Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop P
Sequence Number 2
Notes
Date Text
2006-12-23 17:38:49DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
  
 3. SHT P1-1.1 PUMP ROOM A1-112. RPZV BACKFLOW SHALL BE
 INSTALLED A MAXIMUM OF 4' ABOVE THE FLOOR FOR
 CERTIFICATION AND SERVICE.
 ****RESPONSE NOTED, HEIGHT TO BE INDICATED FOR THE
 BACKFLOWS TO BE A MAXIMUM OF 4' ABOVE THE FLOOR.
 ****RESPONSE NOTED, BUT PLANS INDICATE MINIMUM 4' ABOVE
 THE FLOOR. THE REQUIREMENT IS FOR MAXIMUM 4' ABOVE THE
 FLOOR.
  
 4. OK
  
 5. SHTS P1-1.1 THRU P1-1.3 CLEANOUTS REQUIRED BY
 SECTIONS 708.3.1, 708.3.2, 708.3.4, 708.3.5 AND 11-8.1
 (FOR STORM) SHALL BE SHOWN ON THE PLANS. ****RESPONSE
 NOTED, BUT COMMENT NOT ADDRESSED. MANY CLEANOUTS
 REQUIRED ARE NOT INDICATED. MANY CLEANOUTS REQUIRED ARE
 NOT SHOWN. CLEANOUTS AT THE BASE OF STACKS AS SHOWN ARE
 INCORRECT. THEY DO NOT CLEANOUT THE BASE OF THE STACK.
 ALSO SHOW THE CLEANOUTS REQUIRED ON THE RISER
 DIAGRAMS.
 ****RESPONSE NOTED, BUT THE CLEANOUT SHOWN ON P3-3.0
 DETAIL 1 AS SHOWN IS CORRECT, BUT IT'S NOT SHOWN ON THE
 FLOOR PLAN. PLEASE CORRELATE INFORMATION ON ALL SHEETS.
 ALSO SEE RISERS P/1, P/7 & P/8.
  
 6.OK
 7.OK
 8.OK
 9.OK
 10. OK
 11. OK
 12. OK
 13. OK
  
 14. SHT P1-6.0 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF EACH
 AREA, AND SHOW 1/2 AREA OF ALL VERTICAL WALLS,
 INCLUDING PARAPETS, AS WELL AS ALL AREAS OF ROOFS
 DRAINING ONTO THE ROOF FROM ABOVE IN THE CALCULATIONS.
 SECTIONS 1106, AND 1107 WITH ALL SUBSECTIONS. SHOW THE
 LOCATION OF ALL SECONDARY ROOF DRAINS AND OR EMERGENCY
 OVERFLOW SCUPPERS. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT NO CALCULATIONS WERE
 SUBMITTED.
 ****RESPONSE NOTED, BUT THE CALCULATIONS ARE NOT
 CORRECT. NO VERTICAL CONTRIBUTION IS SHOWN FOR THE
 LOWER ROOFS. (A1 THRU A4, A7 THRU A9, E1 THRU E4, E7
 THRU E9, E1 THRU E4, & H1 THRU H4). THE WALL AT COL.
 LINES 4&7 BETWEEN COL. LINES A&D, CALCULATIONS INDICATE
 7', WHICH IS SUPPOSED TO BE 1/2 THE WALL HEIGHT. BY
 LOOKING AT A SECTION OF THE WALL, THE HEIGHT IS 20' AND
 1/2 THE WALL HEIGHT SHOULD BE 10'. (SEE A4-2.0WHICH
 SHOW THE WALL TO BE 18', AND IF ITS SIMILAR TO DETAIL 3
 ON SHT A5-1.1 WILL HAVE A 2' PARAPET WALL ON TOP OF THE
 ROOF LINE. PLEASE RECHECK ALL CALCULATIONS FOR THE ROOF
 AREAS.
  
 15. OK
 16. OK (SHOWN ON SHT P2-1.0U)
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
 28. OK
 29. OK
 30. OK
 31. OK
 32. OK
 33. OK
 34. OK
 35. OK
  
 36. SUBMIT A SANITARY HORIZONTAL RISER ISOMETRIC AND
 VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, TRAPS,
 VENTS, CLEANOUTS, OFFSETS, RISER NUMBERS AND DFU'S AS
 THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3.
 ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN,
 ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND DFU'S ARE NOT
 SHOWN AS THEY ACCUMULATE IN THE SYSTEM. ALSO INDICATE
 ON THE FIRST FLOOR WHERE ALL RISERS BEGIN IN THE
 SYSTEM.
 ****RESPONSE NOTED, BUT SHT P3-1.0 RISER 1, LAVS DO NOT
 REFLECT THE FLOOR PLAN 2ND FLOOR C2-1.03. - DOES NOT
 REFLECT THE FLOOR PLAN C4.103/C4.104 DRINKING FOUNTAINS
 SHOW 3, FLOOR PLAN SHOWS 2. - CLEANOUT NOT SHOWN AT THE
 BASE OF P/1. - NOT ALL PIPE SIZES SHOWN.-SHT P3-2.0
 RISER P/2 CLEANOUT DOWNSTREAM OF JANITOR SINK IN ROOM
 C4.101 NOT INSTALLED PER SECTION 706.3. SECOND CLEANOUT
 AT THE BASE OF P/2 NOT REQUIRED AS IT DOES NOT CLEANOUT
 THE BASE OF THE STACK, NOR DOES IT REFLECT THE FLOOR
 PLAN. - FLOOR DRAIN PIPING IN ROOM D1.101 AS INDICATED
 IS BEING INSTALLED ABOVE THE FLOOR. - EACH DRINKING
 FOUNTAIN SHALL HAVE ITS OWN TRAP. SAFE WASTE FOR THE
 FIXTURES IS NOT APPROVED.(SEE ROOMS D1.101, D1.108,
 AND A3.111). -CLEANOUTS ARE REQUIRED AT THE BASE OF
 STACKS P/4 & P/10. - CLEANOUT FOR P/7 NOT INSTALLED AT
 THE BASE OF P/7. -THE NEW SANT. PIPING TO TOILET ROOM
 D2.105 NOT SHOWN ON THE FLOOR PLAN. -SHOW ALL TOILET
 ROOM NUMBERS ON THE RISER DIAGRAM. - SHOW ALL PIPE
 SIZES. THE PIPE SIZES ARE NOT SHOWN ON MANY PIPES.-
 SHT P3-3.0A TWO WAY CLEANOUT IS REQUIRED NEAR THE
 JUNCTION OF THE BUILDING DRAIN AND THE BUILDING SEWER.
 (DETAIL 1).-THE RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN FOR A1.05 & A1.106. AN EXTRA FLOOR DRAIN IS
 INDICATED THAT IS NOT SHOWN ON THE FLOOR PLAN.-
 A3.102 & A3.103 ONLY SHOWS 2 LAVS ON THE RISER AND THE
 FLOOR PLAN SHOWS 4.-A4.103 & A4.104TWO W/C'S ARE
 MISSING FROM THE RISER THAT ARE SHOWN ON THE FLOOR
 PLAN.-A4.105NO FLOOR DRAIN AND A SECOND SINK ARE
 SHOWN ON THE FLOOR PLAN THAT ARE NOT SHOWN ON THE RISER
 DIAGRAM. (JANITOR ROOM).-A5.105 SHOWS THE BRANCH
 LINE CONNECTING NEAR THE DRINKING FOUNTAINS ON THE
 FLOOR PLAN, BUT CONNECTING DOWNSTREAM OF THE NEXT
 FIXTURES ON THE RISER DIAGRAM.-A CLEANOUT IS
 REQUIRED AT THE BASE OF RISER P/8-ALL RISER
 DIAGRAMS,CHECK ALL PIPE SIZES, MAKE SURE THE RISER
 DIAGRAMS REFLECT THE FLOOR PLAN FOR BOTH THE SANITARY
 AND THE VENTING.SECTIONS106.1.1, 106..1.2, 706.3,
 708.3.4, 708.3.5, 100.2.1.
  
 37. SUBMIT A STORM HORIZONTAL RISER ISOMETRIC DIAGRAM &
 VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, OFFSETS,
 & CLEANOUTS AND INDICATE THE RISER NUMBERS. SHOW THE
 SQUARE FOOTAGE AS IT ACCUMULATES IN THE SYSTEM. SECTION
 106.3.5.1.3.
 ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN,
 ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND SQUARE
 FOOTAGE AS IT ACCUMULATES IN THE SYSTEM IS NOT
 INDICATED.
 ****RESPONSE NOTED, BUT THE GARAGE STORM INDICATES A
 TOTAL OF 10,498SF. THE TOTAL AREA WITHOUT ANY VERTICAL
 WALL/PARAPET CONTRIBUTION IS 23,663SF. PLEASE
 RECALCULATE THE SQUARE FOOTAGE DRAINING INTO EACH
 DRAIN. SHOW 1/2 AREA OF ALL VERTICAL WALL INCLUDING
 PARAPETS, AS WELL AS ALL AREAS FROM ROOFS THAT DRAIN
 ONTO THE ROOF FROM ABOVE, (SEE STAIRWELL ROOFS &
 ELEVATOR), IN CALCULATIONS. -THE TRENCH DRAINS SHOW
 NO SF CONTRIBUTING TO THE TOTAL SF. INDICATE THE
 LOCATIONS OF THE DOWNSPOUTS FROM THE ROTUNDA/MECHANICAL
 ROOF. IF THE LOCATION IS THE SAME AS SHOWN ON THE
 ARCHITECTURAL PLANS, PLEASE EXPLAIN THE REASONING FOR
 DIVIDING THE UPPER ROOF CONTRIBUTION TO TWO ROOF DRAINS
 ON EACH SIDE OF THE BUILDING, WHEN ACTUALLY THE TOTAL
 AREA WILL DRAIN TO ONE DRAIN ON EACH SIDE. THIS IS ALSO
 A CONCERN FOR THE LOWER ROOF (FIRST STORY)ROOF DRAINS
 ( 1736SF). PLEASE CLARIFY.
  
 38. SUBMIT A WATER RISER ISOMETRIC DIAGRAM. SHOW ALL
 PIPE SIZES, VALVES, WATER HAMMER ARRESTORS, BACKFLOW
 PROTECTION ETC. SECTION 106.3.5.1.3.
 ****RESPONSE NOTED, BUT NOT ALL PIPE SIZES ARE SHOWN,
 NOT ALL REQUIRED VALVES ARE SHOWN, AND ALL WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9, (ICE MAKERS,
 DISHWASHERS, & WASH MACHINES IF FIXTURES ARE
 PROVIDED).
 ****RESPONSE NOTED, BUT THE VALVES ON ALL DOWN-FEED
 WATER LINES ARE MISSING FROM MANY LAV SUPPLY LINES,
 SOME TOILET ROOMS, SS, ETC. SECTION 106.1(4).
  
 39. OK
  
 40. ALL PME & FIRE PROTECTION SHEETS. PLANS SHALL BE
 SIGNED, SEALED, AND DATED. SECTION 106.1. ALL TITLE
 BLOCK INFORMATION REQUIRED BY FAC 61G1-23.002 AND FS
 471.025 SHALL BE SUBMITTED ON EACH SHEET. ****RESPONSE
 NOTED, BUT THE SEAL USED IS NOT APPROVED. NEW SEALS
 SHALL INDICATE THE WORD "LICENSE" IN THE SEAL. (SEE
 ATTACHED SHEET FROM THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS).
 ****RESPONSE NOTED, BUT THE SEALS OF SOME MECH. AND
 PLUMBING SHEETS ARE STILL THE OLD SEAL. - ALSO THERE
 SEEMS TO BE TWO SETS OF SIGNATURES FOR THE ENGINEER OF
 RECORD. PLEASE SUBMIT A SIGNED, SEALED, DATED,
 NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE OF THE
 ENGINEER OF RECORD FOR OUR FILES. ONE SET OF PLANS
 SHALL BE RETAINED FOR POSSIBLE REVIEW BY THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS.
  
 **************NEW COMMENTS**************
  
 1B. SHTS P1-1.0U, P1-1.1U, P1-1.1 & P1-2.1. RWL-4 DOES
 NOT REFLECT THE SQUARE FOOTAGE SHOWN ON RISER DIAGRAM
 OR ROOF PLAN. PLEASE CORRELATE RISER, FLOOR PLAN, &
 ROOF PLAN. SECTION 106.1.1.
 ****RESPONSE NOTED. WILL RECHECK AFTER THE CALCULATIONS
 FOR THE ROOF DRAINS HAS BEEN RESUBMITTED WITH
 CORRECTIONS.
  
 2B. SHTS P1-1.OU & P1-1.1U ALL RWL'S THAT CONNECT TO
 RWL-4 TO BE INDICATED ON THE 1ST FLOOR. THIS WILL AID
 IN TRACING THE RWL'S THROUGH THE BUILDING AND TO VERIFY
 PIPE SIZES. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT ISSUE NOT ADDRESSED.
  
 3B. SHTS P1-1.1U & P2-1.0U DETAIL #6 THE SINK SHALL NOT
 DRAIN THRU THE WET VENT FOR THE TOILET ROOM. THE
 DISCHARGE FOR THE SINK SHALL CONNECT DOWNSTREAM OF THE
 TOILET ROOM FIXTURES. SECTION 909.1.
 ****RESPONSE NOTED, BUT THE PIPING HAS NOT BEEN CHANGED
 ON SHT P1-1.0U
  
 4B. OK
  
 5B. SHT P1-1.2U CLEANOUT REQUIRED AT THE BASE OF P/1 &
 P/10 RISERS, NEAR THE JUNCTION OF THE BUILDING DRAIN
 AND THE BUILDING SEWER, AND AT ALL CHANGES OF DIRECTION
 OVER 45 DEGREES. PLEASE INDICATE ON PLANS. SECTIONS.
 708.3.3, 708.3.4, 708.3.5.
 ****RESPONSE NOTED, BUT C/O'S ARE NOT SHOWN ON SHTS
 P3-1.0 & P3-2.0.
  
 6B. SHTS P1-1.2U, ASSOCIATED RISER DIAGRAMS, AND
 ENLARGED FLOOR PLANS. INDICATE HOW THE STACKS P/1 &
 P/10 CAN DRAIN INTO THE TOILET GROUP FIXTURE BRANCH.
 SUBMIT A DETAIL SHOWING THE 4" CLEANOUT TEE, THE 4"
 CROSS FOR THE FIXTURE BRANCH, AND THE 4" DOUBLE
 Y/EIGHTH BEND FITTINGS STACKED ON TOP OF EACH OTHER.
 WILL THEY BE AT THE RIGHT HEIGHT FOR THE W/C'S?SEE
 SECTION 908.3 ALSO. SECTION 106.1.1. (STACKS SHOULD
 CONNECT TO THE BUILDING DRAIN AND FIXTURE GROUPS SHOULD
 CONNECT TO THE STACK SO THAT THE STACK DOES NOT RUN
 THRU THE MIDDLE OF THE FIXTURE GROUP). ****RESPONSE
 NOTED, BUT C/O'S ARE REQUIRED AT THE BASE OF EACH
 STACK. COMMENT HAS NOT BEEN ADDRESSED.
  
 7B. SHTS P1-1.3U, P1-2.0, P1-2.3, P1-3.3, & P1-4.3
 RWL-6 DOES NOT REFLECT THE SQUARE FOOTAGE SHOWN ON THE
 RISER DIAGRAM, NOR ON THE ROOF PLAN. PLEASE CORRELATE
 INFORMATION. SECTION 106.1.1 & TABLE 1106.3.
 ****RESPONSE NOTED, BUT THE COMMENT WAS NOT ADDRESSED
 ON SHTS P1-3.3, & P1-4.3.
  
 8B. OK
 9B. OK
 10B. OK
 11B. OK
  
 12B. SHT P1-4.1 SHOW RISER P/3 VTR. - NOTE STATES "SEE
 01 ON DRAWING P2-3.0". INFORMATION NOT SHOWN ON DETAIL
 01. PLEASE CLARIFY. - SHOW THE VENTING TO REFLECT THE
 FLOOR PLAN FOR KINK S-1 CONNECTED TO RISER P/8. - 4"
 SANITARY - 4" VTR AT COL. LINE E/8 IS SHOWN AS AN
 OFFSET ON THE RISER DIAGRAM. PLEASE CORRELATE FLOOR
 PLAN AND SANT. RISER DIAGRAM. SECTION 106.1.1.
 ****RESPONSE NOTED. NOTE DELETED, BUT COMMENT NOT
 ADDRESSED FOR OFFSETS AND VENTING. -VENTING ON ALL
 RISERS SHALL REFLECT THE VENTING ON THE FLOOR PLAN.
 (ALL VENTING NOT SHOWN ON THE FLOOR PLAN), AND ON THE
 ENLARGED PLUMBING PLANS FLOOR PLAN.
  
 13B. OK
 14B. OK
  
 15B. SHT P1-6.0 SHOW THE LOCATIONS FOR ALL VTR'S. -
 INDICATE THE RWL EACH ROOF DRAIN IS CONNECTED TO.
 SECTION 106.1.1.
 ****RESPONSE NOTED, BUT VTR'S 1, 3, 9 & 10 ARE NOT
 SHOWN.
  
 16B. SHT P2-1.0U DETAIL 1, FLOOR DRAINS IN C1.104 ARE
 NOT VENTED. SECTION 901.2.1. - THE PIPING AT THE LAVS
 IN ROOM C1.103 DOES NOT REFLECT THE RISER DIAGRAM.
 PLEASE CORRELATE. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE FLOOR DRAIN IN THE
 ACCESSIBLE STALL HAS NOT CHANGED TO REFLECT THE CHANGE
 IN THE RISER DIAGRAM.
  
 17B. SHT P2-1.0U DETAIL 2 DOES NOT REFLECT THE PIPING
 LAYOUT SHOWN ON P1-1.2U. - SUBMIT A DETAIL FOR THE
 SANT. PIPING ARRANGEMENT FOR THE DRINKING FOUNTAINS,
 SHOW HOW THE PIPING CONNECTS THROUGH THE SIDE OF THE
 D.F. UNITS. - SUBMIT A DETAIL FOR THE FITTING
 ARRANGEMENT WHERE THE TOILET ROOM FIXTURES CONNECT TO
 THE BLDG. DRAIN. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT A DETAIL HAS NOT BEEN
 SUBMITTED. ALSO EXPLAIN THE 3" SANT. LINE FROM THE
 DRINKING FOUNTAINS TO THE MEN'S ROOM D1/101.-THE
 FLOOR DRAIN PIPING APPEARS TO BE ABOVE THE SLAB. PLEASE
 CLARIFY.
  
 18B. OK
  
 19B. SHT P2-1.0U DETAIL 6, SINK SHALL CONNECT
 DOWNSTREAM OF THE WET VENTED FIXTURES IN THE TOILET
 ROOM. SECTION 909.1.
 ****RESPONSE NOTED. CORRECTED, BUT NOT CORRECTED ON SHT
 P1-1.1U. PLEASE CORRECT TO REFLECT RISER AND DETAIL.
  
 20B. OK
 21B. OK
  
 22B. SHT P2-1.0 DETAIL 4 DOES NOT REFLECT THE FLOOR
 PLAN. NO WATER TO WH'S & SHOWS 2" WATER SUPPLY. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT STILL NO WATER SUPPLY TO WATER
 HEATERS.
  
 23B. OK
 24B. OK
 25B. OK.
  
 26B. SHT P2-2.0 DETAIL 3, SUBMIT A DETAIL FOR SANT.
 PIPING TO D.F.'S - INDICATE RISERS FOR COLD WATER
 DOWNSTREAM OF LAST W/C'S. HOT WATER LINE NOT SHOWN THRU
 BATHROOM FIXTURES. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT STILL SHOWS PIPING OUT THE SIDE
 OF 1ST DF.
  
 27B. OK
 28B. OK
 29B. OK
  
 30B. SHT P2-3.0 DETAIL 1, INDICATE WHERE SANT. BRANCH
 LINE CONNECTS TO THE SANT. RISER. - FLOOR DRAIN SHOWS
 NO PIPING. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT RISER SHOWS P1 RISER BETWEEN
 W/C'S & LAVS, WHEREAS THE FLOOR PLAN SHOW THE RISER
 BETWEEN W/C'S. CORRELATE RISER AND FLOOR PLAN.
  
 31B. OK
 32B. OK
 33B. OK
  
 34B. SHT P3.1.0 SANT RISER DIAGRAM, TRAPS ARE REQUIRED
 ON ALL DRINKING FOUNTAINS. SECTION 1002.1. - 1ST FLOOR
 LAVS PIPING DOES NOT REFLECT THE FLOOR PLAN. - FLOOR
 DRAINS DOWNSTREAM OF RISER P/1 ARE NOT VENTED. SECTION
 901.2.1. - A C/O IS REQUIRED AT THE BASE OF STACK P/1
 SECTION 708.3.4 - SHOW THE CONNECTION DETAIL AT THE
 BASE OF STACK P/1 WITH A 4" CLEANOUT, A 4" CROSS, AND
 4" WYE FITTINGS INDICATING THE HEIGHT OF THE W/C
 STUBOUT. - W/C-1 AT THE BASE OF STACK IS NOT VENTED.
 SECTION 901.2.1. -W/C ON 2ND FLOOR IS NOT VENTED.
 SECTION 901.2.1. - LAV ON 3RD FLOOR NOT VENTED. SECTION
 901.2.1. - INDICATE HOW/WHERE PIPING FOR LAVS & FLOOR
 DRAINS CONNECT TO THE RISER/BRANCH ON THE 2ND, 3RD, &
 4TH FLOORS. THE FITTINGS INDICATE THAT THE PIPING IS
 SLOPED TO THE LAVS. PLEASE CLARIFY. - MEN C4.104 DOES
 NOT REFLECT ROOM NUMBER ON THE FLOOR PLAN. - PIPING FOR
 FLOOR DRAINS & LAVS 4TH FLOOR DOES NOT REFLECT THE
 FLOOR PLAN. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT 1ST FLOOR LAVS PIPING DOES NOT
 REFLECT THE FLOOR PLAN. -A C/O IS REQUIRED AT THE
 BASE OF STACK P/1 SECTION 708.3.4 - SHOW THE CONNECTION
 DETAIL AT THE BASE OF STACK P/1 WITH A 4" CLEANOUT, A
 4" CROSS, AND 4" WYE FITTINGS INDICATING THE HEIGHT OF
 THE W/C HOW THE CONNECTION DETAIL AT THE BASE OF STACK
 P/1 WITH A 4" CLEANOUT, A 4" CROSS, AND 4" WYE FITTINGS
 INDICATING THE HEIGHT OF THE W/C STUBOUT. - MEN C4.104
 DOES NOT REFLECT ROOM NUMBER ON THE FLOOR PLAN. -
 PIPING FOR FLOOR DRAINS & LAVS 4TH FLOOR DOES NOT
 REFLECT THE FLOOR PLAN. SECTION 106.1.1. THESE ITEMS
 HAVE NOT BEEN ADDRESSED.
  
 35B. ALL RISER DIAGRAMS, ALL FLOOR PLANS FOR ALL
 SYSTEMS. INDICATE THE PIPE SIZE. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT MANY PIPE SIZES ARE NOT SHOWN
 ON THE RISER DIAGRAMS.
  
 36B. SHT P3-2.0 JANITOR ROOM PIPING DOES NOT REFLECT
 THE FLOOR PLAN. - TRAPS REQUIRED ON ALL DRINKING
 FOUNTAINS. SECTION 1002.1. - CLEANOUTS REQUIRED AT THE
 BASE OF ALL STACKS. 708.3.4. - PIPING TO FLOOR DRAIN
 SHOWN ABOVE THE FLOOR IN ROOM D1.101. PLEASE CLARIFY. -
 PIPING AT THE BASE OF RISER P/2 DOES NOT REFLECT THE
 FLOOR PLAN. - PIPING TO FD-2 AT THE LOADING D1.106 DOES
 NOT REFLECT THE FLOOR PLAN. - PIPING FOR A1.108/A1.109
 DOES NOT REFLECT THE FLOOR PLAN. - ROOM D2.103 IS
 INDICATED AS D2.104 ON THE FLOOR PLAN. CORRELATE
 INFORMATION. - ALL VENTING AT RISER P/10 STOPS AT LEVEL
 2. SECTION 903.3 VTR REQUIRED. - TOILET ROOM A2.708 IS
 INDICATED AS A2.706 ON THE FLOOR PLAN. CORRELATE
 INFORMATION. - BATHROOM RISER DOES NOT REFLECT THE
 FLOOR PLAN. (NO FD). - PIPING TO ROOM A4.414 DOES NOT
 REFLECT THE FLOOR PLAN. - CLEANOUT PIPING DOWNSTREAM OF
 C4.101 IS NOT APPROVED AS PIPED. SECTION 706.3. -
 PIPING ON RISER DOES NOT REFLECT THE FLOOR PLAN
 UPSTREAM OF C3.105. - JANITOR SINK C3.105 IS NOT
 VENTED. SECTION 901.2.1. - FLOOR DRAIN CONNECTION AT
 BRANCH LINE 4TH FLOOR DOES NOT REFLECT THE FLOOR PLAN.
 - PIPING AT A2.107 DOES NOT REFLECT THE FLOOR PLAN. (NO
 F.D. PIPING). - PIPING AT ROOM A3.111 DOES NOT REFLECT
 THE FLOOR PLAN AT THE LAVS. - ROOM A3.111 SUBMIT A
 DETAIL FOR FITTING TO W/C & LAVS. - ROOM D2.105 SHOWN
 AS D2.106/D2.107 ON FLOOR PLANS. CORRELATE INFORMATION.
 - ROOM C3.410/C3.412 FLOOR DRAIN FITTING ARE SHOWN TO
 BE INSTALLED AGAINST THE FLOW. SECTION 706.3. - SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT SOME COMMENTS WERE NOT
 ADDRESSED. SEE THE FOLLOWING: JANITOR ROOM PIPING DOES
 NOT REFLECT THE FLOOR PLAN. - TRAPS REQUIRED ON ALL
 DRINKING FOUNTAINS. SECTION 1002.1. - CLEANOUTS
 REQUIRED AT THE BASE OF ALL STACKS. 708.3.4. - PIPING
 TO FLOOR DRAIN SHOWN ABOVE THE FLOOR IN ROOM D1.101.
 PLEASE CLARIFY.- PIPING AT THE BASE OF RISER P/2 DOES
 NOT REFLECT THE FLOOR PLAN. - PIPING FOR A1.108/A1.109
 DOES NOT REFLECT THE FLOOR PLAN. - ROOM D2.103 IS
 INDICATED AS D2.104 ON THE FLOOR PLAN. CORRELATE
 INFORMATION.- TOILET ROOM A2.708 IS INDICATED AS
 A2.706 ON THE FLOOR PLAN. CORRELATE INFORMATION. -
 PIPING TO ROOM A4.414 DOES NOT REFLECT THE FLOOR PLAN.
 - CLEANOUT PIPING DOWNSTREAM OF C4.101 IS NOT APPROVED
 AS PIPED. SECTION 706.3. - PIPING AT ROOM A3.111 DOES
 NOT REFLECT THE FLOOR PLAN AT THE LAVS. - ROOM A3.111
 SUBMIT A DETAIL FOR FITTING TO W/C & LAVS. - ROOM
 D2.105 SHOWN AS D2.106/D2.107 ON FLOOR PLANS. CORRELATE
 INFORMATION.
  
 37B. SHT P3-3.0 PIPING TO A3.304 & DOWNSTREAM DOES NOT
 REFLECT THE FLOOR PLAN. - VENT PIPING FROM S-1 SINK
 DOES NOT REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN. -
 TRAPS REQUIRED ON ALL DRINKING FOUNTAINS. SECTION
 1002.1. - S-1 SINK SHALL NOT DRAIN THRU THE WET VENT OF
 THE TOILET ROOM A1.303. SINK SHALL DISCHARGE DOWNSTREAM
 OF THE W/C & LAV. SECTION 909.1. - INDICATE P/8 WITH
 P/6 AT THE BASE OF THE STACK WHERE IT BEGINS. - PIPING
 TO ROOMS A1.105/A1.106 DOES NOT REFLECT THE FLOOR PLAN.
 FLOOR DRAIN PIPING IS SHOWN AS ABOVE THE FLOOR. - P/5 &
 P/9 BEGIN AT THE BASE OF THE STACK. PLEASE INDICATE ON
 RISER DIAGRAM. - PIPING FOR A3.102/A3.103 DOES NOT
 REFLECT THE FLOOR PLAN. - CLEANOUT REQUIRED AT THE BASE
 OF P/9 STACK. - PIPING TO FLOOR DRAINS IN ROOMS
 A3.102/A3.103 ARE ABOVE THE FLOOR. -W/C AT THE BASE
 OF STACK NOT VENTED. SECTION 901.2.1. - INDICATE WHERE
 LINES TO FLOOR DRAINS IN ROOMS A4.103/A4.104 &
 A5.103/A5.104 ARE CONNECTING TO THE BRANCH/STACK. -
 PIPING FOR A4.103/A4.104 DOES NOT REFLECT THE FLOOR
 PLAN. - W/C AT RISER STACK A4.103 IS NOT VENTED.
 SECTION 901.2.1. - PIPING FOR A4.105 DOES NOT REFLECT
 THE FLOOR PLAN. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT
 ADDRESSED:-PIPING TO A3.304 & DOWNSTREAM DOES NOT
 REFLECT THE FLOOR PLAN. - VENT PIPING FROM S-1 SINK
 DOES NOT REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN. -
 PIPING TO ROOMS A1.105/A1.106 DOES NOT REFLECT THE
 FLOOR PLAN. FLOOR DRAIN PIPING IS SHOWN AS ABOVE THE
 FLOOR. -PIPING FOR A4.103/A4.104 DOES NOT REFLECT THE
 FLOOR PLAN. - W/C AT RISER STACK A4.103 IS NOT VENTED.
 SECTION 901.2.1. - PIPING FOR A4.105 DOES NOT REFLECT
 THE FLOOR PLAN. SECTION 106.1.1.
  
 38B. OK
  
 39B. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS PERMIT:
  
 A. OK - "NEW"SHOW THE LOCATION OF THE 2PSI TO 1/2PSI
 REGULATOR. SHUT OFF VALVE REQUIRED UPSTREAM OF
 REGULATOR.
 B. OK
 C. OK
 D. OK
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT NOT ADDRESSED
  
 F. OK - INFORMATIONAL - 2PSI AT MAXIMUM 200 FT
 DEVELOPED LENGTH ALLOWS 39,656,000 BTU'S. ONLY 10,000
 BTU'S ARE INDICATED ON PLANS. THE 10,000 BTU'S IS
 QUESTIONABLE AS MOST RESIDENTIAL DRYERS ARE RATED AT
 22,000 BTU'S. FOR COMPARISON, A .5 PSI SYSTEM WITH 2"
 PIPE WILL DELIVER 800,000 BTU'S. WITH THE EXTRA
 DEVELOPED LENGTH TO THE FARTHEST FUTURE GENERATOR,ITS
 APPROXAMATLY 180'.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT NO MANUF. SHEETS FOR THE
 GENERATOR HAS BEEN SUBMITTED. - ALSO SUBMIT THE MANUF.
 SPECIFICATION SHEETS FOR THE GAS REGULATORS. INDICATE
 MODEL NUMBER. LISTING INFORMATION REQUIRED.
  
 H. NA
 I. NA
  
 40B. SHT P3-5.0 NO HOT WATER LINE SHOWN IN 1ST THRU 4TH
 FLOOR TOILET ROOMS OFF WATER RISER W/1. - WATER RISER
 DOES NOT REFLECT THE FLOOR PLAN AT THE LAVS. - FULL
 OPEN VALVES ARE REQUIRED ON ALL WATER DOWN-FEED LINES.
 SECTION 606.1(4). - RISER DOES NOT REFLECT THE FLOOR
 PLAN AT ROOMS C2.102/C2.103. (2 LAVS SHOWN EACH TOILET
 ROOM). - PIPE SIZE SUPPLYING ROOMS D1.101/D1.102,
 JANITOR ROOM D1.110, TOILET ROOMS A1.108/A1.109. -
 INDICATE THAT RISERS W/4, W/5, & W/8 RISERS START WITH
 RISER W/2 ON THE 1ST FLOOR. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT
 ADDRESSED: - WATER RISER DOES NOT REFLECT THE FLOOR
 PLAN AT THE LAVS. - FULL OPEN VALVES ARE REQUIRED ON
 ALL WATER DOWN-FEED LINES. SECTION 606.1(4). (MANY
 LAVS, TOILET ROOMS, SINKS ETC MISSING VALVES).- RISER
 DOES NOT REFLECT THE FLOOR PLAN AT ROOMS C2.102/C2.103.
 (2 LAVS SHOWN EACH TOILET ROOM). - PIPE SIZE SUPPLYING
 ROOMS D1.101/D1.102, JANITOR ROOM D1.110, TOILET ROOMS
 A1.108/A1.109. (2" SHOWN ON FLOOR PLAN, 1-1/2" ON
 RISER. 3/4" ON FLOOR PLAN, 1/2" ON RISER.SOME LAVS
 SHOW SEPARATE DROPS TO EACH LAV ON THE FLOOR PLAN, BUT
 SINGLE DROPS ON THE RISER). - INDICATE THAT RISERW/8
 STARTS WITH RISER W/2 ON THE 1ST FLOOR. SECTION
 106.1.1.
  
 41B. SHT P3-6.0 RISERS 4, 5 & 8 ARE NOT INDICATED ON
 THE 1ST FLOOR. - RISER DOES NOT REFLECT THE FLOOR PLAN
 ROOMS C3.107/C3.108 AT JAN. SINK, ROOMS C3.410/C3.412,
 AE.111, A4.103/A4.104, A4.105 AND THE TOP OF RISER W/4
 TO ROOM A5.105, PIPE SIZE AT ROOM A2.209 & SUPPLY TO
 TOILET ROOM ADJACENT, PIPE SIZE SUPPLYING RISER W/8 &
 RISER, SUPPLY LINE TO ROOMS D2.102/D2.103. - W/2 NOT
 FOUND ON 4TH FLOOR AS INDICATED ON RISER. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT THE FOLLOWING COMMENTS WERE NOT
 ADDRESSSED: RISER 8 STILL NOT INDICATED ON THE 1ST
 FLOOR. - RISER DOES NOT REFLECT THE FLOOR PLAN ROOMS
 C3.410/C3.412,A4.103/A4.104, (FLOOR PLAN INDICATES
 OVER-HEAD SUPPLY WITH DROPS, BUT RISER INDICATES SUPPLY
 RUN IN THE WALL OFF WATER RISER. TWO W/C'S MISSING ON
 RISER).-PIPE SIZE AT ROOM A2.209, (SHOWS 1" ON THE
 FLOOR PLAN), - PIPE SIZE SUPPLYING RISER W/8 & RISER, (
 1" ON FLOOR PLAN, 2" ON RISER - 1-1/2" ON THE FLOOR
 PLAN, BUT 2" ON THE RISER). -W/2 NOT FOUND ON 4TH OR
 5TH FLOORS AS INDICATED ON RISER. SECTION 106.1.1.
 PLEASE CORRELATE RISER AND FLOOR PLANS.
  
 42B. SHT P3-7.0 SIZE ALL PIPE PER SECTION 1106.3, AND
 SHOW ALL PIPE SIZES ON THE RISER. - RISER DOES NOT
 REFLECT THE FLOOR PLAN TOP FLOORS RWL/6 & RWL/7. -
 RISERS INDICATE A 5TH FLOOR, BUT FLOOR PLAN DOES NOT
 SHOW A 5TH FLOOR. - RISER SHOWS TRENCH DRAINS ON TWO
 FLOORS, BUT ONLY SHOW TRENCH DRAINS ON 1 FLOOR, (ROOF
 LEVEL), ON THE FLOOR PLAN. -RWL'S 9 THRU 14 SHOW OFFSET
 PIPING FOR ROOF DRAINS IN THE 4TH FLOOR CEILING, BUT
 INDICATE THE ROOF DRAINS TO BE ON THE 4TH LEVEL. PLEASE
 CLARIFY. - PIPE SIZING IS INCORRECT AT 8"/11,715SF,
 6"/5077SF, 6"/6657SF. TABLE 1106.3. - RWL/9 INDICATES
 PIPING IN 3RD FLOOR CEILING, BUT ROOF DRAINS ARE TO BE
 ON THE 3RD LEVEL. PLEASE CLARIFY. - RWL/15 DOES NOT
 REFLECT THE FLOOR PLAN TO 4" ROOF DRAINS. - PIPING AT
 THE 1ST FLOOR CEILING CONNECTING TO ROOF DRAINS ON THE
 1ST LEVEL. PLEASE CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT SOME COMMENTS THE FOLLOWING
 COMMENTS WERE NOT ADDRESSED:- RISER DOES NOT REFLECT
 THE FLOOR PLAN TOP FLOORS RWL/6 & RWL/7. - RISERS
 INDICATE A 5TH FLOOR, BUT FLOOR PLAN DOES NOT SHOW A
 5TH FLOOR. - RISER SHOWS TRENCH DRAINS ON TWO FLOORS,
 BUT ONLY SHOW TRENCH DRAINS ON 1 FLOOR, (ROOF LEVEL),
 ON THE FLOOR PLAN. - PIPE SIZING IS INCORRECT AT
 8"/11,715SF, 6"/5077SF, 6"/6657SF. TABLE 1106.3.
  
 43B. SHTS 1,2,3 OF 3 ARE NOT SIGNED, SEALED, & DATED AS
 REQUIRED PER FS 472.025(1). ALSO SEE SHT 1 WHICH STATES
 "NOT VALID UNLESS SEALED WITH SURVEYOR'S EMBOSSED SEAL
 AND SIGNATURE"
 ****NO RESPONSE, NOT ADDRESSED.
  
 44B. SHTS C1, C5 THRU C22 ENGINEERING CERTIFICATE OF
 AUTHORIZTION IS REQUIRED IN THE TITLE BLOCK.
 61G15-23.002(2) & FS 471.025. - AN EMBOSSED SEAL IS
 REQUIRED TO IMPRESS REQUIRED INFORMATION ON EACH SHEET.
 UNABLE TO GLEAN ALL INFORMATION REQUIRED FROM SEAL.
 PLEASE RESEAL PLANS.
 ****NO RESPONSE, NOT ADDRESSED.
  
 45B. SHTS LP-0 THRU LP-3 & IR-1 THE CERTIFICATE OF
 AUTHORIZATION IS REQUIRED IN THE TITLE BLOCK.
 61G1-16.004(1) & FS 481.319.
 ****NO RESPONSE, NOT ADDRESSED.
  
 46B. SHT LL-1 IS MISSING THE TITLE BLOCK INFORMATION
 REQUIRED IN 61G1-16.004.
 ****NO RESPONSE, NOT ADDRESSED.
  
 47B. SHT IR-1 THE CONTROLER & RAIN SENSOR LOCATIONS ARE
 REQUIRED ON PLANS. SECTION 106.1.1.
 ****NO RESPONSE. THIS INFORMATION SHALL BE SUBMITTED AS
 A REVISION PRIOR TO APPLICATION, OR WITH THE
 APPLICATION FOR IRRIGATION PERMIT - NEW COMMENT, NO
 CERTIFICATE OF AUTHORIZATION IN THE TITLE BLOCK AS
 REQUIRED BY 61G1-16.004(2) & FS 481.319.
  
 48B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 2ND
 FLOOR DRINKING FOUNTAINS SHOWS 4 REQUIRED, BUT ONLY 3
 ARE REQUIRED PER TABLE 403.1. FIXTURE COUNT INDICATES
 ONLY 2 ARE PROVIDED. PLEASE PROVIDE REQUIRED AMOUNT OF
 DRINKING FOUNTAINS.
 ****NO RESPONSE, NOT ADDRESSED.
  
 49B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 3RD
 FLOOR DRINKING FOUNTAINS SHOW ONLY 3 ARE REQUIRED. PER
 TABLE 403.1, 4 DRINKING FOUNTAINS ARE REQUIRED. PLEASE
 UPDATE FIXTURE COUNT.
 ****NO RESPONSE, NOT ADDRESSED.
  
 50B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 4TH
 FLOOR DRINKING FOUNTAINS INDICATE 4 REQUIRED, BUT ONLY
 3 ARE PROVIDED. PLEASE PROVIDE 4 DRINKING FOUNTAINS.
 TABLE 403.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 51B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 1ST
 FLOOR DRINKING FOUNTAINS 2 REQUIRED PER TABLE 403.1,
 BUT READS 1 REQUIRED. PLEASE CORRECT FIXTURE COUNT
 REQUIRED.
 ****NO RESPONSE, NOT ADDRESSED.
  
 52B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 3RD
 FLOOR DRINKING FOUNTAINS 4 REQUIRED PER TABLE 403.1,
 BUT READS 2 REQUIRED. PLEASE CORRECT FIXTURE COUNT
 REQUIRED. - SHOWS 2 PROVIDED, BUT 4 ARE REQUIRED.
 PLEASE CORRECT INFORMATION.
 ****NO RESPONSE, NOT ADDRESSED.
  
 53B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 4TH
 FLOOR LAVS REQUIRED 2, INDICATED AS 1. PLEASE CORRECT
 THE FIXTURE COUNT. TABLE 403.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 54B. SHT LSO.0 LIBRARY/MUSEUM INDICATES A RESTURANT IN
 OCCUPANT LOAD 1ST FLOOR.PLEASE CONTACT LYNN MASSON,
 ENVIRONMENTAL COMPLIANCE MANAGER CONCERNING THE
 POSSIBLE REQUIREMENT FOR A GREASE INTERCEPTOR. CONTACT
 LYNN BY PHONE (561) 822-2271, OR FAX (561) 822-2279, OR
 E-MAIL [email protected].
 ****PER ARCHITECT, NO RESTURANT WILL BE IN THE LIBRARY.
 THIS WAS INDICATED AS A RESTURANT FOR OCCUPANCY
 CALCULATIONS ONLY. THERE WILL BE A CAFE IN THE LIBRARY
 WITH NO FOOD PREPARATION.
  
 55B. SHT LSO.0 INDICATES ASSEMBLY OCCUPANCY FOR THE
 CITY HALL AND LIBRARY/MUSEUM. POTTY PARITY IS REQUIRED
 PER SECTION 403.1.1 AND HAS BEEN INDICATED IN THE 50%
 REVIEW BY PAUL SCHMITZ. THIS HAS NOT BEEN ADDRESSED.
 PLEASE SHOW COMPLIANCE WITH THIS REQUIREMENT. ****NO
 RESPONSE, NOT ADDRESSED.
  
 56B. SHT A2-0 3 AREAS SHOW STORM WATER FROM ROOF AREAS
 ABOVE THAT CONTRIBUTE TO THE MAIN ROOF AREAS BELOW. THE
 SLOPE OF THE MAIN ROOF AND THE LOCTION OF THE DOWNSPOUT
 IS SHOWING THE TOTAL AREA DRAINING TO ONE ROOF DRAIN,
 BUT THE AREA IS DIVIDED EQUALLY BETWEEN TWO ROOF
 DRAINS. THE SIZING FOR THE ROOF DRAINS WILL HAVE TO BE
 RECHECKED TO ACCOUNT FOR THE AMOUNT OF AREA DRAINING TO
 ONE DRAIN, NOT TWO. TABLE 1106.3. (SEE ROOF AREAS AT
 COL. LINES 1THRU 4/A THRU D, 7 THRU 9.1/A THRU D, AND 4
 - 5/E THRU H).
 ****NO RESPONSE, NOT ADDRESSED.
  
 57D. SHTS A2-0, A2-1, A2-2, A2-3 SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS. INDICATE THE
 CONTRUBUTION ADD FROM 1/2 AREA OF ALL VERTICAL WALLS,
 INCLUDING PARAPETS, AND ROOF AREAS FROM ABOVE ADDED TO
 THE ROOF SECTIONS. THIS IS REQUIRED FOR ALL ROOF
 LEVELS. SQUARE FOOTAGE IS SHOWN, BUT NO CALCULATIONS
 WERE SUBMITTED. CONTRIBUTING VERTICAL AREAS FOR WALLS
 IS UNCLEAR. IS THE AREA SHOWN INDICATED PER WALL, OR
 TOTAL FOR ALL WALLS SHOWN. PLEASE CLARIFY. SECTIONS
 1106.1, 1106.2, 1106.3, 1106.4.
 ****NO RESPONSE NOTED. PRIMARY AND SECONDARY ROOF DRAIN
 CALCULATIONS WERE NOT FOUND.
  
 58B. SHT A2-0 UPPER ROOF BY DOME SHOWS A DETAIL
 INDICATOR 20/A2-D.1. DETAIL 20 NOT FOUND ON SHT A2-D.1.
 PLEASE CLARIFY. SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 59B. SHT A2-D.1 DETAIL 04 SHOW HEIGHT AND WIDTH AND
 INDICATE THE MEASUREMENT FROM THE ROOF TO THE FLOW LINE
 OF THE SCUPPER. SECTIONS 106.1.1 AND 1503.4.3. ****NO
 RESPONSE, NOT ADDRESSED.
  
 60B. SHT A6-1.1 DETAILS 1 THRU 6. SHOW THE TURNING AREA
 IN THE TOILET ROOMS. NOT IN THE ACCESSIBLE STALLS.
 SECTION 11-4.22.3.
 ****NO RESPONSE, NOT ADDRESSED.
  
 61B. SHT A6-1.1 DETAIL 2, SHOW THE CLEAR FLOOR SPACE
 FOR THE URINAL. SECTION 11-4.18.3.
 ****NO RESPONSE, NOT ADDRESSED.
  
 62B. SHT A6-1.1 DETAIL 4, ACCESSIBLE W/C SHALL BE 1'6"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG.
 11-28. LAV TO BE MIN. 15" (C/L OF CLEAR FLOOR SPACE).
 ****NO RESPONSE, NOT ADDRESSED.
  
 63B. SHT A6-1.1 DETAIL 7, ACCESSIBLE W/C SHALL BE 1'6"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG.
 11-28. (SHOWS 2'2").
 ****NO RESPONSE, NOT ADDRESSED.
  
 64B. SHT A6-2.1 DETAILS 2, 6 & 7 SHOWTHE TURNING AREA
 IN THE TOILET ROOMS. NOT IN THE ACCESSIBLE STALLS.
 SECTION 11-4.22.3.
 ****NO RESPONSE, NOT ADDRESSED.
  
 65B. SHT A6-2.1 DETAIL 4, ACCESSIBLE W/C SHALL BE 1'6"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG.
 11-28.
 ****NO RESPONSE, NOT ADDRESSED.
  
 66B. SHT A6-3.1 DETAIL 2, SHOW A TURNING AREA IN THE
 LOCKER ROOM AREA. SECTION 11-4.2.3.
 ****NO RESPONSE, NOT ADDRESSED.
  
 67B. SHT A6-3.1 DETAILS 1, 3, 4 & 5, SHOW THE TURNING
 AREA IN THE TOILET ROOMS, NOT IN THE ACCESSIBLE STALLS.
 SECTION 11-4.22.3.
 ****NO RESPONSE, NOT ADDRESSED.
  
 68B. SHT A6-4.1 DETAILS 1 & 2, SHOW THE TURINING AREA
 IN THE TOILET ROOMS, NOT IN THE ACCESSIBLE STALLS.
 SECTION 11-4.22.3.
 ****NO RESPONSE, NOT ADDRESSED.
  
 69B. SHT A6-5.1 DETAIL 1, SHOW THE TURNING AREA IN THE
 TOILET ROOM, AND SHOW THE CLEAR FLOOR SPACE FOR THE
 URINAL. SECTIONS 11-4.22.3 AND 11-4.18.3.
 ****NO RESPONSE, NOT ADDRESSED.
  
 70B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS
 C1.105, C1.106, A2.705, A2.706, A2.210, A2.211, A3.111,
 A3.114, C3.410, AND C3.412 ALL INDICATE THE WALLS TO BE
 PAINTED. PLEASE INDICATE HOW THIS COMPLIES WITH THE
 REQUIREMENT FOR "SMOOTH, HARD, NONABSORBENT WALLS AS
 REQUIRED IN SECTION 1210.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 71B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS D2.10
 & D2.104 SHOW NO WALL FINISH AND THE FLOORING/BASE
 INDICATE RUBBERIZED FLOORING. INDICATE HOW THIS
 COMPLIES WITH "SMOOTH, HARD, NONABSORBENT FLOORS AS
 REQUIRED IN SECTION 1210.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 72B. SHT A9-4.1 INDICATE THE ROOM NUMBERS THAT THE
 DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.2 CLEARANCES
 C. 11-4.19.4 EXPOSED PIPES & CLEARANCES
 ****NO RESPONSE, NOT ADDRESSED.
  
 73B. SHT A9-4.2 INDICATE THE ROOM NUMBERS THAT THE
 DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 DETAIL #1
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.2 CLEARANCES
 C. 11-4.19.4 EXPOSED PIPES & CLEARANCES
 ****NO RESPONSE, NOT ADDRESSED.
  
 DETAIL #2
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.2 CLEARANCES
 C. 11-4.19.4 EXPOSED PIPES & CLEARANCES
 ****NO RESPONSE, NOT ADDRESSED.
  
 74B. SHT A9-4.4 INDICATE THE ROOM NUMBERS THAT THE
 DETAILS ARE REFERENCING.SHOW COMPLIANCE WITH THE
 FOLLOWING:
 DETAILS #1 - #2 - #3
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 ****NO RESPONSE, NOT ADDRESSED.
  
 75B. SHT A9-4.5 DETAILS (1) & (2), SHOW THE FOLLOWING
 FOR COMPLIANCE:A. 11-4.19.2 CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 D. 11-4.21.5 CONTROLS
 E. 11-4.21.7 CURBS
 ****NO RESPONSE, NOT ADDRESSED.
  
 76B. SHTS A1.307, A1.709, A2.209, A2.315, A2.407,
 A3.109, C3.409, C3.310, A5.504 - SHOW COMPLIANCE WITH
 THE FOLLOWING
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED)
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
 ****NO RESPONSE, NOT ADDRESSED.
  
 *************NEW COMMENTS*************
  
 1C. SHT P9-4.6 DETAILS 1 & 2 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.2 CLEARANCES
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
  
 2C. SHT P9-4.7 DETAILS 1, 2, & 3 SHOW COMPLIANCE WITH
 THE FOLLOWING:
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.2 CLEARANCES
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
  
 3C. SHT P1-6.0 THE FOLLOWING VENTS ARE NOT SHOWN ON THE
 ROOF. P1, P2, P3, & P10. PLEASE SHOW ON THIS SHEET OR
 INDICATE WHERE THEY ARE SHOWN. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. SUBMITTING THE RED
 LINED SET OF PLUMBING SHEETS WHEN RESUBMITTING FOR
 REVIEW WILL HELP EXPEDITE THE PERMIT ALSO. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  