Date |
Text |
2007-01-30 17:59:07 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS |
| |
| |
| FROM PREVIOUS REVIEW: |
| FROM PREVIOUS REVIEW: |
| |
| 39B. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING |
| INFORMATION IS REQUIRED FOR THE GAS PERMIT: |
| |
| A. OK - "NEW"SHOW THE LOCATION OF THE 2PSI TO 1/2PSI |
| REGULATOR. SHUT OFF VALVE REQUIRED UPSTREAM OF |
| REGULATOR. |
| B. OK |
| C. OK |
| D. OK |
| |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| ****RESPONSE NOTED, BUT NOT ADDRESSED |
| |
| F. OK - INFORMATIONAL - 2PSI AT MAXIMUM 200 FT |
| DEVELOPED LENGTH ALLOWS 39,656,000 BTU'S. ONLY 10,000 |
| BTU'S ARE INDICATED ON PLANS. THE 10,000 BTU'S IS |
| QUESTIONABLE AS MOST RESIDENTIAL DRYERS ARE RATED AT |
| 22,000 BTU'S. FOR COMPARISON, A .5 PSI SYSTEM WITH 2" |
| PIPE WILL DELIVER 800,000 BTU'S. WITH THE EXTRA |
| DEVELOPED LENGTH TO THE FARTHEST FUTURE GENERATOR,ITS |
| APPROXAMATLY 180'. |
| |
| G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| ****RESPONSE NOTED, BUT NO MANUF. SHEETS FOR THE |
| GENERATOR HAS BEEN SUBMITTED. - ALSO SUBMIT THE MANUF. |
| SPECIFICATION SHEETS FOR THE GAS REGULATORS. INDICATE |
| MODEL NUMBER. LISTING INFORMATION REQUIRED. |
| |
| H. NA |
| I.NA |
| |