2006-12-25 20:33:37 | ** UNSAT 2ND REVIEW ** |
| |
| |
| **** CITY CENTER ******* |
| |
| FOURTH REVIEW, 2ND UNDER PERMIT APPLICATION. |
| |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| MADE ON PREVIOUS REVIEWS. |
| |
| ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| PREVIOUS REVIEW NOTES. |
| |
| A "NO" IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR |
| FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS |
| ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER |
| EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| |
| AN "OK" WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| |
| A "NO/OK" MEANS PART OF THE COMMENT MAY HAVE BEEN |
| ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| |
| ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |
| |
| |
| 1) NOTE: NO, PLEASE SEE THREE SETS OF ALL ARE REQUIRED. |
| PLEASE SEE MISSING A THIRD SET OF ELECTRICAL SUBMITTALS |
| FOR GENERATOR, ATS, MTS ETC. |
| PLEASE ALSO SEE OTHER NOTES FOR MISSING THE LIGHTING |
| SPEC BOOKS AND ENGINEERING CALCULATIONS WHICH WERE |
| PREVIOUSLY SUBMITTED. |
| ENGINEERING FOR SELECTIVE COORDINATION PREVIOUSLY |
| SUBMITTED ETC. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE KNOW WHEN SUBMITTING FOR FINAL PERMITTING AND |
| STAMPING, A THIRD SET OF SIGNED, DATED AND SEALED PLANS |
| WILL BE REQUIRED. |
| PLEASE SEE FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE |
| CITY OF WEST PALM BEACH, 106.1.2106.1.3, 109.3.6 FOR |
| THRESHOLD BUILDINGS. THIS IS WILL BE REQUIRED FOR ALL |
| DOCUMENTATION AND PLANS AND FOR ALL TRADES WHETHER OR |
| NOT COMMENT IS MADE BY OTHER TRADES. |
| |
| 2) NOTE: NO, PLEASE SEE SYMBOL LEGEND ONLY HAD CHANGES |
| TO TWO OF THE DEVICES. PLEASE SEE ALL SWITCH/OVER RIDE |
| TYPE DEVICES INCLUDING THE OC SENSOR SHOULD INDICATE ON |
| THE SYMBOL LEGEND ITS DESIGNATION AND TIMES ON OVER |
| RIDES. THIS WOULD INCLUDE S3, ST, OC ETC. |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE FBC CHAPTER 13. PLEASE SEE 13-415.1.ABC.1.1, |
| .1.2 AND .1.3. |
| PLEASE BE SURE ALL DEVICE ON PLANS CORRELATE WITH THE |
| DEVICE SYMBOL LEGEND. |
| PLEASE BE SURE MAX TIME OF OVER -RIDES ARE SHOWN. IF |
| TIMER TYPE, (4HRS MAX), IF OCCUPANCY SENSOR TYPE (30 |
| MINS MAX). |
| PLEASE SEE ADDITIONAL COMMENTS FOR CONTROLS AND SYSTEM |
| BEING PROPOSED. |
| |
| 3) NOTE: OK. |
| |
| 4) NOTE: OK/NO, PLEASE SEE THESE WERE NOW SUBMITTED |
| HOWEVER PLEASE SEE NEW NOTES AT THE END OF THESE |
| COMMENTS AS THESE ARE NOW BEING SUBMITTED AND REVIEWED |
| FOR THE FIRST TIME AND THERE ARE COMMENTS ON DOCUMENTS |
| SUBMITTED. |
| PLEASE ALSO SEE NEW NOTES PERTAINING TO THE SIGNATURE |
| OF THE MECHANICAL ENGINEER OF RECORD ON SAID |
| DOCUMENTS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS FOR THE |
| ENTIRE BUILDING FOR REVIEW OF ALL TRADES. PLEASE KNOW |
| AS NONE WERE SUBMITTED AT THIS TIME THERE ARE MANY |
| ITEMS WHICH CAN NOT BE VERIFIED WITH THE PLANS, |
| EQUIPMENT AND LIGHTING. |
| PLEASE SEE 13-415.1.AB.1. |
| |
| 5) NOTE: OK/NO, PLEASE SEE THESE WERE SUBMITTED AND |
| SEEM TO BE OK, HOWEVER AS NOTED IN NOTE #4 ABOVE THERE |
| ARE NEW NOTES BASED ON THE COORDINATION OF THESE |
| DOCUMENTS WITH THE ENERGY CALCULATIONS SUBMITTED. |
| PLEASE SEE THE TOTALS ON THE WATTAGE DO NOT SEEM TO |
| CORRELATE WITH THE ENERGY CALCULATIONS AS SUBMITTED. |
| PLEASE ALSO SEE NEW NOTES. |
| PLEASE KNOW THE THREE SETS OF LIGHTING POWER DENSITIES |
| SHALL CONTAIN TITLE BLOCKS FOR THE ENGINEER AND/OR FIRM |
| OF RECORD. THIS MAY BE RE-DONE ON NEW SHEETS WHICH |
| CONTAIN THESE TITLE BLOCKS, STAMPED ON EACH SHEET WHICH |
| IS SIGNED AND SEALED BY THE ENGINEER OR HANDWRITTEN. |
| PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE 13-415.2, 13-415.2ABC.1 FOR MINIMUM AND |
| MAXIMUM PERFORMANCE CALCULATIONS. PLEASE SEE THE |
| CALCULATIONS SUBMITTED SHOWING THE LIGHTING POWER |
| DENSITIES (LPD) ARE NOT COMPLETE AND/OR THERE ARE ITEMS |
| WHICH DO NOT CORRELATE WITH SAID PLANS. |
| PLEASE SEE THERE ARE MANY ROOMS INDICATED ON PLANS |
| WHICH COULD NOT BE LOCATED IN CALCULATIONS OR THERE ARE |
| ROOMS ON CALCULATIONS WHICH COULD NOT BE LOCATED ON |
| PLANS. |
| PLEASE CORRELATE AND PLEASE SEE SOME OF THE LPD'S SEEM |
| TO BE VERY HIGH FOR SOME OF THE ROOMS AND AREAS AS |
| NOTED AND SHOWN. |
| PLEASE SEE OFFICE IN PARKING GARAGE FOR INSTANCE. |
| PLEASE SEE SOME OTHERS WHICH BASED ON THE TABLES AS |
| SET-FORTH IN THE CODE MAY ALLOW 1.7, THE CALCULATIONS |
| MAY SHOW 10.5 ETC. |
| PLEASE REVIEW ALL AND RE-ADJUST AS REQUIRED AND |
| NEEDED. |
| |
| 6) NOTE: NO, UNABLE TO VERIFY AT THIS TIME DUE TO THE |
| CONFLICTS BETWEEN THE ENERGY CALCULATIONS FOR EXTERIOR |
| LIGHTING AND THE ALLOWANCE LEVELS NOT BEING SHOWN. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE 13-415.2.ABC.1.3 FOR ALL EXTERIOR LIGHTING |
| ALLOWANCES, INCLUDING THAT WHICH IS DECORATIVE. PLEASE |
| SEE THERE ARE EXCEPTIONS FOR SOME AREAS; HOWEVER THESE |
| AREAS AS LISTED WOULD BE REQUIRED BY SECTIONS AS |
| LISTED. PLEASE SEE 13-415.0(3) (EXCEPTS). |
| |
| 7) NOTE: OK/NO, PLEASE SEE THE PLANS NOW SEEM TO |
| INDICATE THE EQUIPMENT MORE IN DETAIL, HOWEVER AS NOTED |
| IN NOTE #1, THE MANUFACTURES SPECS/CUT SHEETS WERE NOT |
| SUBMITTED BACK. THIS REVIEWER ONLY HAS THE ONE BOOK |
| WHICH WAS RETAINED BY THIS OFFICE. |
| WHEN SUBMITTING BOOKS/SPECS, PLEASE BE SURE TO HIGH |
| LIGHT AND COORDINATE WITH THE PLANS SUBMITTED FOR THE |
| EQUIPMENT AND DEVICES BEING INSTALLED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE PLANS SHALL INDICATE THE ACTUAL PANEL BEING |
| USED FOR LIGHTING CONTROLS. PLEASE SEE THERE ARE |
| SEVERAL PANELS INDICATE IN THE MANUFACTURE SPECS/CUT |
| SHEETS SUBMITTED AND THE ACTUAL UNIT NEEDS TO BE |
| HIGH-LIGHTED IN SPECS. PLANS SHALL ALSO BE REQUIRED TO |
| PROVIDE THE TECHNICAL INFORMATION AT EACH LIGHTING |
| CONTROL PANEL. (LCP) |
| ** PLEASE KNOW AS REFERENCE TO LIGHTING CONTROL PANELS |
| IN NOTES HERE ON WILL BE DESIGNATED AS "LCP'S". PLEASE |
| SEE RISER INDICATES LCP'S AS 225A RATED, WHICH IS OK, |
| HOWEVER PLEASE BE SURE THE INFORMATION AS SHOWN ON |
| CUT/SPEC SHEETS IS BROUGHT OVER TO THE PLANS AND LISTED |
| ON EACH LCP. |
| |
| 8) NOTE: OK/NO, PLEASE KNOW MOST OF THE SYSTEM IS |
| UNDERSTOOD HOWEVER THERE ARE AREAS IN WHICH A SWITCH |
| TYPE DEVICE (SENTRY) IS BEING INSTALLED ALONG WITH AN |
| OC (OCCUPANCY SENSOR) TYPE DEVICE. THE DETAIL WAS |
| LOCATED ON 7-2.0 HOWEVER THIS WOULD STILL PERMIT THE |
| TURNING OFF LIGHTS IN AN UNWANTED FASHION.PLEASE SEE |
| EGRESS STAIRS FOR MEZZANINE AREA WHICH COULD BE TURNED |
| OFF, YET OF AN OCCUPANT WAS STILL LOCATED ON THE UPPER |
| LEVEL THEY WOULD HAVE NO CONTROL OF LIGHTING AS SHOWN. |
| |
| PLEASE SEE ROOF TOP AREA ON E1-6.1 WHICH LOCATES A |
| SWITCH ON WHAT APPEARS TO BE AN OUTSIDE WALL TO CONTROL |
| LIGHTING IN ELEVATOR EQUIPMENT ROOM AS WELL AS OTHER |
| LIGHTING AS REQUIRED FOR LIFE SAFETY. |
| PLEASE SEE OTHER AREAS WHICH CONTAIN BOTH. |
| PLEASE ALSO SEE AS NO SPECS WERE SUBMITTED BACK, COULD |
| NOT LOCATE A LETTER FROM THE LUTRON MANUFACTURE WHICH |
| PERMITS THE USE OF THE SENTRY SWITCH IN THEIR SYSTEM. |
| PLEASE SEE AREAS OF MEETINGS ROOMS AND COMMISSION |
| CHAMBERS AREA WHICH DO NOT PROVIDE ENOUGH INFORMATION |
| FOR HOW THESE WILL BE CONTROLLED. PLEASE SEE THAT THE |
| NOTE ON THE PLANS FOR THIS TO BE PROVIDED BY LIGHTING |
| TECHNICAL NEEDS TO BE REPLACED WITH ACTUAL DETAILS ON |
| HOW THESE WILL BE ADDRESSED TO COMPLY WITH CHAPTER 13 |
| AT THIS TIME. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE KNOW THERE IS CONCERN OVER THE TYPE OF SYSTEM |
| BEING PROPOSED AND CONTROLS OF SAID SYSTEM. PLANS CALL |
| FOR A "SWEEP" EACH HOUR FOR THE SYSTEM OUT OF NORMAL |
| BUSINESS HOURS AND THIS WILL TURN OFF ANY AND ALL |
| DEVICES. THE DEVICES WILL THEN HAVE THE ABILITY TO OVER |
| RIDE THE SYSTEM IN ANY PARTICULAR AREA WHICH THE |
| CIRCUIT/SWITCH IS DESIGNATED TO. PLEASE KNOW THIS |
| BUILDING IN SEVERAL SECTIONS WILL BE OCCUPIED OUT OF |
| THE NORMAL BUSINESS HOURS WHICH ARE SET UP AND WILL |
| CAUSE DARKNESS EACH HOUR EVEN WHEN OCCUPIED. PLEASE SEE |
| SPECS SHEETS AS SUBMITTED SPEAK OF THE INCLUSION OF AN |
| OCCUPANT SENSOR TYPE DEVICE TO ALLEVIATE THIS. |
| (UNINTENDED BLACK-OUTS). PLEASE SEE AREAS LIKE THE |
| LIBRARY, COMMISSIONS CHAMBERS, OFFICE DESIGNATED FOR |
| POLICE, AND OTHER AREAS. |
| PLEASE SEE THE CODE ON THE OTHER HAND FOR ALL AREAS |
| WHICH DURING NORMAL BUSINESS HOURS WHICH WILL REQUIRE |
| ROOMS TO BE OFF. PLEASE SEE 13-415.1.ABC.1.2, FOR ALL |
| ROOMS CONTAINING FLOOR TO CEILING HEIGHT PARTITIONS |
| WHICH WILL REQUIRED SEPARATE CONTROL. PLEASE SEE AS |
| SHOWN ON PLANS, THESE ROOMS WILL COME "ON" AT THE SET |
| BUSINESS HOUR TIMES AND WILL REMAIN ON UNTIL AFTER THE |
| "ONE HOUR SWEEP" AFTER THE NORMAL OPERATIONAL TIMES |
| HAVE PASSED. |
| PLEASE SEE CLOSETS, OFFICES, STORAGE AREAS ETC. THERE |
| ARE FAR TOO NUMEROUS ROOMS TO LIST. |
| PLEASE SEE THERE ARE MANY ROOMS ON PLANS WHICH DO |
| INDICATE "OC" TYPE DEVICES; HOWEVER THERE IS NOT DETAIL |
| ON THE LIGHTING CONTROL RISER HOW THESE WILL BE |
| CONNECTED OR TIED IN. |
| PLEASE SEE BATHROOMS ETC. |
| PLEASE KNOW THIS TYPE OF DEVICE WILL WORK IN MANY AREAS |
| IN THIS BUILDING; HOWEVER THERE ARE AREAS WHICH WILL |
| NOT MEET CODE OR THE INTENT IN SEPARATE SPACES. PLEASE |
| KNOW AT THIS TIME, AS SHOWN THERE ARE SEVERAL ITEMS |
| WHICH WILL BE REQUIRED TO BE ADJUSTED. PLEASE ALSO |
| OBTAIN A LETTER FROM THE "SENTRY SWITCH" MANUFACTURE |
| WHICH PERMITS THIS TYPE OF DEVICE TO BE USED WITH THE |
| LUTRON GRAFIK PANEL. |
| 110.3, 90.7 NEC. |
| |
| 9) NOTE: OK/NO, PLEASE SEE COORDINATION OF NUMERICAL |
| IDENTIFICATION SEEMS TO BE BETTER; HOWEVER PLEASE SEE |
| SEVERAL AREAS AND ROOM HAVE THEIR DESIGNATION COVERED |
| BY A DEVICE, FIXTURE OR SOME OTHER ITEM. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE THERE ARE SEVERAL ROOM NUMERICAL |
| DESIGNATIONS ON CALCULATIONS WHICH COULD NOT BE LOCATED |
| ON PLANS. PLEASE SEE GARAGE PLANS. |
| PLEASE SEE SOME WHERE THE ROOM DESIGNATION IS THERE |
| HOWEVER IT SEEMS TO BE VERY LIGHT IN COLOR AND CAN NOT |
| BE EASILY READ. PLEASE SEE OTHER AREAS WHICH THE |
| FIXTURE DESIGNATION COVERS THE ROOM IDENTIFICATION OR |
| VICE VERSA, THE FIXTURE TYPE COULD NOT BE SEEN DUE TO |
| THE OVER LAY OF THE NUMERICAL DESIGNATION. |
| PLEASE COORDINATE. A1-116-2-1.610 ETC |
| FBC ADMIN SECTION 106.1.2, 106.1.3 |
| |
| 10) NOTE: OK, HOWEVER PLEASE KNOW BASED ON FURTHER |
| COMMENTS, ADJUSTMENTS IN FIXTURE TYPES AND DESIGNATIONS |
| WILL BE NEEDED. |
| |
| 11) NOTE:NO, PLEASE SEE THERE ARE SEVERAL ROOMS WHICH |
| STILL DO NOT INDICATE A BATTERY BACK UP FIXTURE OF SOME |
| SORT WHICH WILL BE REQUIRED. |
| FIRE PUMP ROOMS, MAIN ELECTRICAL ROOM, MAIN MECHANICAL |
| ROOM, THE MAIN MECHANICAL ROOM ELECTRICAL ROOM, |
| ELEVATOR EQUIPMENT ROOM. ETC. |
| PLEASE ALSO SEE NEW NOTES FOR ROOF TOP/ELEVATOR |
| EQUIPMENT ROOM AND OUTSIDE AREA TO STAIR TWO. PLEASE |
| ALSO SEE GARAGE STAIR TOWERS WILL ALSO BE REQUIRED TO |
| CONTAIN MINIMUM BATTERY BACK UP FOR FIXTURES AS OTHER |
| STAIR TOWERS IN MAIN BUILDING ARE DONE. |
| ** PLEASE ALSO SEE FIRE REVIEW COMMENTS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE THAT BATTERY BACK UP FIXTURES OF SOME TYPE |
| WILL BE REQUIRED FOR THE FOLLOWING LOCATIONS. SOME ARE |
| SHOWN ALREADY, HOWEVER NOT ALL. THE MAIN ELECTRICAL |
| ROOM, THE FIRE COMMAND CENTER, BOTH FIRE PUMP ROOMS, |
| ELEVATOR EQUIPMENT ROOM, AND AT THE LOCATION OF THE |
| ROOF TOP GENERATOR WILL ALL REQUIRE THIS. PLEASE SEE |
| THAT ALL STAIR TOWERS AND EGRESS PATHS SHALL ALSO |
| INCLUDE SOME SORT OF BATTERY BACK UP FIXTURE. THERE ARE |
| MANY LOCATIONS WHICH INCLUDE THIS; HOWEVER AS SOME OF |
| THE FIXTURE INFORMATION IS NOT CLEAR AT THIS TIME THIS |
| CAN NOT BE VERIFIED. THIS BUILDING IS EXPECTED TO BE |
| OCCUPIED IN THE TIME OF POWER OUTAGES AND IN THE EVENT |
| OF THE TRIPPING OF A SINGLE MEANS OF OVER CURRENT |
| PROTECTION (EMSB1) OR GEN MAIN, THIS WILL PLACE MANY |
| AREAS IN COMPLETE DARKNESS WHICH IS NOT PERMITTED. NEC |
| 700.12E, 700.16, LS 101 7.9. |
| |
| 12) NOTE: OK. |
| |
| 13) NOTE: OK. |
| |
| 14) NOTE: NO, PLEASE SEE COMMENTS WITH RESPECT TO STAIR |
| TOWERS IN GARAGE AND OTHER ROOMS WITH THESE |
| DESIGNATIONS WHICH MAY BE CHANGED OR ADJUSTED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE FIXTURE "E", PLEASE SEE IT APPEARS TO BE |
| BATTERY BACK UP, BUT NOT ENOUGH INFORMATION IS |
| PROVIDED. PLEASE SEE FIXTURES, Z,ETC. |
| |
| 15) NOTE: OK. |
| |
| 16) NOTE: NO, PLEASE SEE RESPONSE LETTER MENTIONS THIS |
| IS TO BE DONE BY THE STRUCTURAL ENGINEER/DESIGNER OF |
| RECORD HOWEVER COULD NOT LOCATED ANY DETAIL FOR THIS ON |
| THE S SHEETS. PLEASE SEE THE SAME DETAIL FOR GROUND |
| LEVEL POLES IS BEING USED FOR ROOF TOP MOUNTING? PLEASE |
| SEE NEW NOTES WITH RESPECT TO THE S SHEETS AND TITLE |
| BLOCKS MISSING AND OTHER NOT CONTAIN ANY CERTIFICATE OF |
| AUTHORIZATION NUMBER AS REQUIRED. SEE NEW ELECTRICAL |
| NOTES. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE PROVIDE ALL MINIMUM WIND LOADING FOR SITE |
| LIGHTING LIGHT POLES, AND THAT OF THE POLES ON GARAGE |
| ROOF STRUCTURE. PLEASE KNOW A DETAIL ON HOW THESE WILL |
| BE ATTACHED ON PARKING DECK OF THE GARAGE AND POLE |
| DETAIL FOR GROUND MOUNTED/BURIED POLES WILL BE |
| REQUIRED. PLEASE KNOW ALL SHOW MEET THE FBC 140MPH |
| (3SEC GUST) 120MPH SUSTAINED. |
| THE STRUCTURAL CALCULATIONS WILL BE REVIEWED BY THE |
| BUILDING PLAN REVIEWER. |
| FBC 106.1.2 ADMIN SECT. |
| |
| 17) NOTE: OK. |
| |
| 18) NOTE: OK. |
| |
| 19) NOTE:NO, THIS IS STILL UNCLEAR HOW THE SHORTER |
| LENGTHS OF CONDUCTORS OUT TO FIXTURES ACTUALLY CONTAIN |
| A HIGHER VOLTAGE DROP. |
| PLEASE SEE OTHER COMMENTS ON THE FOLLOWING NOTE #20. |
| |
| ** PREVIOUS REVIEW NOTE** |
| PLEASE PROVIDE THE VOLTAGE DROP ON THIS SAME CIRCUIT AS |
| NOTED ABOVE IN NOTE # 18, PLEASE SEE FIXTURE SA |
| INDICATE #8'S, AND YET SB WHICH CONTAIN A LONGER RUN |
| AND MORE FIXTURES ONLY INCREASE UP TO A #10 AWG. PLEASE |
| SEE FBC 13-413.1.ABC.1.2. |
| |
| 20) NOTE:NO, COULD NOT LOCATE ANY FOR BRANCH |
| CIRCUITING. ONLY LOCATED THE FEEDERS ON RISER. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE PROVIDE A WORST CASE FOR BOTH FEEDER AND BRANCH |
| CIRCUIT. |
| 13-413.1ABC.1. |
| IT IS NOTEDTHAT ON MANY OF THE PANEL SCHEDULES A VD % |
| IS ALREADY SHOWN, HOWEVER PLEASE BE SURE TO INDICATE |
| THE ABOVE. (CAN BE DONE ON A SIMPLE TYPICAL TABLE). FBC |
| 106.1.2. |
| |
| 21) NOTE: NO, SAME NOTE. PLEASE SEE THE FS SHEETS STILL |
| INDICATE ELECTRICAL FIRE PUMPS ALONG WITH DIFFERENT |
| SIZES OF EQUIPMENT THAN THAT SUBMITTED IN THE |
| ELECTRICAL SUBMITTAL BOOKS. PLEASE SEE DIFFERENT |
| MANUFACTURE, ETC. |
| PLEASE SEE THAT BASED ON THE COMMENTARY PROVIDED FOR |
| FUEL USAGE, THE FUEL FOR ONE APPEARS TO BE OK, HOWEVER |
| THE OTHER (110HP) DOES NOT MEET THE MINIMUM LEVEL OF |
| FUEL REQUIRED. PLEASE SEE AS TWO DIFFERENT SIZE PUMPS |
| ARE SUBMITTED, I AM UNABLE TO REVIEW WHICH THE ONE FOR |
| INSTALLATION AT THIS TIME. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE THE 100% FIRE SPRINKLER PLANS SUBMITTED DO |
| NOT CORRELATE WITH THE FA OR ELECTRICAL PLANS SUBMITTED |
| WITH RESPECT TO THE FIRE PUMPS. PLEASE SEE THE FS |
| SHEETS WHICH INDICATE ELECTRIC, ELECTRICAL/ DIESEL AND |
| DIESEL. PLEASE SEE THE ELECTRICAL PLANS AND THE |
| MANUFACTURE SPECS/CUT SHEETS SUBMITTED ONLY INDICATE |
| DIESEL. |
| PLEASE SEE THE MINIMUM FUEL TANK SIZE SHALL BE |
| SUFFICIENT FOR A MINIMUM OF 8HRS AT 100% LOADS. IF |
| ELECTRICAL AND BEING DRIVEN BY THE BACK UP POWER OF AN |
| EMERGENCY GENERATOR, THE ON-SITE FUEL SUPPLY SHALL BE |
| BASED ON THE 100% LOAD OF THE FIRE PUMP AND ALL OTHER |
| LEGAL AND EMERGENCY STAND-BY LOADS AT 100% FOR TIMES |
| REQUIRED. |
| PLEASE SEE 2002 NFPA-110, TEXT EXTRACTED FORM THE |
| CODE: |
| 9.6.2.2 THE FUEL SUPPLY CAPACITY SHALL BE SUFFICIENT |
| TO PROVIDE 8 HOURS OF FIRE PUMP OPERATION AT 100 |
| PERCENT OF THE RATED PUMP CAPACITY IN ADDITION TO THE |
| SUPPLY REQUIRED FOR OTHER DEMANDS. |
| PLEASE SEE NFPA-20 2003 IF DIESEL DRIVEN AND THE SAME |
| AMOUNT OF FUEL REQUIRED WHICH EQUALS 1GAL PER HP PER |
| HOUR PLUS 5% FOR SUMP AND 5% FOR EXPANSION. PLEASE SEE |
| THE FOLLOWING THE CODE. |
| 11.4.3.1 FUEL SUPPLY TANK(S) SHALL HAVE A CAPACITY AT |
| LEAST EQUAL TO 5.07 L PER KW (1 GAL PER HP), PLUS 5 |
| PERCENT VOLUME FOR EXPANSION AND 5 PERCENT VOLUME FOR |
| SUMP AND THE COMMENTARY SECTION AS FOLLOWS, A.11.4.3 |
| THE QUANTITY 5.07 L PER KW (1 GAL PER HP) IS EQUIVALENT |
| TO 0.634 L PER KW (1 PINT PER HP) PER HOUR FOR 8 |
| HOURS. WHERE PROMPT REPLENISHMENT OF FUEL SUPPLY IS |
| UNLIKELY, A RESERVE SUPPLY SHOULD BE PROVIDED ALONG |
| WITH FACILITIES FOR TRANSFER TO THE MAIN TANKS. |
| |
| 22) NOTE: OK. |
| |
| 23) NOTE: OK/NO, PLEASE SEE AS SOME AREAS ARE NOT CLEAR |
| UNABLE TO VERIFY ANY GFI NOTATION. PLEASE SEE SOME ARE |
| SHOWN WITH THE GFI IDENTIFICATION AND IF THE SYMBOLS |
| WERE A LITTLE MORE CLEAR THE SYMBOL LEGEND ON E0.10 MAY |
| BE IF USE. |
| PLEASE ALSO SEE SHEET E1.-1.2 WHICH SHOULD BE A SECTION |
| OF THE BUILDING WHICH WOULD BE LARGER IN SIZE. IT SEEMS |
| SOMETHING WITH THE PRINTING OF SHEET CAUSED SHEET TO BE |
| MUCH SMALLER. PLEASE SEE KITCHEN AREAS WHICH ARE |
| LOCATED ON THIS SHEET COULD NOT BE VERIFIED AT THIS |
| TIME. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE NEC 210.8B3 FOR ALL RECEPTACLES IN KITCHENS |
| IN OTHER THAN DWELLING UNITS. PLEASE SEE THIS WOULD BE |
| REQUIRED FOR CAFE/ KITCHENETTE AREAS AS SHOWN ON |
| PLANS. |
| |
| 24) NOTE: OK. |
| |
| 25) NOTE: NO, PLEASE SEE PHOTO-METRICS ARE CONFUSING. |
| PLEASE SEE THE GARAGE STAIRS SEEM TO NOW BE SHOWN, |
| HOWEVER THERE IS NO SPECIFIED UNDER NORMAL OR UNDER |
| EMERGENCY. PLEASE SEE DESIGNATIONS ON ALL OTHER STAIRS |
| AND LABELING OF AREAS DOES NOT CORRELATE WITH ACTUAL |
| PLANS AND STAIR TOWERS AS SHOWN. PLEASE KNOW THIS |
| COMMENT IS NOT JUST FOR GARAGE STAIRS AS PREVIOUS |
| COMMENT WAS TO ADDRESS ALL PHOTO-METRICS. PLEASE SEE |
| MISSING STAIR 13, MEZZ STAIRS, PLEASE SEE OTHER STAIR |
| DESIGNATIONS NOT LABELED ETC. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE MISSING THE PHOTO-METRICS FOR THE GARAGE |
| STAIR TOWERS. PLEASE SEE THE PHOTO-METRICS AS SUBMITTED |
| ARE A LITTLE CONFUSING. PLEASE PREVIOUS COMMENTS ONLY |
| REQUESTED EGRESS PATHS OF LEVELS SURFACES/ CORRIDORS |
| AND EGRESS PATHS THAT OF THE STAIR TOWERS. PLEASE SEE |
| THERE MUCH INFORMATION SUBMITTED GIVING FIXTURE |
| DESIGNATIONS AND ROOM BY ROOM LEVELS? PLEASE PROVIDE |
| THE EGRESS PATHS INFORMATION INDICATING THE CLEAR |
| NORMAL AND EMERGENCY LEVELS AS NEEDED AND REQUIRED BY |
| CODE. |
| PLEASE PROVIDE A BREAKDOWN OF THE NORMAL AND EMERGENCY |
| AVERAGE. PLEASE SEE THAT INFORMATION OF WHICH IS |
| SUPPLIED ON EACH "OVER-ALL" SHEET DOES NOT SUPPLY THE |
| INFORMATION AS NEEDED. |
| PLEASE SEE 9-4.1 WHICH INDICATES IN TITLE BLOCK, |
| EMERGENCY/ NORMAL? |
| |
| 26) NOTE: OK. |
| |
| 27) NOTE: NO, PLEASE SEE SOME ARE STILL SHOWING THIS |
| DESIGNATION. |
| |
| ** PREVIOUS REVIEW NOTE** |
| PLEASE CLARIFY GARAGE LIGHTING WHICH SHOWS "ON" NEXT |
| TO SOME FIXTURES ON PLANS. (RAMP AREAS) THIS IS UNCLEAR |
| AT THIS TIME WHAT IS MEANT BY THIS. |
| FBC 106.1.2 ADMIN SECTION |
| |
| 28) NOTE: OK. |
| |
| 29) NOTE: OK. |
| |
| 30) NOTE: OK/NO, PLEASE SEE ROOM LAYOUT DESIGNATION ON |
| SHEET E1-1.3 INDICATES SHEET E4-1.0, WHEN IT SHOULD BE |
| E- 1.1 |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE MISSING THE ELECTRICAL ROOM FOR 1HMGB AND |
| 1HMGA ON THE LAYOUTS FOR THE ELECTRICAL ROOMS. PLEASE |
| PROVIDE. 106.1.2, |
| NEC 110.26 |
| |
| 31) NOTE: NO/OK, PLEASE SEE THE DOOR SWINGS SEEM TO BE |
| OK, HOWEVER PLEASE SEE NO NOTE FOR PANIC HARDWARE AS |
| REQUIRED COULD BE LOCATED ON PLANS. THIS WILL BE |
| REQUIRED FOR MAIN ELECTRICAL ROOM AND MAIN ELECTRICAL |
| EQUIPMENT FOR MECHANICAL MAIN ELECTRICAL EQUIPMENT |
| ROOMS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE MAIN ELECTRICAL ROOM AND THE MISSING |
| ELECTRICAL ROOM FROM NOTE #30 ABOVE WHICH IS STILL |
| INDICATING DOORS WITH AN "IN-SWING" WHICH IS NOT |
| PERMITTED. PLEASE ALSO BE SURE TO ADD A NOTE WITH |
| RESPECT TO PANIC HARDWARE REQUIRED FOR ALL DOORS AS |
| REQUIRED PER 110.26. (MAIN ELECTRICAL ROOM/ AND ROOM |
| NOTED ON NOTE #30). |
| PLEASE SEE THE DOOR SWINGS WERE NOTED ON ALL OF THE |
| REVIEWS BASED ON THE 50%, 90% AND THIS REVIEW. PLEASE |
| GO OVER ALL PLANS AND DOORS. |
| |
| 32) NOTE: NO, PLEASE SEE SEVERAL OF THESE UNITS ARE |
| BEING SHOWN ON PLANS AT JANITOR CLOSET LOCATIONS, |
| HOWEVER NOT ALL OF THESE ROOMS CONTAIN THESE. PLEASE |
| ALSO SEE SEVERAL KITENETTE AREA WHICH ALSO INCLUDES |
| THESE HOWEVER MANY DO NOT? IN EITHER CASE PLEASE SEE NO |
| SPECS WERE SUBMITTED AND NO DISCONNECTING MEANS FOR ALL |
| UNITS COULD BE LOCATED ON PLANS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS FOR AL |
| THE TANK-LESS WATER HEATER UNITS. THESE MAY ALSO BE |
| LABELED AS INSTA-HOTS. PLEASE SEE MISSING DISCONNECTS |
| AS REQUIRED ON THESE UNITS. THESE COULD NOT BE LOCATED |
| ON PLANS. |
| PLEASE SEE SIZING OF THE OVER CURRENT DEVICES, |
| DISCONNECTS AND ETC SHALL BE BASED ON EACH UNIT. PLEASE |
| SEE 422.31, 110.3, AND 90.7. |
| |
| 33) NOTE:NO, SAME NOTE. PLEASE VERIFY ALL. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE SOME TWH UNITS WHICH ARE SHOWN ON PLANS ARE |
| MISSING THE REQUIRED CIRCUITING. CAN NOT REVIEW FOR |
| COMPLIANCE OF LOAD, CONDUCTOR SIZE, OCP ETC AT THIS |
| TIME. |
| PLEASE COMPLETE. 240.4, 310.16, 408.4, FBC 106.1.2 |
| |
| 34) NOTE: OK. |
| |
| 35) NOTE: OK. |
| |
| 36) NOTE: OK |
| |
| 37) NOTE: OK. |
| |
| 38) NOTE: OK. |
| |
| 39) NOTE: OK. |
| |
| 40) NOTE: OK. |
| |
| 41) NOTE: OK, HOWEVER SEE NOTE FOR CORRELATION OF ROOM |
| A5.107 |
| |
| 42) NOTE: OK. |
| |
| 43) NOTE: NO? SAME AS SHOWN. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE "SHADED" AREAS ON MEZZANINE LEVEL PLANS |
| E-1.1.4, PLEASE CLARIFY |
| 106.1.2 FBC ADMIN SECTION. |
| |
| 44) NOTE: OK. |
| |
| 45) NOTE: OK. |
| |
| 45) NOTE: NO/OK, PLEASE SEE WALL AS LOCATED, HOWEVER |
| SEPARATE LIGHTING CONTROLS FOR SEPARATE SPACES AS |
| REQUIRED COULD NOT BE LOCATED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE WHAT APPEARS TO BE MISSING WALLS, DOORS |
| SEPARATION E-1-1.2, LIBRARY/MUSEUM/ STORE? PLEASE SHOW |
| AS THE REQUIREMENTS FOR CHAPTER 13 CAN NOT VERIFIED FOR |
| CONTROL OF LIGHTING. LIGHTING OF SOME TYPE INCLUDING |
| EXIT/EMERGENCY LIGHTS ARE STILL REQUIRED IN SPACE, EVEN |
| IF FOR FUTURE BUILD OUT. PLEASE SEE LS 101 7.8, 7.9 AND |
| POSSIBLE COMMENTS FROM FIRE MARSHAL?S OFFICE. |
| 13-415.1.ABC.1.ABC.1.1, .1.2, .1.3 |
| |
| 46) NOTE: OK. |
| |
| 47) NOTE: NO/OK, SOME OF THESE WERE DONE BY THE CHANGES |
| IN THE UNDER GROUND TO OTHER SECTIONS OF BUILDING, |
| HOWEVER NOT DETAIL FOR THE ENCASED FEEDERS FROM |
| GENERATOR COULD BE LOCATED. PLANS MENTIONS TO SEE |
| ARCHITECTURAL PLANS; HOWEVER NO INFORMATION FOR WHICH |
| SHEET OR DETAIL THIS IS COULD BE FOUND. PLEASE PROVIDE |
| THE DETAIL. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE PROVIDE AN ELEVATION/DETAIL FOR ALL ELECTRICAL |
| CONDUITS BEING RUN FROM GARAGE TO THE MAIN BUILDING. |
| THIS BUILDING IS BEING CONSIDERED "ATTACHED" AND ONE " |
| BUILDING" BY DEFINITION, HOWEVER DUE THE UNDERSTANDING |
| OF MANY OF THE CONDUITS ARE NOW BEING INSTALLED IN THE |
| SLAB OR UNDER GROUND AND THE AMOUNT OF OTHER CONDUITS, |
| PIPING, BEING INSTALLED IN THIS SAME AREA, IT IS OF |
| CONCERN FOR THE SPACE REQUIREMENTS FOR BUNDLING OF |
| CONDUITS, DE-RATING OF CONDUCTOR AMPACITIES. ETC. (THIS |
| CAN BE A DETAIL LIKE A DUCT-BANK DETAIL) |
| FBC 106.1.2, 310.16, 300.8, 300.10, 310.10, 310.15, |
| 310.16, 300.17 ETC. |
| THERE ARE MANY SECTIONS WHICH COULD BE REFERENCED. |
| PLEASE ALSO SEE COMMENT WITH RESPECT TO WIRING METHODS |
| OF EMERGENCY FEEDERS ETC. |
| |
| 48) NOTE: OK, HOWEVER SEE NEW NOTES DUE TOP HAND DRAWN |
| CHANGES MADE TO PLANS. |
| |
| 49) NOTE: NO, PLEASE SEE THE RATING OF THIS ROOM IS |
| STILL REQUIRED. THIS COMMENT WILL BE IN REVIEWS FROM |
| MULTIPLE REVIEWERS AND AS THIS WILL CHANGE THE BACK |
| GROUND OF WALL DETAIL PLEASE ADDRESS AT THIS TIME. |
| |
| ** PREVIOUS REVIEW NOTE** |
| PLEASE KNOW AS NO INFORMATION FOR THE IT ROOM EQUIPMENT |
| IS BEING SUBMITTED WITH THIS RECORD SET OF PLANS, |
| PLEASE PLACE NOTE AND CLOUD ON 4TH FLOOR POWER PLANS |
| THAT ALL ELECTRICAL EQUIPMENT, UPS, SERVER EQUIPMENT |
| ETC IN THE IT ROOM SHALL BE UNDER A SEPARATE PERMIT, |
| PLANS, AND FEES BASED ON THE EQUIPMENT BEING INSTALLED |
| IN THIS ROOM. REVIEW FOR CODE COMPLIANCE FOR THIS ROOM |
| CAN NOT BE COMPLETED AT THIS TIME. THE REQUIREMENTS FOR |
| THE CONSTRUCTION OF THIS ROOM IS REQUIRED AT THIS TIME, |
| INCLUDING THE MINIMUM 1HR RATING, THE FIRE DAMPERS ETC |
| (IF APPLICABLE) AND THE SHUT DOWN OF AN AND ALL A/C |
| EQUIPMENT. |
| NEC 645, NFPA-75 |
| |
| 50) NOTE: OK. |
| |
| 51) NOTE: OK. |
| |
| 52) NOTE: OK. |
| |
| 53) NOTE:OK/NO, THIS NOTE WILL REMAIN AS IT IS THIS |
| REVIEWERS UNDERSTANDING THAT THERE WILL BE COMMENTS |
| FROM OTHER TRADES WHICH WILL SUBSTANTIALLY AFFECT |
| BACKGROUNDS AND LAYOUTS OF SAID PLANS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE COORDINATE ALL OVER-LAYS AND LAYOUTS FOR |
| ELECTRICAL, MECHANICAL, PLUMBING, BUILDING AND ALL |
| OTHER TRADE PLANS. PLEASE KNOW THE ELECTRICAL 100% |
| PLANS DO NOT SHOW THE SAME ELECTRICAL ROOMS AND |
| EQUIPMENT AS THE 100% MECHANICAL PLANS, PLUMBING OR |
| BUILDING PLANS ALONG WITH OTHER SHEETS FROM OTHER |
| TRADES. |
| REVIEW OF ALL APPLICABLE ITEMS WILL STILL NEED TO BE |
| DONE AS REQUIREMENTS FOR ELECTRICAL AND OTHER TRADES |
| WILL MOST CONTAIN CLEAR CONFLICTS WHICH MAY OR MAY NOT |
| BE PERMITTED. |
| 110.26, 240.24 NEC. |
| FBC 106.3.5.1.1 ADMIN SECTION FOR ALL TRADES FOR |
| COMMERCIAL PLANS. |
| |
| 54) NOTE:NO, SAME NOTE. PLEASE SEE PLANS IN SEVERAL |
| LOCATIONS 6-1.0,1-6.3,5-1.1 ETC INDICATE 800KW AND |
| SUBMITTALS ARE 900KW. |
| PLEASE ALSO SEE SHEET WHICH STILL INDICATES ONLY 5 |
| GALLON SPILL CONTAINMENT. THIS MAY BE PART OF THE FIRE |
| OR MECHANICAL REVIEW NOTES, IF NOT PLEASE SEE THIS |
| NEEDS TO BE VERIFIED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE CORRELATE THE PLANS WITH THE MANUFACTURE |
| SPECS/CUT SHEETS FOR THE GENERATOR WHICH IS BEING |
| SUBMITTED AS A LARGER UNIT IN THE SPEC BOOK AS SHOWN ON |
| PLANS. THIS WILL AFFECT THE FUEL SUPPLY, AND THE FUEL |
| LINE SUPPLY FOR THE PROPOSED NATURAL GAS LINE. 90.7, |
| 110.3, |
| FBC 106.1.2 |
| |
| 55) NOTE: OK. |
| |
| 56) NOTE: OK. |
| |
| 57) NOTE:OK/NO, PLEASE SEE PREVIOUS COMMENT WITH |
| RESPECT TO HOW THIS WILL ACTUALLY BE DESIGNED AND |
| INSTALLED. THIS COMMENT WILL REMAIN AT THIS TIME AS A |
| REMINDER. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE SOME BATHROOMS CONTAIN OC SENSORS AND MANY |
| DO NOT, PLEASE EXPLAIN AND PLEASE SEE OTHER COMMENTS |
| FOR TYPE OF DEVICES WHICH WILL BE REQUIRED. |
| 13-415.1.ABC.1.2 |
| |
| 58) NOTE: NO, PLEASE SEE MOST WERE DONE, HOWEVER PLEASE |
| SEE 2-2.2, 2-3.1,2-4.2 AND ANY OTHER LARGER BATHROOMS |
| OTHER THAN A SINGLE POINT OF USE OCCUPIED ROOM. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE KNOW SOME SORT OF BATTERY BACK UP FIXTURE WILL |
| BE REQUIRED IN THE LARGER BATHROOMS (ROOM OTHER THAN |
| SINGLE POINT OF USE). |
| PLEASE SEE LS 101 7.8., 7.9 |
| THIS WAS DISCUSSED WITH THE FIRE MARSHAL CHIEF AND WILL |
| BE REQUIRED BOTH BY THIS OFFICE AND THE FIRE MARSHAL'S |
| OFFICE IN THE INTEREST OF LIFE SAFETY AND CODE AS |
| REFLECT. |
| |
| 59) NOTE: OK. |
| |
| 60) NOTE: OK. |
| |
| 61) NOTE: NO, PLEASE SEE RESPONSE MENTIONS MINIMUM |
| LIGHTING REQUIRED FOR EGRESS, HOWEVER PLEASE KNOW THE |
| AREA OF THE LOBBY AFTER HOURS WOULD REQUIRE OVER RIDE |
| FOR NORMAL LIGHTING. ONLY WOULD THEY NEED THESE |
| FIXTURES TO BE BATTERY BACK UP FOR AN EMERGENCY. THIS |
| WAS DISCUSSED WITH THE DESIGNER, HOWEVER THE NUMBER OF |
| FIXTURES EXCEED ANY REASONABLE AMOUNT PERMITTED TO BE |
| LEFT ON FOR THE EXCEPTIONS AS PERMITTED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE THERE ARE SOME LOCATIONS ON PLANS WHICH ARE |
| SHOWING "NL'S" (NIGHT LIGHTS) BEING PART OF A PERMANENT |
| ON SCENARIO; HOWEVER THE NUMBERS OF FIXTURES BEING |
| PROPOSED TO REMAIN ON AS NIGHT LIGHTS ARE OVER WHAT IS |
| BEING CONSIDERED AS NORMAL. PLEASE KNOW THIS CAN BE |
| GONE OVER, HOWEVER PLEASE SEE SOME AREAS WHERE THERE |
| ARE 10-20PLUS LIGHTS BEING LEFT ON. |
| THE INTENT OF CHAPTER 13 AND ALSO THE INTEREST OF LIFE |
| SAFETY SHOULD BE CONSIDERED. PLEASE CALL TO OVER. SEE |
| SHEET E2-1.2 FOR EXAMPLE IN LOBBY AREA. |
| |
| 62) NOTE:NO/OK, PROJECT MANUALS ARE TO BE REVIEWED |
| FOR ALL OF THESE ITEMS AND DOCUMENTATION WILL BE |
| REQUIRED BEFORE FINAL. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE NFPA-20 11.3, 11.3.2, 11.3.2.3 AND FLORIDA |
| FIRE PREVENTION CODE , NFPA-1 7-4FOR OTHER REQUIREMENTS |
| FOR FIRE PUMPS AND ROOMS IN WHICH THEY ARE LOCATED. |
| PLEASE ALSO SEE 11.4.6.2 FUEL PIPING SHALL NOT BE |
| GALVANIZED STEEL OR COPPER. |
| PLEASE KNOW AS PART OF THE COMPLETED TESTING AND |
| ACCEPTANCE AS REQUIRED IN CHAPTER 14, DOCUMENTATION FOR |
| TESTING FOR FIRE PUMP ON A WEEKLY BASIS IS REQUIRED TO |
| THE OWNER OF RECORD.CODE TEXT FROM NFPA-20: 11.6.1.1 |
| ENGINES SHALL BE STARTED NO LESS THAN ONCE A WEEK AND |
| RUN FOR NO LESS THAN 30 MINUTES TO ATTAIN NORMAL |
| RUNNING TEMPERATURE. |
| |
| 63) NOTE:NO, RESPONSE MENTIONS INFORMATION GIVEN TO |
| ARCHITECT AND STRUCTURAL ENGINNER WHICH IS OK, HOWEVER |
| COULD NOT LOCATE ANY INFORMATION OR DETAIL FOR THIS. |
| THIS UNIT AND ITS SIZE IS BEING PLACED ON THE ROOF OF |
| THE GARAGE AND IT IS OF THE UTMOST IMPORTANCE THAT THE |
| INFORMATION IS PROVIDED A THIS TIME AS IT MAY AFFECT |
| PLANS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE NFPA-110 CHAPTER 7 FOR THE INSTALLATION OF |
| THE GENERATOR. PLEASE SEE 7.4 AND 7.5, PROVIDE DETAIL |
| FOR MOUNTING OF UNIT TO ALLEVIATE ANY INTEGRITY |
| INTERFERENCE OF THE STRUCTURE. |
| |
| 64) NOTE: NO, PLEASE SEE THE SAME SPECS WHICH CONTAIN |
| HAND WRITTEN INFORMATION WAS SUBMITTED BACK FOR REVIEW. |
| PLEASE KNOW, THIS SYSTEM AS SUBMITTED IS NOT ACCEPTABLE |
| TO THIS AHJ WITHOUT THE FAIL SAFE OPERATION TO |
| COMPLETELY PREVENT INADVERTENT SIMULTANEOUS OPERATION. |
| PLEASE KNOW THERE ARE NUMEROUS OF THE TYPES OF SYSTEMS |
| ON THE MARKET WHICH WILL PERMIT BOTH SIDE BEING ON AT |
| THE SAME TIME. PLEASE KNOW AS PER KNOWLEDGE OF THIS |
| REVIEWER MR. MARK ODE FROM UL WAS IN DISCUSSION WITH |
| SAID COMPANY TO START WITH THE PROCEEDINGS TO HAVE |
| THEIR EQUIPMENT LISTED AS TRANSFER EQUIPMENT PER UL |
| 1081. PLEASE KNOW AT THIS TIME, EITHER PROVIDE THE |
| NEEDED INFORMATION OR CHANGE EQUIPMENT TO AN ACCEPT |
| UNIT WHICH IS LISTED BY A NRTL. (NATIONALLY RECOGNIZED |
| TESTING LABORATORY). |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SUBMIT THE SPEC/CUT SHEET FOR THE PROPOSED MTS. |
| THE "KIRK KEY" AS SHOWN AND HAND WRITTEN ON SPECS IS |
| NOT ACCEPTED AT THIS TIME. THERE ARE MANY OF THESE |
| SYSTEMS ON THE MARKET WHICH WILL PERMIT THE POWER FROM |
| TWO SOURCES AT ONCE WHICH IS STRICTLY PROHIBITED. |
| PLEASE SEE 700.6, 701.7, 110.3, AND 90.7 CAN NOT VERIFY |
| AT THIS TIME. PLEASE ALSO SEE THE FOLLOWING COMMENT. |
| |
| 65) NOTE: NO/OK, PLEASE SEE SPECS SUBMITTED INDICATE |
| 4-POLE UNITS, HOWEVER EACH ATS ON RISER WHEN SUBMITTED |
| FOR THE 90% REVIEW CONTAINED DESIGNATION NEXT TO EACH |
| UNIT TO BE 4-POLE. PLEASE PLACE THIS MEANS OF |
| IDENTIFICATION/DESIGNATION ON RISER AT THIS TIME TO |
| AVOID ANY CONFUSION OF WHAT TYPE OF UNITS ARE TO BE |
| INSTALLED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE RISER AND PLANS WERE REVISED FROM THE 50% |
| AND 90% PLANS CHANGING ALL ATS UNITS TO 3-POLE UNITS. |
| PLEASE SEE ALTHOUGH GF PROTECTION IS NOT REQUIRED ON |
| THE EMERGENCY SIDE OF THE EMERGENCY SYSTEM AND LEGALLY |
| REQUIRED SYSTEMS, PROPER GROUND FAULT SENSING IS |
| REQUIRED. PLEASE KNOW DOCUMENTATION FROM MORE THAN ONE |
| MANUFACTURE WAS SENT TO THE ENGINEER PRIOR TO THE |
| REVIEW WHEN THE PLANS WERE SUBMITTED ON THE 7TH OF NOV. |
| PLEASE SEE NFPA-110 6.2.15** ISOLATION OF NEUTRAL |
| CONDUCTORS. PROVISIONS SHALL BE INCLUDED FOR ENSURING |
| CONTINUITY, TRANSFER, AND ISOLATION OF THE PRIMARY AND |
| THE EPS NEUTRAL CONDUCTORS WHEREVER THEY ARE SEPARATELY |
| GROUNDED TO ACHIEVE GROUND-FAULT SENSING. |
| PLEASE SEE AN ATTACHED BRIEF EXPLANATION FROM"ASCO" |
| WHITE PAPER: WHERE GROUND FAULT PROTECTION IS TRIGGERED |
| BY THE CODE AND AN ALTERNATE POWER SUPPLY IS INCLUDED, |
| SWITCHING OF THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT |
| SHOWN ABOVE ILLUSTRATES SUCH A CIRCUMSTANCE. THE |
| SERVICE IS LARGER THAN 1,000 AMPS. CONSEQUENTLY, GROUND |
| FAULT PROTECTION IS REQUIRED AT THE MAIN SERVICE |
| DISCONNECT AT A MINIMUM. IF IT IS INSTALLED THERE AND |
| THE GENERATOR NEUTRAL GROUNDING WAS THROUGH A SOLID |
| CONNECTION TO THE MAIN SERVICE NEUTRAL, A GROUND FAULT |
| WHEN THE GENERATOR IS FEEDING THE LOAD WILL CAUSE THE |
| MAIN SERVICE DISCONNECT TO OPEN. THIS WILL NOT |
| DISCONNECT THE ARCING FAULT FROM THE GENERATOR. |
| COORDINATION IS THUS LOST." |
| PLEASE KNOW BASED ON THE INFORMATION FROM SEVERAL |
| MANUFACTURES AND THE CODE PLEASE ADJUST AS REQUIRED. |
| PLEASE ALSO SEE GENERATOR GROUNDING DETAIL WILL BE |
| REQUIRED TO BE REVISED. |
| PLEASE SEE E5-1.1.18 WHICH NOTES A #3 CONDUCTOR, WHICH |
| WOULD NOT BE LARGE ENOUGH. |
| PLEASE SEE 250.20, 250.30, 250.66, 240.13, 230.95, |
| 700.7D, 700.26 |
| PLEASE SEE THE MTS. |
| |
| 66) NOTE: OK, HOWEVER PLEASE SEE SOME OF THESE ARE |
| BEING SHOWN ATTACHED DIRECTLY TO CIRCUITS WHICH SEEMED |
| TO BE CONTROLLED BY LIGHTING CONTROL SYSTEM OR DEVICES. |
| THE NOTES ON PLANS MENTION TO BE SURE TO CONNECT AHEAD |
| OF ANY CONTROL OR SWITCHING DEVICES HOWEVER PLEASE |
| VERIFY THIS ON THE PLANS AT THIS TIME AS SHOWN. PLEASE |
| SEE THERE ARE STILL SOME EXIT LIGHT FIXTURES ON PLANS |
| WHICH STILL DO NOT SHOW ANY CONNECTION TO LOCAL |
| CIRCUITS E2-3.2,E2-4.2 |
| |
| PLEASE SEE THERE ARE MANY EXIT/EMERGENCY LIGHTS WHICH |
| DO NOT SHOW ANY CONNECTION TO ANY LOCAL CIRCUIT IN |
| ANYWAY. PLANS NOTE THIS AND MANY ARE SHOWN THIS WAY, |
| HOWEVER NOT ALL. PLEASE GO THROUGH PLANS. PLEASE SEE |
| 700.12E WHICH REQUIRES THE BRANCH CIRCUIT FEEDING THE |
| UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT |
| SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED |
| AHEAD OF ANY LOCAL SWITCHES. |
| |
| 67) NOTE:NO, SAME NOTE. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE OVER ALL 3RD FLOOR PLANS, WHICH SEEM TO BE |
| SHOWING LIGHTING OF SOME KIND ON GARAGE PLANS? PLEASE |
| ALSO SEE E2-4.0 |
| FBC 106.1.2 ADMIN SECTION. |
| |
| 68) NOTE: NO, PLEASE SEE THE LOCATION AS SHOWN WOULD |
| NOT BE AN ACCEPTABLE LOCATION. PLEASE THE RUNNING OF |
| CABLES IN THE EGRESS PATH IS NOT PERMITTED IN FRONT OF |
| DOOR WAYS AND ANY OTHER EGRESS PATHS. PERHAPS CONDUITS |
| TO A J-BOX OF SOME TYPE TO THE OUTSIDE WALL ON THE |
| NORTH SIDE OF BUILDING. PLEASE KNOW TRIPPING HAZARDS |
| UNDER THE REQUIREMENTS IN THE CODE FOR TEMPORARY |
| INSTALLATIONS IS STILL NOT PERMITTED. PLEASE SECTIONS |
| AS PREVIOUSLY GIVEN. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE NOTE #2 ON RISER WITH RESPECT TO THE MTS |
| WHICH IS TO PROVIDE FUTURE PROVISIONS FOR POSSIBLE |
| PORTABLE GENERATOR TO RUN THE EMERGENCY SYSTEMS, PLEASE |
| KNOW A DETAIL TO A LOCATION AND HOW THIS CONNECTION |
| WILL BE MADE IS REQUIRED.THE RUNNING OF CORDS, |
| CONDUCTORS ETC SHALL BE PERMITTED TO TRAVEL THROUGH THE |
| ELECTRICAL ROOM DOORS, ON SIDEWALK AREAS OR ANY |
| LOCATIONS PROVIDING A TRIPPING HAZARD OR NOT SECURING |
| LIVE PARTS ETC. |
| PLEASE PROVIDE A DETAIL AS THIS CONNECTION POINT WILL |
| BE SUBSTANTIAL IN NATURE. (J-BOX) ETC ON THE OUTSIDE OF |
| BUILDING ETC. |
| 110.26, 110.27, NEC 527. |
| |
| 69) NOTE: OK. |
| |
| 70) NOTE: OK. |
| |
| 71) NOTE: OK, PLEASE KNOW ALL LOW VOLTAGE WILL NOT BE |
| INCLUDED IN THIS PERMIT. NOTE WILL REMAIN ONLY AS |
| INFORMATION AS TO WHAT WILL BE REQUIRED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE KNOW IF IT IS THE INTENT TO UTILIZE THESE PLANS |
| FOR FUTURE LOW VOLTAGE WORK FOR LOCATIONS OF PHONE, |
| DATE DROP ETC, PLEASE COMPLETE PLANS AS SUBMITTED |
| SHOWING ALL LOCATIONS FOR DROPS.PLEASE SEE MANY AREAS |
| WHICH LOW VOLTAGE DATE/PHONE DROPS WILL BE REQUIRED OR |
| INSTALLED, HOWEVER THESE LOCATIONS ARE NOT BEING SHOWN |
| AT THIS TIME. |
| IF THE LV SCOPE IS PART OF THE PERMITTED PLANS AS |
| SUBMITTED PLEASE REMOVE AND NOTE AS UNDER SEPARATE |
| PERMIT PLANS AND FEES. |
| |
| 72) NOTE: OK. |
| |
| 73) NOTE:OK/NO, PLEASE SEE PREVIOUS NOTE #47, WHERE |
| THE DETAIL FOR THE FEEDERS IN GARAGE WAS NOT PROVIDED. |
| THE DETAIL FOR UNDERGROUND IS OK. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE 700.9D FOR THE FEEDERS FROM THE GENERATOR TO |
| THE EMSB1 AND THE FEEDERS OUT TO SYSTEMS WHICH MAY BE |
| CONSIDERED INSIDE THE BUILDING. PLEASE SEE THE CODE AS |
| THERE ARE WAYS TO MEET THE INSTALLATION OF THESE |
| FEEDERS, HOWEVER PLANS SHALL INDICATE WHICH WILL BE |
| USED. (TYPE OF CABLE, ENCASED IN 2INCHES OF CONCRETE, |
| FULLY SPRINKLED ETC) |
| PLEASE KNOW AS THE REQUIREMENT OF FULLY SPRINKLED IS |
| OFTEN MISTAKEN AS A BUILDING CONTAINING SPRINKLERS. |
| THIS IS NOT THE CASE. PLEASE SEE THE INTENT OF 700.9D |
| FOR THIS HAS ALWAYS BEEN THAT ALL AREAS CONTAINING |
| THESE FEEDERS BE SPRINKLED IF INSTALLED IN OPEN OR |
| ABOVE CEILINGS. PLEASE KNOW A COMMENTARY IN THE 2005 |
| NEC MAKES IS CLEAR WHAT THE INTENT OF THE CODE AND THE |
| FURTHER EXPLANATION IS PROVIDED. |
| |
| 74) NOTE: OK. |
| |
| 75) NOTE: OK.. |
| |
| 76) NOTE: NO, COULD NOT LOCATE. RESPONSE MENTIONS TO |
| SEE SHEETS; HOWEVER THIS WAS REQUESTED FOR RISER TO |
| SHOW THIS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE PROVIDE THE SIZE OF THE CONDUCTOR ON THE |
| GROUNDING ELECTRODE RISER AS PROVIDED. PLEASE SEE THE |
| GROUNDING ELECTRODE DETAIL SHOWS A 4/0'S, HOWEVER |
| PLEASE SEE E5-2.0. |
| 250.50, 250.58 |
| |
| 77) NOTE: NO, PLEASE SEE RESPONSE MENTIONS ALL |
| TERMINATE IN OCP. YES, THIS IS TRUE, HOWEVER AS STATED |
| IN PREVIOUS REVIEW PER 240.21C THE OCP SHALL LIMIT THE |
| LOAD ON CONDUCTORS. |
| PLEASE SEE E5-1.0 WHICH SHOWS A 45KVA TRANSFORMER, WHEN |
| E6-1.0 SHOWS 1/0'S FOR THE TYPICAL 45 KVA TRANSFORMER |
| ON THE SECONDARY SIDE, THIS WOULD MEAN THE OCP WOULD BE |
| LIMITED TO 150A?S. PLEASE SEE 6-1.0 FOR 1LD2 WHICH |
| INDICATES 225A OCP AS THE SECONDARY MCB. PLEASE SEE |
| 6-7.0 1HD WHICH SHOWS 1/0'S ON THE SECONDARY SIDE OF |
| THE FEEDERS. |
| PLEASE ADJUST. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE THE SIZE OF THE CONDUCTORS ON THE SECONDARY |
| SIDE OF ANY TRANSFORMER SHALL BE SIZED AND TERMINATE IN |
| OVER-CURRENT PROTECTION WHICH LIMITS THE LOAD ON THE |
| CONDUCTORS. PLEASE SEE 240.21C, 310.16. PLEASE SEE |
| 1LD2 |
| |
| 78) NOTE: OK. |
| |
| 79) NOTE: NO, PLEASE CLARIFY WHERE CONTINUOUS LOADS AND |
| LARGEST MOTOR LOADS ARE SHOWN AT 125%. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SUBMIT LOAD CALCULATIONS. PLEASE INDICATE AND |
| SHOW ALL CONTINUOUS LOADS AND LARGEST MOTOR LOADS AT |
| 125%. |
| 220.3, 220.10, 220.11, 220.13, 215.3,230.42 ETC |
| |
| 80) NOTE: OK. |
| |
| 81) NOTE:NO, PLEASE KNOW BASED ON THE PREVIOUS NOTES |
| ABOVE WITH RESPECT TO PHOTO-METRICS, THIS COMMENT WILL |
| REMAIN DUE TO POSSIBLE CHANGES IN PLANS. |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE PREVIOUS NOTES WITH RESPECT TO MINIMUM FOOT |
| CANDLES REQUIRED. PLEASE SEE GARAGE SHALL CONTAIN |
| EGRESS PATHS WHICH MEET THIS MINIMUM. BASED ON SOME |
| AREAS SHOWN ON PHOTO-METRICS, IT DOES NOT APPEAR THIS |
| IS MET. |
| PLEASE SEE LIFE SAFETY CODE NFPA-101 2003 7.8.1.3, |
| 7.9.2.2 |
| |
| 82) NOTE: OK. |
| |
| 83) NOTE:NO/OK, PLEASE SEE MOST WERE DONE, HOWEVER |
| PLEASE SEE ROOM A1.507 WHICH SHOWS 75K ON RISER AND 45K |
| ON ROOM PLANS. |
| |
| ** PREVIOUS REVIEW NOTE** |
| PLEASE CORRELATE THE TRANSFORMERS ON THE ELECTRICAL |
| ROOM LAYOUTS AND THE ELECTRICAL RISER. PLEASE SEE THERE |
| ARE MANY WHICH ARE SHOWN AS 15KVA ON ONE SHEET AND |
| 45KVA ON OTHER SHEETS OR 45KVA ON ONE AND 75KAV ON |
| ANOTHER. PLEASE ALSO SEE RISER. |
| PLEASE SEE SOME BELOW AS NOTED, THIS IS ONLY SOME AND |
| IS IN NO WAY ALL POSSIBLE. |
| 1HB, 75KVA ON RISER, 45KVA IN ELECTRICAL ROOM. 2HB, |
| 75KVA ON RISER, 45KAV IN ELECTRICAL ROOM. 1GLA-1GHA, |
| 45K ON RISER, 15K ON ELECTRICAL ROOM PLANS. ETC |
| |
| 84) NOTE: OK, |
| |
| 85) NOTE: NO, PLEASE SEE NOTE NOTES COULD BE LOCATED ON |
| FA SHEETS, IN FACT SHEETS STILL ONLY NOTE NFPA72 FOR |
| LEVELS. |
| PLEASE ADJUST ALL SHEETS AND NOTES ACCORDINGLY AS |
| PREVIOUSLY REQUESTED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE FBC 2004 CHAPTER 11 FOR REQUIREMENTS FOR ADA |
| WITH RESPECT TO HORNS, AND STROBES. THE AUDIBLE LEVELS |
| SHALL BE PER BOTH FBC CHAPTER 11 AND NFPA-72 AS NOTED, |
| HOWEVER THE MORE STRINGENT SHALL APPLY. |
| PLEASE SEE 11-4.28.1, 11-4.28.2 AND 11-4.28.3(4). |
| PLEASE BE SURE THE LEVELS ARE INDICATED ON PLANS. |
| PLEASE KNOW THE LIGHTING CANDELA LEVELS AS REQUIRED IN |
| THE FBC ARE FAR GREATER THAN THAT OF NFPA-72. THE |
| MINIMUM LEVELS FOR VISUAL SHALL BE 75 CANDELAS. PLEASE |
| ADJUST AND PLACE REQUIREMENTS ON PLANS. PLEASE SEE ALL |
| FA SHEETS WHICH ONLY INDICATE NFPA-72. |
| |
| |
| 86) NOTE:OK, PLEASE DO THE SAME. NOTE WILL REMAIN. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE KNOW A RESPONSE LETTER/NOTES WERE PROVIDED, |
| HOWEVER AS THIS REVIEW WAS MORE OF A REVIEW FOR CODE |
| COMPLIANCE, A MORE DETAILED RESPONSE WOULD GREATLY HELP |
| IN THE REVIEW PROCESS. THIS RESPONSE COULD INDICATE THE |
| SHEETS/LOCATIONS OF CHANGES, CORRECTIONS OR ANY |
| COMMENTS RELATED TO AND RESPECT TO THIS REVIEWERS |
| NOTES. |
| |
| ********** NEW NOTES FOR THIS REVIEW************ |
| |
| 87) NOTE: PLEASE SEE FLORIDA STATUTES WITH RESPECT TO |
| THE ENGINEER OF RECORD SIGNING AND SEALING DOCUMENTS IN |
| 471.025. PLEASE SEE SHEETS SIGNED OTHER THAN MR. MINDUR |
| CONTAINS WHAT APPEARS TO BE MORE THAN ONE SIGNATURE FOR |
| THE SAME ENGINEER. PLEASE KNOW AS STATED BY THE |
| PLUMBING REVIEWER FOR PLUMBING SHEETS, THE SAME APPLIES |
| TO FS SHEETS AND OTHER DOCUMENTS SIGNED AND SEALED. |
| PLEASE KNOW UNTIL LEGAL SIGNATURE VERIFICATION CAN BE |
| DONE, THE ENERGY CALCULATIONS WHICH ARE SIGNED AND |
| SEALED ALSO BY OTHER THAN MR. MINDUR CAN NOT BE |
| ACCEPTED AT THIS TIME. |
| FAC 61G15-23.002 |
| PLEASE BE SURE LETTER FOR LEGAL SIGNATURE VERIFICATION |
| FOR MR. WU IS CORRECTLY NOTARIZED PER FLORIDA STATUTES |
| 117.05. |
| |
| 88) NOTE: PLEASE KNOW AS COMMENTS FROM ELECTRICAL |
| ENGINEER MENTIONED TO SEE S SHEETS FOR INFORMATION, |
| UPON REVIEW OF SAID SHEETS THIS REVIEW NOTICE MANY |
| SHEETS WHICH WERE DATED IN DECEMBER NOT CONTAINING ANY |
| TITLE BLOCKS FOR THE ENGINEERING FIRM OF RECORD. PLEASE |
| SEE SOME SHEETS WHICH WERE DATED FROM OCTOBER WHICH DO |
| CONTAIN THE TITLE BLOCKS FOR FIRM DO NOT CONTAIN THE |
| CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED UNDER |
| FS 471.023 AND FAC 61G15-23.002. THIS IS REQUIRED FOR S |
| SHEETS WHETHEROR NOT COMMENT IS MADE BY ANY OTHER |
| TRADE. |
| |
| 89) NOTE: PLEASE SEE ENERGY CALCULATIONS WHICH ARE NOW |
| SUBMITTED ONLY INDICATE 3 FIXTURES FOR EXTERIOR |
| LIGHTING? HOW IS THIS POSSIBLE? PLEASE CORRELATE WITH |
| PLANS AND FIXTURES AS SHOWN ON PLANS. |
| PLEASE ALSO CORRELATE WITH THE WATTAGES AS SHOWN ON |
| LIGHTING POWER DENSITIES AND PLANS. |
| PLEASE CLARIFY ZONES IN ENERGY CALCULATIONS AS SHOWN. |
| PLEASE SEE FBC 13-415.1.AB.1, 13-415.2 |
| |
| 90) NOTE: PLEASE SEE NOTES ON LIGHTING SEQUENCE OF |
| OPERATION SHEETS. PLEASE SEE NOTE #11 ON E5-3.0 WHICH |
| MENTIONS PHOTO-CELL FOR CONTROL OF ROOMS? PLEASE SEE |
| THE SAME ROOMS AND NOTE #3 ON 5-3.1 WHICH MENTIONS |
| DIFFERENT CONTROLS. |
| |
| 91) NOTE: PLEASE SEE WATER COOLERS LOCATIONS OF |
| RECEPTACLES. PLEASE SEE MANY INDICATE THE RECEPT TO BE |
| LOCATED AT THE CEILING LEVEL AND MANY INDICATE AT WC |
| LEVEL. PLEASE EXPLAIN THE INDICATION FOR DEVICE AT |
| CEILING. PLEASE ALSO SEE AREAS WHERE MORE THAN TWO |
| WATER COOLERS ARE BEING SHOWN HOWEVER ONLY ONE DUPLEX |
| RECEPT IS BEING SHOWN. PLEASE ADJUST TO QUAD AND PLEASE |
| VERIFY LOAD ON THESE UNITS WHICH ARE NOT TO EXCEED |
| RATING OF DEVICE AND CIRCUIT. THIS WAS NOT COMMENTED ON |
| THE PREVIOUS REVIEW. |
| 240.4, 310.16, 210.25, 2210.21B2 ETC. |
| |
| 92) NOTE: PLEASE PLACE NOTE ON E0-2.1 FOR SECTIONS OF |
| 314PART IV , SECTIONS 314.50-314.59 TO BE MET. |
| NOT ON PREVIOUS REVIEW. |
| |
| 93) NOTE: PLEASE SEE UPON REVIEW OF PROJECT MANUAL, |
| PLEASE SEE COLOR CODING SHALL BE BROWN, PURPLE, YELLOW |
| FOR 277/480V SYSTEMS. PLEASE SEE THE CODE DOES NOT |
| PROVIDE COLOR CODING FOR MOST SYSTEMS, HOWEVER ORANGE |
| AS BEING NOTED FOR THIS IS FOR A HIGH-LEG SYSTEM WHICH |
| IS NOT WHAT IS BEING INSTALLED. PLEASE KNOW AS PER |
| LOCAL AMENDMENTS FOR 3 DECADES OR SO UNDER THE 2004 FBC |
| THE CITY OF WEST PALM BEACH ALONG WITH PALM BEACH |
| COUNTY HAD THIS COLOR SCENARIO FOR 277/480V SYSTEMS AND |
| WILL BE REQUIRED TO REMAIN THE SAME FOR ALL OTHER |
| BUILDING BEING PROPOSED. PLEASE PLACE A NOTE ON RISER |
| FOR COLOR CODING. |
| 90.4., FBC ADMIN SECTION 104.6 |
| |
| 94) NOTE:PLEASE SEE BUILDING REVIEW NOTES AND |
| CLARIFY THE TWO PULL BOXES BEING SHOWN ON E0-2.1 WHICH |
| SEEM TO BE DIRECTLY LOCATED IN THE WALL OR FOOTER. |
| PLEASE CLARIFY THESE AT THE LOCATIONS AS SHOWN AND |
| PLEASE ADJUST PLANS AS NEEDED. PLEASE SEE CODE FOR |
| ACCESSIBILITY. |
| 110.26 |
| |
| 95) NOTE: PLEASE CLARIFY THE FUEL TANK ROOM AS BEING |
| SHOWN ON THE GARAGE PLANS NEXT TO THE FIRE PUMP ROOM. |
| PLEASE KNOW IT WAS BEING ASSUMED THIS WAS THE LOCATION |
| OF THE TANK FOR THE FIRE PUMP; HOWEVER IT HAS COME TO |
| OUR ATTENTION THAT THIS IS NOT THE CASE. PLEASE PROVIDE |
| INFORMATION FOR THIS FOR MECHANICAL AND FIRE REVIEW AS |
| WELL AS ELECTRICAL REVIEW. PLEASE SEE NEC 500. SPECIFIC |
| SECTIONS CAN NOT BE GIVEN AT THIS TIME, AS THE USE AND |
| RATING OF ROOM ETC IS NOT KNOWN AT THIS TIME. |
| FBC ADMIN SECTION 106.1.2 (MORE INFORMATION). NFPA-70, |
| 72, 30? ETC. |
| |
| 96) NOTE: PLEASE SEE ELEVATOR EQUIPMENT ROOM |
| DISCONNECTS ARE BEING SHOWN WITH 3-WAY SWITCH NOTATIONS |
| INSTEAD OF DISCONNECTS OR MOTOR RATED SYMBOL. |
| NOT ON PREVIOUS REVIEW. |
| PLEASE ADJUST. 620.51, 620.61, 620.62 ETC |
| FBC 106.1.2, |
| |
| 97) NOTE: PLEASE SEE ANY HAND DRAWN CHANGES WHICH MAY |
| HAVE BEEN DONE BY THE ENGINEER AFTER PLANS WERE SIGNED, |
| DATED AND SEALED, SHOULD BE REVISED AT THIS TIME. ONLY |
| THE ENGINEER OF RECORD MAY MAKE CHANGES TO SAID PLANS |
| WHICH ARE SIGNED AND SEALED. FS 471.025 PLEASE KNOW AS |
| PLANS ARE SEALED, MANY OF THE SEALS ARE NOT CLEAR AND |
| VISIBLE WITH INFORMATION ON SAID SEAL. PLEASE BE SURE |
| PLANS ARE SEALED TO SEE INFORMATION. FS 471.025 |
| |
| |
| IF ANY OF THESE COMMENTS ARE NOT CLEAR IN ANY FASHION |
| OR IF ANY ITEMS ARE NOT UNDERSTOOD IN ANY WAY?PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| |
| ** PLEASE KNOW AS THERE IS SOME INFORMATION NOT YET |
| SUBMITTED PLEASE BE SURE TO GO OVER ALL. |
| |
| |
| PLEASE SUBMIT THE ABOVE FOR REVIEW. ONCE AGAIN IF THERE |
| ARE ANY QUESTIONS , PLEASE DO NOT HESITATE IN |
| CONTACTING THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
2006-12-25 08:06:40 | 2006-12-25 08:06:40 |
| IN PROGRESS |
2006-12-24 20:14:29 | 2006-12-24 20:14:29 |
| REVIEW STOPPED. TO CONTINUE ON 12/25 |
2006-12-24 18:11:34 | 2006-12-24 18:11:34 |
| ONE ROLL OF MEP'S IN ELECTRIC FOR REVIEW ALONG WITH ONE |
| COPY OF RESPONSE LETTERS AND ONE COPY OF SUBMITTIALS |
| FOR REVIEW. |
| REVIEW IN PROGRESS. |