2006-12-26 13:25:55DENIED:
 RESPONSE TO COMMENTS DATED 11-07-06:
  
 COMMENT 1:OK
 COMMENT 2A & 2B:OK
  
 COMMENT 2C:RESPONSE INDICATES THE CAPACITY OF THE
 FUEL STORAGE TANK LOCATED ON THE FIRST FLOOR IS 500
 GALLONS. THE SUBMITTAL BOOK REFLECTS (2) DAY TANKS ONE
 WITH THE CAPAPCITY OF 100 GALLONS AND THE SECOND ONE
 WITH A CAPACITY OF 150 GALLONS.PLEASE SUBMIT THE
 CORRECT SUBMITTAL FOR THE DAY TANK.
  
 COMMENT 3:OK
  
 COMMENT 9:OK
  
 COMMENT 10:OK
  
 COMMENT 11:OK
  
 COMMENT 12:OK
  
 COMMENT 13:OK
  
 COMMENT 14:OK
  
 COMMENT 15:OK
  
 COMMENT 16:RESPONSE INDICATES FIRE RATINGS ARE NOT
 REQUIRED FOR ELECTRICAL RM.SMOKE RATING IS INDICATED
 FOR THE MECHANICAL ROOM AND A 1 HR RATING FOR THE
 ELEVATOR EQUIPMENT RM.PER 2004 FMC 607.8,SMOKE
 DAMPERS, FIRE DAMPERS AND COMBINATION DAMPERS ARE TO BE
 IDENTIFIEDON THE BUILDING PLANS.PLEASE NOTE, LIFE
 SAFETY PLANS IDENTIFY CERTIAN WALLS/PARTITIONS AS
 HAVING A FIRE, SMOKE OR FIRE/SMOKE RATING THAT ARE NOT
 REFLECTED ON THE ARCHITECTURAL PLANS.PLEASE CORRELATE
 LIFE SAFETY, ARCHITECTURAL AND MECHANICAL PLANS. PLEASE
 SEE ?ADDITIONAL COMMENT #21?.
  
 COMMENT 17:OK
  
 COMMENT 18:OK
  
 COMMENT 19:OK
  
 COMMENT 20:OK
 ADDITIONAL COMMENTS:
  
 21.THE FOLLOWING PLAN SHEET & ROOM NUMBERS ARE
 MISSING DAMPERS AS REQUIRED PER 2004 FMC 607.5.4 &
 607.5.4.1:
  
 DWG M1-1.1; RM# - A1.014, A1.118, A1.110
 DWG M1-2.1; RM# - C1.101, D1.108, A1.110, D1.111.
  
 PLEASE ALSO NOTE ON DWG #M1-1.2, THE OUTSIDE AIR INTAKE
 TO THE WEST EXTERIOR WALL.PER 2004 FMC 401.5.1,
 INTAKE OPENINGS SHALL BE LOCATED A MINIMUM OF 10 FT
 FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 STREETS, ALLEYS, PARKING LOTS OR LOADING DOCKS.
  
 DWG M1-2.1 CORRIDOR A2.010, 38/18 & 12/10 DUCT,RM #
 A2.104, A2.108, A2.407, A2.08, A2.409
 DWG M1-2.2 RM# C2.101, C2.219, D2.108
 DWG M1-3.1 CORRIDOR A3.008, A3.012, A3.406, A3.308,
 A3.706, C3.414 RM# A3.107, A3.106, A3.421, A3.420,
 A3.105, A3.104, A3.304, A3.205, C3.314, C3.413, A3.705,
 A3.603, A3.115, A3.514, A3.513
 DWG M1-3.2 CORRIDOR C3.417, C3.407, C3.426, RM# C3.418,
 C3.310, C3.309, C3.402, C3.107,C3.101
 DWG M1-4.1 CORRIDOR A4.009, A4.008, A4.007 RM#A4.415,
 A4.101 & F/D FROM RM# A4.416.
 DWG M1-4.2 RM# C4.106, C4.104.PLEASE NOTE, MECHANICAL
 FLOOR PLAN DOES NOT MATCH THE LIFE SAFETY PLAN FOR THIS
 PARTICULAR FLOOR.THE VOICE DATA RM & ELECTRICAL RM
 ARE NOT INDICATED ON THE MECHANICAL SHEET.
  
 DWG M1-5.1 CORRIDOR A5.009, A5.008, A5.007 RM# A5.303,
 A5.203, A5.101, A5.507, A5.107, A5.416
  
 22.PLAN SHEET M1-1.0 KEY NOTE 1 SPECIFIES THE
 CONDENSATE TO MOP SINK IN THE GARAGE AREA.PER CITY
 CODE SEC. 90-125(5) CONDENSATE SHALL NOT TERMINATE INTO
 THE SANITARY.PLAN SHEET P1-10U INDICATES THE
 CONDENSATE TO A DRYWELL WHICH IS CODE COMPLIANT. PLEASE
 CORRELATE MECHANICAL PLAN WITH PLUMBING PLAN.
  
 ADDITIONAL PERMIT REQUIRED FOR FUEL PIPING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].
  
  
  
  
  
  
  
  