Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2006-12-22 11:22:461. ON PAGE C-16 AT LEAST FIVE FIRE DEPARTMENT
 CONNECTIONS ARE SHOWN. AS STATED PREVIOUSLY, THAT MANY
 FIRE DEPARTMENT CONNECTIONS ARE NOT NEEDED.
 2. SEVERAL AREAS ON PAGE FP1-1.1 ARE ABSENT OF FIRE
 SPRINKLER PROTECTION.
 3. SEVERAL AREAS ON PAGE FP1-1.2 ARE ABSENT OF FIRE
 SPRINKLER PROTECTION.
 4. STAIR # 2 ON PAGE FP1-2.1 IS MISSING THE FIRE
 VALVE.
 5. FIRE SPRINKLER HEADS MISSING IN VOICE DATA A2.105
 AND UTILITY ROOM A2105.1 ON PAGE FP1-2.1.
 6. CLOSETS A3.110.1 AND A3.118.1 ARE ABSENT OF FIRE
 SPRINKLER HEADS ON PAGE FP1-3.1.
 7. SERVER ROOM A4.416 SHOWN ON PAGE FP1-4.1 IS EQUIPPED
 WITH AN FM 200 SYSTEM. THIS ROOM IS LOCATED IN A
 SPRINKLERED BUILDING AND SHALL CONTAIN FIRE SPRINKLER
 PROTECTION SERVED BY A SEPARATE VALVE PER THE
 REQUIREMENTS OF NFPA 75, THE STANDARD FOR THE
 PROTECTION OF INFORMATION TECHNOLOGY EQUIPMENT. SECTION
 8-1.1 AND 8.1.3 PROVIDES GUIDANCE ON THESE
 REQUIREMENTS.
 8. FIRE SPRINKLER HEADS NOT SHOWN IN CAFE C1.401 ON
 PAGE FP1-1.0.
 9. EXIT DOOR NEAR VOICE DATA C4.108 SWINGS IN THE WRONG
 DIRECTION ON PAGE ID2-4.2.
 10. "NO EXIT" SIGNS SHALL BE INSTALLED ON THE DOUBLE
 DOORS TO SERVER ROOM NEAR STAIR # ON PAGE LS1-4.1.
 THESE DOORS ARE IN CLOSE PROXIMITY TO THE EXIT DOOR.
 11. ONLY TWO FIRE ALARM STROBES EXIST IN THE PARKING
 AREA SHOWN ON PAGE FA1-6.
 12. NO FIRE ALARM DEVICES EXIT IN MACHINE ROOM A6.102
 ON PAGE FA1-6. PLEASE EXPLAIN.
 13. MANUAL PULL STATION LOCATED IN VOICE DATA CLOSET
 C4.108 ON PAGE FA1-4.0. THE MANUAL PULL STATION SHOULD
 BE LOCATED NEXT TO STAIR.
 14. VOICE DATA C3.104 ON PAGE FA1-3 IS MISSING SMOKE
 DETECTOR LIKE OTHER SIMILAR SPACES. PLEASE ADVISE.
 15. MANUAL PULL STATION MISSING FROM STAIR # 2 ON PAGE
 FA1-2.
 16. NO SMOKE DETECTOR PRESENT IN VOICE DATA C1.102 BUT
 EXIST IN SIMILAR SPACES ON PAGE FA1-1.
 17. NO EXIT SIGNS APPEAR TO EXIST IN PROGRAM MEETING
 ROOM C3.306 WHICH CONTAINS FIFTY SEATS ON PAGE E2-3.2.
 18. AN EXIT SIGN IN THE PROGRAM/MEETING ROOM ON PAGE
 E2-3.2 IS CONFUSING. IF THE SIGN IS LOCATED INSIDE THE
 ROOM, THE EXIT SIGN IS SWINGING IN THE WRONG DIRECTION.
 IF THE SIGN IS OUTSIDE THE ROOM OTHER EXIT SIGNS ARE
 VAILABLE TO DIRECT PERSONS. PLEASE ADVISE.
 19. THE EXIT SIGN FROM PLANNING INTO THE ENTRY/WAITING
 AREA STILL APPEARS CONFUSING. ONCE IN THE ENTRY/WAITING
 AREA WHAT IS THE PREFERRED EXIT TRAVEL DIRECTION
 ANTICIPATED ON PAGE E2-2.1. PLEASE PROVIDE MORE
 DETAILS.
 20. EXIT SIGNS STILL APPEAR TO BE MISSING FROM BACK OF
 HOUSE OF THE COMMISSION CHAMBERS ON PAGE E2-2.1.
 21. NO ILLUMINATED EXIT SIGNS DISPLAYED IN LARGE
 MECHANICAL ROOM DISPLAYED ON PAGE ON PAGE E1-1.3
 22. SOME ISSUES REMAIN WITH THE LIFE SAFETY SHEETS AND
 THE ARCHITECTURAL DRAWINGS AS THEY RELATE TO WALL
 RATINGS. PLEASE ENSURE THAT THEY MIRROR ONE ANOTHER.
 23. COULD NOT LOCATE FLOOR LEVEL INFORMATION AS IT
 RELATES TO EXIT DOORS. PLEASE SEE NFPA 101, THE LIFE
 SAFETY CODE, SECTION 7.2.1.3.
 24. COULD NOT LOCATE A VISUAL ON THE FIREFIGHTERS SMOKE
 CONTROL PANEL ONLY A DESCRIPTION OF WHAT IT WILL LOOK
 LIKE.
 25. THE TEMPORARY STANDPIPE SYSTEM REQUIREMENT COULD
 NOT BE LOCATED ON THE LIFE SAFETY OR FIRE SPRINKLER
 SYSTEM DRAWINGS.
 26. ALL BUILDING, MECHANICAL, ELECTRICAL, PLUMBING
 COMMENTS ARE TO BE SATISFIED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER