |
| INFORMATION. |
| |
| 37B. SHT P3-3.0 PIPING TO A3.304 & DOWNSTREAM DOES NOT |
| REFLECT THE FLOOR PLAN. - VENT PIPING FROM S-1 SINK |
| DOES NOT REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN. - |
| TRAPS REQUIRED ON ALL DRINKING FOUNTAINS. SECTION |
| 1002.1. - S-1 SINK SHALL NOT DRAIN THRU THE WET VENT OF |
| THE TOILET ROOM A1.303. SINK SHALL DISCHARGE DOWNSTREAM |
| OF THE W/C & LAV. SECTION 909.1. - INDICATE P/8 WITH |
| P/6 AT THE BASE OF THE STACK WHERE IT BEGINS. - PIPING |
| TO ROOMS A1.105/A1.106 DOES NOT REFLECT THE FLOOR PLAN. |
| FLOOR DRAIN PIPING IS SHOWN AS ABOVE THE FLOOR. - P/5 & |
| P/9 BEGIN AT THE BASE OF THE STACK. PLEASE INDICATE ON |
| RISER DIAGRAM. - PIPING FOR A3.102/A3.103 DOES NOT |
| REFLECT THE FLOOR PLAN. - CLEANOUT REQUIRED AT THE BASE |
| OF P/9 STACK. - PIPING TO FLOOR DRAINS IN ROOMS |
| A3.102/A3.103 ARE ABOVE THE FLOOR. -W/C AT THE BASE |
| OF STACK NOT VENTED. SECTION 901.2.1. - INDICATE WHERE |
| LINES TO FLOOR DRAINS IN ROOMS A4.103/A4.104 & |
| A5.103/A5.104 ARE CONNECTING TO THE BRANCH/STACK. - |
| PIPING FOR A4.103/A4.104 DOES NOT REFLECT THE FLOOR |
| PLAN. - W/C AT RISER STACK A4.103 IS NOT VENTED. |
| SECTION 901.2.1. - PIPING FOR A4.105 DOES NOT REFLECT |
| THE FLOOR PLAN. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT |
| ADDRESSED:-PIPING TO A3.304 & DOWNSTREAM DOES NOT |
| REFLECT THE FLOOR PLAN. - VENT PIPING FROM S-1 SINK |
| DOES NOT REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN. - |
| PIPING TO ROOMS A1.105/A1.106 DOES NOT REFLECT THE |
| FLOOR PLAN. FLOOR DRAIN PIPING IS SHOWN AS ABOVE THE |
| FLOOR. -PIPING FOR A4.103/A4.104 DOES NOT REFLECT THE |
| FLOOR PLAN. - W/C AT RISER STACK A4.103 IS NOT VENTED. |
| SECTION 901.2.1. - PIPING FOR A4.105 DOES NOT REFLECT |
| THE FLOOR PLAN. SECTION 106.1.1. |
| |
| 38B. OK |
| |
| 39B. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING |
| INFORMATION IS REQUIRED FOR THE GAS PERMIT: |
| |
| A. OK - "NEW"SHOW THE LOCATION OF THE 2PSI TO 1/2PSI |
| REGULATOR. SHUT OFF VALVE REQUIRED UPSTREAM OF |
| REGULATOR. |
| B. OK |
| C. OK |
| D. OK |
| |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| ****RESPONSE NOTED, BUT NOT ADDRESSED |
| |
| F. OK - INFORMATIONAL - 2PSI AT MAXIMUM 200 FT |
| DEVELOPED LENGTH ALLOWS 39,656,000 BTU'S. ONLY 10,000 |
| BTU'S ARE INDICATED ON PLANS. THE 10,000 BTU'S IS |
| QUESTIONABLE AS MOST RESIDENTIAL DRYERS ARE RATED AT |
| 22,000 BTU'S. FOR COMPARISON, A .5 PSI SYSTEM WITH 2" |
| PIPE WILL DELIVER 800,000 BTU'S. WITH THE EXTRA |
| DEVELOPED LENGTH TO THE FARTHEST FUTURE GENERATOR,ITS |
| APPROXAMATLY 180'. |
| |
| G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| ****RESPONSE NOTED, BUT NO MANUF. SHEETS FOR THE |
| GENERATOR HAS BEEN SUBMITTED. - ALSO SUBMIT THE MANUF. |
| SPECIFICATION SHEETS FOR THE GAS REGULATORS. INDICATE |
| MODEL NUMBER. LISTING INFORMATION REQUIRED. |
| |
| H. NA |
| I. NA |
| |
| 40B. SHT P3-5.0 NO HOT WATER LINE SHOWN IN 1ST THRU 4TH |
| FLOOR TOILET ROOMS OFF WATER RISER W/1. - WATER RISER |
| DOES NOT REFLECT THE FLOOR PLAN AT THE LAVS. - FULL |
| OPEN VALVES ARE REQUIRED ON ALL WATER DOWN-FEED LINES. |
| SECTION 606.1(4). - RISER DOES NOT REFLECT THE FLOOR |
| PLAN AT ROOMS C2.102/C2.103. (2 LAVS SHOWN EACH TOILET |
| ROOM). - PIPE SIZE SUPPLYING ROOMS D1.101/D1.102, |
| JANITOR ROOM D1.110, TOILET ROOMS A1.108/A1.109. - |
| INDICATE THAT RISERS W/4, W/5, & W/8 RISERS START WITH |
| RISER W/2 ON THE 1ST FLOOR. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT |
| ADDRESSED: - WATER RISER DOES NOT REFLECT THE FLOOR |
| PLAN AT THE LAVS. - FULL OPEN VALVES ARE REQUIRED ON |
| ALL WATER DOWN-FEED LINES. SECTION 606.1(4). (MANY |
| LAVS, TOILET ROOMS, SINKS ETC MISSING VALVES).- RISER |
| DOES NOT REFLECT THE FLOOR PLAN AT ROOMS C2.102/C2.103. |
| (2 LAVS SHOWN EACH TOILET ROOM). - PIPE SIZE SUPPLYING |
| ROOMS D1.101/D1.102, JANITOR ROOM D1.110, TOILET ROOMS |
| A1.108/A1.109. (2" SHOWN ON FLOOR PLAN, 1-1/2" ON |
| RISER. 3/4" ON FLOOR PLAN, 1/2" ON RISER.SOME LAVS |
| SHOW SEPARATE DROPS TO EACH LAV ON THE FLOOR PLAN, BUT |
| SINGLE DROPS ON THE RISER). - INDICATE THAT RISERW/8 |
| STARTS WITH RISER W/2 ON THE 1ST FLOOR. SECTION |
| 106.1.1. |
| |
| 41B. SHT P3-6.0 RISERS 4, 5 & 8 ARE NOT INDICATED ON |
| THE 1ST FLOOR. - RISER DOES NOT REFLECT THE FLOOR PLAN |
| ROOMS C3.107/C3.108 AT JAN. SINK, ROOMS C3.410/C3.412, |
| AE.111, A4.103/A4.104, A4.105 AND THE TOP OF RISER W/4 |
| TO ROOM A5.105, PIPE SIZE AT ROOM A2.209 & SUPPLY TO |
| TOILET ROOM ADJACENT, PIPE SIZE SUPPLYING RISER W/8 & |
| RISER, SUPPLY LINE TO ROOMS D2.102/D2.103. - W/2 NOT |
| FOUND ON 4TH FLOOR AS INDICATED ON RISER. SECTION |
| 106.1.1. |
| ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT |
| ADDRESSSED: RISER 8 STILL NOT INDICATED ON THE 1ST |
| FLOOR. - RISER DOES NOT REFLECT THE FLOOR PLAN ROOMS |
| C3.410/C3.412,A4.103/A4.104, (FLOOR PLAN INDICATES |
| OVER-HEAD SUPPLY WITH DROPS, BUT RISER INDICATES SUPPLY |
| RUN IN THE WALL OFF WATER RISER. TWO W/C'S MISSING ON |
| RISER).-PIPE SIZE AT ROOM A2.209, (SHOWS 1" ON THE |
| FLOOR PLAN), - PIPE SIZE SUPPLYING RISER W/8 & RISER, ( |
| 1" ON FLOOR PLAN, 2" ON RISER - 1-1/2" ON THE FLOOR |
| PLAN, BUT 2" ON THE RISER). -W/2 NOT FOUND ON 4TH OR |
| 5TH FLOORS AS INDICATED ON RISER. SECTION 106.1.1. |
| PLEASE CORRELATE RISER AND FLOOR PLANS. |
| |
| 42B. SHT P3-7.0 SIZE ALL PIPE PER SECTION 1106.3, AND |
| SHOW ALL PIPE SIZES ON THE RISER. - RISER DOES NOT |
| REFLECT THE FLOOR PLAN TOP FLOORS RWL/6 & RWL/7. - |
| RISERS INDICATE A 5TH FLOOR, BUT FLOOR PLAN DOES NOT |
| SHOW A 5TH FLOOR. - RISER SHOWS TRENCH DRAINS ON TWO |
| FLOORS, BUT ONLY SHOW TRENCH DRAINS ON 1 FLOOR, (ROOF |
| LEVEL), ON THE FLOOR PLAN. -RWL'S 9 THRU 14 SHOW OFFSET |
| PIPING FOR ROOF DRAINS IN THE 4TH FLOOR CEILING, BUT |
| INDICATE THE ROOF DRAINS TO BE ON THE 4TH LEVEL. PLEASE |
| CLARIFY. - PIPE SIZING IS INCORRECT AT 8"/11,715SF, |
| 6"/5077SF, 6"/6657SF. TABLE 1106.3. - RWL/9 INDICATES |
| PIPING IN 3RD FLOOR CEILING, BUT ROOF DRAINS ARE TO BE |
| ON THE 3RD LEVEL. PLEASE CLARIFY. - RWL/15 DOES NOT |
| REFLECT THE FLOOR PLAN TO 4" ROOF DRAINS. - PIPING AT |
| THE 1ST FLOOR CEILING CONNECTING TO ROOF DRAINS ON THE |
| 1ST LEVEL. PLEASE CLARIFY. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT SOME COMMENTS THE FOLLOWING |
| COMMENTS WERE NOT ADDRESSED:- RISER DOES NOT REFLECT |
| THE FLOOR PLAN TOP FLOORS RWL/6 & RWL/7. - RISERS |
| INDICATE A 5TH FLOOR, BUT FLOOR PLAN DOES NOT SHOW A |
| 5TH FLOOR. - RISER SHOWS TRENCH DRAINS ON TWO FLOORS, |
| BUT ONLY SHOW TRENCH DRAINS ON 1 FLOOR, (ROOF LEVEL), |
| ON THE FLOOR PLAN. - PIPE SIZING IS INCORRECT AT |
| 8"/11,715SF, 6"/5077SF, 6"/6657SF. TABLE 1106.3. |
| |
| 43B. SHTS 1,2,3 OF 3 ARE NOT SIGNED, SEALED, & DATED AS |
| REQUIRED PER FS 472.025(1). ALSO SEE SHT 1 WHICH STATES |
| "NOT VALID UNLESS SEALED WITH SURVEYOR'S EMBOSSED SEAL |
| AND SIGNATURE" |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 44B. SHTS C1, C5 THRU C22 ENGINEERING CERTIFICATE OF |
| AUTHORIZTION IS REQUIRED IN THE TITLE BLOCK. |
| 61G15-23.002(2) & FS 471.025. - AN EMBOSSED SEAL IS |
| REQUIRED TO IMPRESS REQUIRED INFORMATION ON EACH SHEET. |
| UNABLE TO GLEAN ALL INFORMATION REQUIRED FROM SEAL. |
| PLEASE RESEAL PLANS. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 45B. SHTS LP-0 THRU LP-3 & IR-1 THE CERTIFICATE OF |
| AUTHORIZATION IS REQUIRED IN THE TITLE BLOCK. |
| 61G1-16.004(1) & FS 481.319. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 46B. SHT LL-1 IS MISSING THE TITLE BLOCK INFORMATION |
| REQUIRED IN 61G1-16.004. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 47B. SHT IR-1 THE CONTROLER & RAIN SENSOR LOCATIONS ARE |
| REQUIRED ON PLANS. SECTION 106.1.1. |
| ****NO RESPONSE. THIS INFORMATION SHALL BE SUBMITTED AS |
| A REVISION PRIOR TO APPLICATION, OR WITH THE |
| APPLICATION FOR IRRIGATION PERMIT - NEW COMMENT, NO |
| CERTIFICATE OF AUTHORIZATION IN THE TITLE BLOCK AS |
| REQUIRED BY 61G1-16.004(2) & FS 481.319. |
| |
| 48B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 2ND |
| FLOOR DRINKING FOUNTAINS SHOWS 4 REQUIRED, BUT ONLY 3 |
| ARE REQUIRED PER TABLE 403.1. FIXTURE COUNT INDICATES |
| ONLY 2 ARE PROVIDED. PLEASE PROVIDE REQUIRED AMOUNT OF |
| DRINKING FOUNTAINS. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 49B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 3RD |
| FLOOR DRINKING FOUNTAINS SHOW ONLY 3 ARE REQUIRED. PER |
| TABLE 403.1, 4 DRINKING FOUNTAINS ARE REQUIRED. PLEASE |
| UPDATE FIXTURE COUNT. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 50B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 4TH |
| FLOOR DRINKING FOUNTAINS INDICATE 4 REQUIRED, BUT ONLY |
| 3 ARE PROVIDED. PLEASE PROVIDE 4 DRINKING FOUNTAINS. |
| TABLE 403.1. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 51B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 1ST |
| FLOOR DRINKING FOUNTAINS 2 REQUIRED PER TABLE 403.1, |
| BUT READS 1 REQUIRED. PLEASE CORRECT FIXTURE COUNT |
| REQUIRED. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 52B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 3RD |
| FLOOR DRINKING FOUNTAINS 4 REQUIRED PER TABLE 403.1, |
| BUT READS 2 REQUIRED. PLEASE CORRECT FIXTURE COUNT |
| REQUIRED. - SHOWS 2 PROVIDED, BUT 4 ARE REQUIRED. |
| PLEASE CORRECT INFORMATION. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 53B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 4TH |
| FLOOR LAVS REQUIRED 2, INDICATED AS 1. PLEASE CORRECT |
| THE FIXTURE COUNT. TABLE 403.1. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 54B. SHT LSO.0 LIBRARY/MUSEUM INDICATES A RESTURANT IN |
| OCCUPANT LOAD 1ST FLOOR.PLEASE CONTACT LYNN MASSON, |
| ENVIRONMENTAL COMPLIANCE MANAGER CONCERNING THE |
| POSSIBLE REQUIREMENT FOR A GREASE INTERCEPTOR. CONTACT |
| LYNN BY PHONE (561) 822-2271, OR FAX (561) 822-2279, OR |
| E-MAIL [email protected]. |
| ****PER ARCHITECT, NO RESTURANT WILL BE IN THE LIBRARY. |
| THIS WAS INDICATED AS A RESTURANT FOR OCCUPANCY |
| CALCULATIONS ONLY. THERE WILL BE A CAFE IN THE LIBRARY |
| WITH NO FOOD PREPARATION. |
| |
| 55B. SHT LSO.0 INDICATES ASSEMBLY OCCUPANCY FOR THE |
| CITY HALL AND LIBRARY/MUSEUM. POTTY PARITY IS REQUIRED |
| PER SECTION 403.1.1 AND HAS BEEN INDICATED IN THE 50% |
| REVIEW BY PAUL SCHMITZ. THIS HAS NOT BEEN ADDRESSED. |
| PLEASE SHOW COMPLIANCE WITH THIS REQUIREMENT. ****NO |
| RESPONSE, NOT ADDRESSED. |
| |
| 56B. SHT A2-0 3 AREAS SHOW STORM WATER FROM ROOF AREAS |
| ABOVE THAT CONTRIBUTE TO THE MAIN ROOF AREAS BELOW. THE |
| SLOPE OF THE MAIN ROOF AND THE LOCTION OF THE DOWNSPOUT |
| IS SHOWING THE TOTAL AREA DRAINING TO ONE ROOF DRAIN, |
| BUT THE AREA IS DIVIDED EQUALLY BETWEEN TWO ROOF |
| DRAINS. THE SIZING FOR THE ROOF DRAINS WILL HAVE TO BE |
| RECHECKED TO ACCOUNT FOR THE AMOUNT OF AREA DRAINING TO |
| ONE DRAIN, NOT TWO. TABLE 1106.3. (SEE ROOF AREAS AT |
| COL. LINES 1THRU 4/A THRU D, 7 THRU 9.1/A THRU D, AND 4 |
| - 5/E THRU H). |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 57D. SHTS A2-0, A2-1, A2-2, A2-3 SUBMIT CALCULATIONS |
| FOR PRIMARY AND SECONDARY ROOF DRAINS. INDICATE THE |
| CONTRUBUTION ADD FROM 1/2 AREA OF ALL VERTICAL WALLS, |
| INCLUDING PARAPETS, AND ROOF AREAS FROM ABOVE ADDED TO |
| THE ROOF SECTIONS. THIS IS REQUIRED FOR ALL ROOF |
| LEVELS. SQUARE FOOTAGE IS SHOWN, BUT NO CALCULATIONS |
| WERE SUBMITTED. CONTRIBUTING VERTICAL AREAS FOR WALLS |
| IS UNCLEAR. IS THE AREA SHOWN INDICATED PER WALL, OR |
| TOTAL FOR ALL WALLS SHOWN. PLEASE CLARIFY. SECTIONS |
| 1106.1, 1106.2, 1106.3, 1106.4. |
| ****NO RESPONSE NOTED. PRIMARY AND SECONDARY ROOF DRAIN |
| CALCULATIONS WERE NOT FOUND. |
| |
| 58B. SHT A2-0 UPPER ROOF BY DOME SHOWS A DETAIL |
| INDICATOR 20/A2-D.1. DETAIL 20 NOT FOUND ON SHT A2-D.1. |
| PLEASE CLARIFY. SECTION 106.1.1. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 59B. SHT A2-D.1 DETAIL 04 SHOW HEIGHT AND WIDTH AND |
| INDICATE THE MEASUREMENT FROM THE ROOF TO THE FLOW LINE |
| OF THE SCUPPER. SECTIONS 106.1.1 AND 1503.4.3. ****NO |
| RESPONSE, NOT ADDRESSED. |
| |
| 60B. SHT A6-1.1 DETAILS 1 THRU 6. SHOW THE TURNING AREA |
| IN THE TOILET ROOMS. NOT IN THE ACCESSIBLE STALLS. |
| SECTION 11-4.22.3. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 61B. SHT A6-1.1 DETAIL 2, SHOW THE CLEAR FLOOR SPACE |
| FOR THE URINAL. SECTION 11-4.18.3. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 62B. SHT A6-1.1 DETAIL 4, ACCESSIBLE W/C SHALL BE 1'6" |
| OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG. |
| 11-28. LAV TO BE MIN. 15" (C/L OF CLEAR FLOOR SPACE). |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 63B. SHT A6-1.1 DETAIL 7, ACCESSIBLE W/C SHALL BE 1'6" |
| OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG. |
| 11-28. (SHOWS 2'2"). |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 64B. SHT A6-2.1 DETAILS 2, 6 & 7 SHOWTHE TURNING AREA |
| IN THE TOILET ROOMS. NOT IN THE ACCESSIBLE STALLS. |
| SECTION 11-4.22.3. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 65B. SHT A6-2.1 DETAIL 4, ACCESSIBLE W/C SHALL BE 1'6" |
| OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG. |
| 11-28. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 66B. SHT A6-3.1 DETAIL 2, SHOW A TURNING AREA IN THE |
| LOCKER ROOM AREA. SECTION 11-4.2.3. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 67B. SHT A6-3.1 DETAILS 1, 3, 4 & 5, SHOW THE TURNING |
| AREA IN THE TOILET ROOMS, NOT IN THE ACCESSIBLE STALLS. |
| SECTION 11-4.22.3. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 68B. SHT A6-4.1 DETAILS 1 & 2, SHOW THE TURINING AREA |
| IN THE TOILET ROOMS, NOT IN THE ACCESSIBLE STALLS. |
| SECTION 11-4.22.3. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 69B. SHT A6-5.1 DETAIL 1, SHOW THE TURNING AREA IN THE |
| TOILET ROOM, AND SHOW THE CLEAR FLOOR SPACE FOR THE |
| URINAL. SECTIONS 11-4.22.3 AND 11-4.18.3. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 70B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS |
| C1.105, C1.106, A2.705, A2.706, A2.210, A2.211, A3.111, |
| A3.114, C3.410, AND C3.412 ALL INDICATE THE WALLS TO BE |
| PAINTED. PLEASE INDICATE HOW THIS COMPLIES WITH THE |
| REQUIREMENT FOR "SMOOTH, HARD, NONABSORBENT WALLS AS |
| REQUIRED IN SECTION 1210.2. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 71B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS D2.10 |
| & D2.104 SHOW NO WALL FINISH AND THE FLOORING/BASE |
| INDICATE RUBBERIZED FLOORING. INDICATE HOW THIS |
| COMPLIES WITH "SMOOTH, HARD, NONABSORBENT FLOORS AS |
| REQUIRED IN SECTION 1210.1. |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 72B. SHT A9-4.1 INDICATE THE ROOM NUMBERS THAT THE |
| DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE |
| FOLLOWING: |
| A. 11-4.18.4 FLUSH CONTROLS |
| B. 11-4.19.2 CLEARANCES |
| C. 11-4.19.4 EXPOSED PIPES & CLEARANCES |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 73B. SHT A9-4.2 INDICATE THE ROOM NUMBERS THAT THE |
| DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE |
| FOLLOWING: |
| DETAIL #1 |
| A. 11-4.18.4 FLUSH CONTROLS |
| B. 11-4.19.2 CLEARANCES |
| C. 11-4.19.4 EXPOSED PIPES & CLEARANCES |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| DETAIL #2 |
| A. 11-4.18.4 FLUSH CONTROLS |
| B. 11-4.19.2 CLEARANCES |
| C. 11-4.19.4 EXPOSED PIPES & CLEARANCES |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 74B. SHT A9-4.4 INDICATE THE ROOM NUMBERS THAT THE |
| DETAILS ARE REFERENCING.SHOW COMPLIANCE WITH THE |
| FOLLOWING: |
| DETAILS #1 - #2 - #3 |
| A. 11-4.19.2 CLEARANCES |
| B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 75B. SHT A9-4.5 DETAILS (1) & (2), SHOW THE FOLLOWING |
| FOR COMPLIANCE:A. 11-4.19.2 CLEARANCES |
| B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| C. 11-4.19.5 FAUCETS |
| D. 11-4.21.5 CONTROLS |
| E. 11-4.21.7 CURBS |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| 76B. SHTS A1.307, A1.709, A2.209, A2.315, A2.407, |
| A3.109, C3.409, C3.310, A5.504 - SHOW COMPLIANCE WITH |
| THE FOLLOWING |
| A. 11-4.24.4 SINK DEPTH |
| B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH |
| REQUIRED) |
| C. 11-4.24.6 EXPOSED PIPES & SURFACES |
| D. 11-4.24.7 FAUCETS |
| ****NO RESPONSE, NOT ADDRESSED. |
| |
| *************NEW COMMENTS************* |
| |
| 1C. SHT P9-4.6 DETAILS 1 & 2 SHOW COMPLIANCE WITH THE |
| FOLLOWING: |
| A. 11-4.18.4 FLUSH CONTROLS |
| B. 11-4.19.2 CLEARANCES |
| C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| |
| 2C. SHT P9-4.7 DETAILS 1, 2, & 3 SHOW COMPLIANCE WITH |
| THE FOLLOWING: |
| A. 11-4.18.4 FLUSH CONTROLS |
| B. 11-4.19.2 CLEARANCES |
| C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| |
| 3C. SHT P1-6.0 THE FOLLOWING VENTS ARE NOT SHOWN ON THE |
| ROOF. P1, P2, P3, & P10. PLEASE SHOW ON THIS SHEET OR |
| INDICATE WHERE THEY ARE SHOWN. SECTION 106.1.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. SUBMITTING THE RED |
| LINED SET OF PLUMBING SHEETS WHEN RESUBMITTING FOR |
| REVIEW WILL HELP EXPEDITE THE PERMIT ALSO. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6721 |
| E-MAIL [email protected] |
| |
| |
| |
| |