2006-12-26 13:25:55 | DENIED: |
| RESPONSE TO COMMENTS DATED 11-07-06: |
| |
| COMMENT 1:OK |
| COMMENT 2A & 2B:OK |
| |
| COMMENT 2C:RESPONSE INDICATES THE CAPACITY OF THE |
| FUEL STORAGE TANK LOCATED ON THE FIRST FLOOR IS 500 |
| GALLONS. THE SUBMITTAL BOOK REFLECTS (2) DAY TANKS ONE |
| WITH THE CAPAPCITY OF 100 GALLONS AND THE SECOND ONE |
| WITH A CAPACITY OF 150 GALLONS.PLEASE SUBMIT THE |
| CORRECT SUBMITTAL FOR THE DAY TANK. |
| |
| COMMENT 3:OK |
| |
| COMMENT 9:OK |
| |
| COMMENT 10:OK |
| |
| COMMENT 11:OK |
| |
| COMMENT 12:OK |
| |
| COMMENT 13:OK |
| |
| COMMENT 14:OK |
| |
| COMMENT 15:OK |
| |
| COMMENT 16:RESPONSE INDICATES FIRE RATINGS ARE NOT |
| REQUIRED FOR ELECTRICAL RM.SMOKE RATING IS INDICATED |
| FOR THE MECHANICAL ROOM AND A 1 HR RATING FOR THE |
| ELEVATOR EQUIPMENT RM.PER 2004 FMC 607.8,SMOKE |
| DAMPERS, FIRE DAMPERS AND COMBINATION DAMPERS ARE TO BE |
| IDENTIFIEDON THE BUILDING PLANS.PLEASE NOTE, LIFE |
| SAFETY PLANS IDENTIFY CERTIAN WALLS/PARTITIONS AS |
| HAVING A FIRE, SMOKE OR FIRE/SMOKE RATING THAT ARE NOT |
| REFLECTED ON THE ARCHITECTURAL PLANS.PLEASE CORRELATE |
| LIFE SAFETY, ARCHITECTURAL AND MECHANICAL PLANS. PLEASE |
| SEE ?ADDITIONAL COMMENT #21?. |
| |
| COMMENT 17:OK |
| |
| COMMENT 18:OK |
| |
| COMMENT 19:OK |
| |
| COMMENT 20:OK |
| ADDITIONAL COMMENTS: |
| |
| 21.THE FOLLOWING PLAN SHEET & ROOM NUMBERS ARE |
| MISSING DAMPERS AS REQUIRED PER 2004 FMC 607.5.4 & |
| 607.5.4.1: |
| |
| DWG M1-1.1; RM# - A1.014, A1.118, A1.110 |
| DWG M1-2.1; RM# - C1.101, D1.108, A1.110, D1.111. |
| |
| PLEASE ALSO NOTE ON DWG #M1-1.2, THE OUTSIDE AIR INTAKE |
| TO THE WEST EXTERIOR WALL.PER 2004 FMC 401.5.1, |
| INTAKE OPENINGS SHALL BE LOCATED A MINIMUM OF 10 FT |
| FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS |
| STREETS, ALLEYS, PARKING LOTS OR LOADING DOCKS. |
| |
| DWG M1-2.1 CORRIDOR A2.010, 38/18 & 12/10 DUCT,RM # |
| A2.104, A2.108, A2.407, A2.08, A2.409 |
| DWG M1-2.2 RM# C2.101, C2.219, D2.108 |
| DWG M1-3.1 CORRIDOR A3.008, A3.012, A3.406, A3.308, |
| A3.706, C3.414 RM# A3.107, A3.106, A3.421, A3.420, |
| A3.105, A3.104, A3.304, A3.205, C3.314, C3.413, A3.705, |
| A3.603, A3.115, A3.514, A3.513 |
| DWG M1-3.2 CORRIDOR C3.417, C3.407, C3.426, RM# C3.418, |
| C3.310, C3.309, C3.402, C3.107,C3.101 |
| DWG M1-4.1 CORRIDOR A4.009, A4.008, A4.007 RM#A4.415, |
| A4.101 & F/D FROM RM# A4.416. |
| DWG M1-4.2 RM# C4.106, C4.104.PLEASE NOTE, MECHANICAL |
| FLOOR PLAN DOES NOT MATCH THE LIFE SAFETY PLAN FOR THIS |
| PARTICULAR FLOOR.THE VOICE DATA RM & ELECTRICAL RM |
| ARE NOT INDICATED ON THE MECHANICAL SHEET. |
| |
| DWG M1-5.1 CORRIDOR A5.009, A5.008, A5.007 RM# A5.303, |
| A5.203, A5.101, A5.507, A5.107, A5.416 |
| |
| 22.PLAN SHEET M1-1.0 KEY NOTE 1 SPECIFIES THE |
| CONDENSATE TO MOP SINK IN THE GARAGE AREA.PER CITY |
| CODE SEC. 90-125(5) CONDENSATE SHALL NOT TERMINATE INTO |
| THE SANITARY.PLAN SHEET P1-10U INDICATES THE |
| CONDENSATE TO A DRYWELL WHICH IS CODE COMPLIANT. PLEASE |
| CORRELATE MECHANICAL PLAN WITH PLUMBING PLAN. |
| |
| ADDITIONAL PERMIT REQUIRED FOR FUEL PIPING. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS |
| AT (561)805-6719 OR E-MAIL [email protected]. |
| |
| |
| |
| |
| |
| |
| |
| |