2006-12-22 11:22:46 | 1. ON PAGE C-16 AT LEAST FIVE FIRE DEPARTMENT |
| CONNECTIONS ARE SHOWN. AS STATED PREVIOUSLY, THAT MANY |
| FIRE DEPARTMENT CONNECTIONS ARE NOT NEEDED. |
| 2. SEVERAL AREAS ON PAGE FP1-1.1 ARE ABSENT OF FIRE |
| SPRINKLER PROTECTION. |
| 3. SEVERAL AREAS ON PAGE FP1-1.2 ARE ABSENT OF FIRE |
| SPRINKLER PROTECTION. |
| 4. STAIR # 2 ON PAGE FP1-2.1 IS MISSING THE FIRE |
| VALVE. |
| 5. FIRE SPRINKLER HEADS MISSING IN VOICE DATA A2.105 |
| AND UTILITY ROOM A2105.1 ON PAGE FP1-2.1. |
| 6. CLOSETS A3.110.1 AND A3.118.1 ARE ABSENT OF FIRE |
| SPRINKLER HEADS ON PAGE FP1-3.1. |
| 7. SERVER ROOM A4.416 SHOWN ON PAGE FP1-4.1 IS EQUIPPED |
| WITH AN FM 200 SYSTEM. THIS ROOM IS LOCATED IN A |
| SPRINKLERED BUILDING AND SHALL CONTAIN FIRE SPRINKLER |
| PROTECTION SERVED BY A SEPARATE VALVE PER THE |
| REQUIREMENTS OF NFPA 75, THE STANDARD FOR THE |
| PROTECTION OF INFORMATION TECHNOLOGY EQUIPMENT. SECTION |
| 8-1.1 AND 8.1.3 PROVIDES GUIDANCE ON THESE |
| REQUIREMENTS. |
| 8. FIRE SPRINKLER HEADS NOT SHOWN IN CAFE C1.401 ON |
| PAGE FP1-1.0. |
| 9. EXIT DOOR NEAR VOICE DATA C4.108 SWINGS IN THE WRONG |
| DIRECTION ON PAGE ID2-4.2. |
| 10. "NO EXIT" SIGNS SHALL BE INSTALLED ON THE DOUBLE |
| DOORS TO SERVER ROOM NEAR STAIR # ON PAGE LS1-4.1. |
| THESE DOORS ARE IN CLOSE PROXIMITY TO THE EXIT DOOR. |
| 11. ONLY TWO FIRE ALARM STROBES EXIST IN THE PARKING |
| AREA SHOWN ON PAGE FA1-6. |
| 12. NO FIRE ALARM DEVICES EXIT IN MACHINE ROOM A6.102 |
| ON PAGE FA1-6. PLEASE EXPLAIN. |
| 13. MANUAL PULL STATION LOCATED IN VOICE DATA CLOSET |
| C4.108 ON PAGE FA1-4.0. THE MANUAL PULL STATION SHOULD |
| BE LOCATED NEXT TO STAIR. |
| 14. VOICE DATA C3.104 ON PAGE FA1-3 IS MISSING SMOKE |
| DETECTOR LIKE OTHER SIMILAR SPACES. PLEASE ADVISE. |
| 15. MANUAL PULL STATION MISSING FROM STAIR # 2 ON PAGE |
| FA1-2. |
| 16. NO SMOKE DETECTOR PRESENT IN VOICE DATA C1.102 BUT |
| EXIST IN SIMILAR SPACES ON PAGE FA1-1. |
| 17. NO EXIT SIGNS APPEAR TO EXIST IN PROGRAM MEETING |
| ROOM C3.306 WHICH CONTAINS FIFTY SEATS ON PAGE E2-3.2. |
| 18. AN EXIT SIGN IN THE PROGRAM/MEETING ROOM ON PAGE |
| E2-3.2 IS CONFUSING. IF THE SIGN IS LOCATED INSIDE THE |
| ROOM, THE EXIT SIGN IS SWINGING IN THE WRONG DIRECTION. |
| IF THE SIGN IS OUTSIDE THE ROOM OTHER EXIT SIGNS ARE |
| VAILABLE TO DIRECT PERSONS. PLEASE ADVISE. |
| 19. THE EXIT SIGN FROM PLANNING INTO THE ENTRY/WAITING |
| AREA STILL APPEARS CONFUSING. ONCE IN THE ENTRY/WAITING |
| AREA WHAT IS THE PREFERRED EXIT TRAVEL DIRECTION |
| ANTICIPATED ON PAGE E2-2.1. PLEASE PROVIDE MORE |
| DETAILS. |
| 20. EXIT SIGNS STILL APPEAR TO BE MISSING FROM BACK OF |
| HOUSE OF THE COMMISSION CHAMBERS ON PAGE E2-2.1. |
| 21. NO ILLUMINATED EXIT SIGNS DISPLAYED IN LARGE |
| MECHANICAL ROOM DISPLAYED ON PAGE ON PAGE E1-1.3 |
| 22. SOME ISSUES REMAIN WITH THE LIFE SAFETY SHEETS AND |
| THE ARCHITECTURAL DRAWINGS AS THEY RELATE TO WALL |
| RATINGS. PLEASE ENSURE THAT THEY MIRROR ONE ANOTHER. |
| 23. COULD NOT LOCATE FLOOR LEVEL INFORMATION AS IT |
| RELATES TO EXIT DOORS. PLEASE SEE NFPA 101, THE LIFE |
| SAFETY CODE, SECTION 7.2.1.3. |
| 24. COULD NOT LOCATE A VISUAL ON THE FIREFIGHTERS SMOKE |
| CONTROL PANEL ONLY A DESCRIPTION OF WHAT IT WILL LOOK |
| LIKE. |
| 25. THE TEMPORARY STANDPIPE SYSTEM REQUIREMENT COULD |
| NOT BE LOCATED ON THE LIFE SAFETY OR FIRE SPRINKLER |
| SYSTEM DRAWINGS. |
| 26. ALL BUILDING, MECHANICAL, ELECTRICAL, PLUMBING |
| COMMENTS ARE TO BE SATISFIED. |
| |
| MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER |
| 804-4709 PHONE |
| 804-4774 FAX |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |