Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop G
Sequence Number 2
Notes
Date Text
2007-01-30 17:59:07DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
  
 FROM PREVIOUS REVIEW:
 FROM PREVIOUS REVIEW:
  
 39B. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS PERMIT:
  
 A. OK - "NEW"SHOW THE LOCATION OF THE 2PSI TO 1/2PSI
 REGULATOR. SHUT OFF VALVE REQUIRED UPSTREAM OF
 REGULATOR.
 B. OK
 C. OK
 D. OK
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT NOT ADDRESSED
  
 F. OK - INFORMATIONAL - 2PSI AT MAXIMUM 200 FT
 DEVELOPED LENGTH ALLOWS 39,656,000 BTU'S. ONLY 10,000
 BTU'S ARE INDICATED ON PLANS. THE 10,000 BTU'S IS
 QUESTIONABLE AS MOST RESIDENTIAL DRYERS ARE RATED AT
 22,000 BTU'S. FOR COMPARISON, A .5 PSI SYSTEM WITH 2"
 PIPE WILL DELIVER 800,000 BTU'S. WITH THE EXTRA
 DEVELOPED LENGTH TO THE FARTHEST FUTURE GENERATOR,ITS
 APPROXAMATLY 180'.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT NO MANUF. SHEETS FOR THE
 GENERATOR HAS BEEN SUBMITTED. - ALSO SUBMIT THE MANUF.
 SPECIFICATION SHEETS FOR THE GAS REGULATORS. INDICATE
 MODEL NUMBER. LISTING INFORMATION REQUIRED.
  
 H. NA
 I.NA
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6721
 E-MAIL [email protected]
  
  
  
  
  