Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop E
Sequence Number 2
Notes
Date Text
2006-12-25 20:33:37** UNSAT 2ND REVIEW **
  
  
 **** CITY CENTER *******
  
 FOURTH REVIEW, 2ND UNDER PERMIT APPLICATION.
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A "NO" IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN "OK" WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A "NO/OK" MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
  
 1) NOTE: NO, PLEASE SEE THREE SETS OF ALL ARE REQUIRED.
 PLEASE SEE MISSING A THIRD SET OF ELECTRICAL SUBMITTALS
 FOR GENERATOR, ATS, MTS ETC.
 PLEASE ALSO SEE OTHER NOTES FOR MISSING THE LIGHTING
 SPEC BOOKS AND ENGINEERING CALCULATIONS WHICH WERE
 PREVIOUSLY SUBMITTED.
 ENGINEERING FOR SELECTIVE COORDINATION PREVIOUSLY
 SUBMITTED ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW WHEN SUBMITTING FOR FINAL PERMITTING AND
 STAMPING, A THIRD SET OF SIGNED, DATED AND SEALED PLANS
 WILL BE REQUIRED.
 PLEASE SEE FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE
 CITY OF WEST PALM BEACH, 106.1.2106.1.3, 109.3.6 FOR
 THRESHOLD BUILDINGS. THIS IS WILL BE REQUIRED FOR ALL
 DOCUMENTATION AND PLANS AND FOR ALL TRADES WHETHER OR
 NOT COMMENT IS MADE BY OTHER TRADES.
  
 2) NOTE: NO, PLEASE SEE SYMBOL LEGEND ONLY HAD CHANGES
 TO TWO OF THE DEVICES. PLEASE SEE ALL SWITCH/OVER RIDE
 TYPE DEVICES INCLUDING THE OC SENSOR SHOULD INDICATE ON
 THE SYMBOL LEGEND ITS DESIGNATION AND TIMES ON OVER
 RIDES. THIS WOULD INCLUDE S3, ST, OC ETC.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13. PLEASE SEE 13-415.1.ABC.1.1,
 .1.2 AND .1.3.
 PLEASE BE SURE ALL DEVICE ON PLANS CORRELATE WITH THE
 DEVICE SYMBOL LEGEND.
 PLEASE BE SURE MAX TIME OF OVER -RIDES ARE SHOWN. IF
 TIMER TYPE, (4HRS MAX), IF OCCUPANCY SENSOR TYPE (30
 MINS MAX).
 PLEASE SEE ADDITIONAL COMMENTS FOR CONTROLS AND SYSTEM
 BEING PROPOSED.
  
 3) NOTE: OK.
  
 4) NOTE: OK/NO, PLEASE SEE THESE WERE NOW SUBMITTED
 HOWEVER PLEASE SEE NEW NOTES AT THE END OF THESE
 COMMENTS AS THESE ARE NOW BEING SUBMITTED AND REVIEWED
 FOR THE FIRST TIME AND THERE ARE COMMENTS ON DOCUMENTS
 SUBMITTED.
 PLEASE ALSO SEE NEW NOTES PERTAINING TO THE SIGNATURE
 OF THE MECHANICAL ENGINEER OF RECORD ON SAID
 DOCUMENTS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS FOR THE
 ENTIRE BUILDING FOR REVIEW OF ALL TRADES. PLEASE KNOW
 AS NONE WERE SUBMITTED AT THIS TIME THERE ARE MANY
 ITEMS WHICH CAN NOT BE VERIFIED WITH THE PLANS,
 EQUIPMENT AND LIGHTING.
 PLEASE SEE 13-415.1.AB.1.
  
 5) NOTE: OK/NO, PLEASE SEE THESE WERE SUBMITTED AND
 SEEM TO BE OK, HOWEVER AS NOTED IN NOTE #4 ABOVE THERE
 ARE NEW NOTES BASED ON THE COORDINATION OF THESE
 DOCUMENTS WITH THE ENERGY CALCULATIONS SUBMITTED.
 PLEASE SEE THE TOTALS ON THE WATTAGE DO NOT SEEM TO
 CORRELATE WITH THE ENERGY CALCULATIONS AS SUBMITTED.
 PLEASE ALSO SEE NEW NOTES.
 PLEASE KNOW THE THREE SETS OF LIGHTING POWER DENSITIES
 SHALL CONTAIN TITLE BLOCKS FOR THE ENGINEER AND/OR FIRM
 OF RECORD. THIS MAY BE RE-DONE ON NEW SHEETS WHICH
 CONTAIN THESE TITLE BLOCKS, STAMPED ON EACH SHEET WHICH
 IS SIGNED AND SEALED BY THE ENGINEER OR HANDWRITTEN.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 13-415.2, 13-415.2ABC.1 FOR MINIMUM AND
 MAXIMUM PERFORMANCE CALCULATIONS. PLEASE SEE THE
 CALCULATIONS SUBMITTED SHOWING THE LIGHTING POWER
 DENSITIES (LPD) ARE NOT COMPLETE AND/OR THERE ARE ITEMS
 WHICH DO NOT CORRELATE WITH SAID PLANS.
 PLEASE SEE THERE ARE MANY ROOMS INDICATED ON PLANS
 WHICH COULD NOT BE LOCATED IN CALCULATIONS OR THERE ARE
 ROOMS ON CALCULATIONS WHICH COULD NOT BE LOCATED ON
 PLANS.
 PLEASE CORRELATE AND PLEASE SEE SOME OF THE LPD'S SEEM
 TO BE VERY HIGH FOR SOME OF THE ROOMS AND AREAS AS
 NOTED AND SHOWN.
 PLEASE SEE OFFICE IN PARKING GARAGE FOR INSTANCE.
 PLEASE SEE SOME OTHERS WHICH BASED ON THE TABLES AS
 SET-FORTH IN THE CODE MAY ALLOW 1.7, THE CALCULATIONS
 MAY SHOW 10.5 ETC.
 PLEASE REVIEW ALL AND RE-ADJUST AS REQUIRED AND
 NEEDED.
  
 6) NOTE: NO, UNABLE TO VERIFY AT THIS TIME DUE TO THE
 CONFLICTS BETWEEN THE ENERGY CALCULATIONS FOR EXTERIOR
 LIGHTING AND THE ALLOWANCE LEVELS NOT BEING SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 13-415.2.ABC.1.3 FOR ALL EXTERIOR LIGHTING
 ALLOWANCES, INCLUDING THAT WHICH IS DECORATIVE. PLEASE
 SEE THERE ARE EXCEPTIONS FOR SOME AREAS; HOWEVER THESE
 AREAS AS LISTED WOULD BE REQUIRED BY SECTIONS AS
 LISTED. PLEASE SEE 13-415.0(3) (EXCEPTS).
  
 7) NOTE: OK/NO, PLEASE SEE THE PLANS NOW SEEM TO
 INDICATE THE EQUIPMENT MORE IN DETAIL, HOWEVER AS NOTED
 IN NOTE #1, THE MANUFACTURES SPECS/CUT SHEETS WERE NOT
 SUBMITTED BACK. THIS REVIEWER ONLY HAS THE ONE BOOK
 WHICH WAS RETAINED BY THIS OFFICE.
 WHEN SUBMITTING BOOKS/SPECS, PLEASE BE SURE TO HIGH
 LIGHT AND COORDINATE WITH THE PLANS SUBMITTED FOR THE
 EQUIPMENT AND DEVICES BEING INSTALLED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS SHALL INDICATE THE ACTUAL PANEL BEING
 USED FOR LIGHTING CONTROLS. PLEASE SEE THERE ARE
 SEVERAL PANELS INDICATE IN THE MANUFACTURE SPECS/CUT
 SHEETS SUBMITTED AND THE ACTUAL UNIT NEEDS TO BE
 HIGH-LIGHTED IN SPECS. PLANS SHALL ALSO BE REQUIRED TO
 PROVIDE THE TECHNICAL INFORMATION AT EACH LIGHTING
 CONTROL PANEL. (LCP)
 ** PLEASE KNOW AS REFERENCE TO LIGHTING CONTROL PANELS
 IN NOTES HERE ON WILL BE DESIGNATED AS "LCP'S". PLEASE
 SEE RISER INDICATES LCP'S AS 225A RATED, WHICH IS OK,
 HOWEVER PLEASE BE SURE THE INFORMATION AS SHOWN ON
 CUT/SPEC SHEETS IS BROUGHT OVER TO THE PLANS AND LISTED
 ON EACH LCP.
  
 8) NOTE: OK/NO, PLEASE KNOW MOST OF THE SYSTEM IS
 UNDERSTOOD HOWEVER THERE ARE AREAS IN WHICH A SWITCH
 TYPE DEVICE (SENTRY) IS BEING INSTALLED ALONG WITH AN
 OC (OCCUPANCY SENSOR) TYPE DEVICE. THE DETAIL WAS
 LOCATED ON 7-2.0 HOWEVER THIS WOULD STILL PERMIT THE
 TURNING OFF LIGHTS IN AN UNWANTED FASHION.PLEASE SEE
 EGRESS STAIRS FOR MEZZANINE AREA WHICH COULD BE TURNED
 OFF, YET OF AN OCCUPANT WAS STILL LOCATED ON THE UPPER
 LEVEL THEY WOULD HAVE NO CONTROL OF LIGHTING AS SHOWN.
  
 PLEASE SEE ROOF TOP AREA ON E1-6.1 WHICH LOCATES A
 SWITCH ON WHAT APPEARS TO BE AN OUTSIDE WALL TO CONTROL
 LIGHTING IN ELEVATOR EQUIPMENT ROOM AS WELL AS OTHER
 LIGHTING AS REQUIRED FOR LIFE SAFETY.
 PLEASE SEE OTHER AREAS WHICH CONTAIN BOTH.
 PLEASE ALSO SEE AS NO SPECS WERE SUBMITTED BACK, COULD
 NOT LOCATE A LETTER FROM THE LUTRON MANUFACTURE WHICH
 PERMITS THE USE OF THE SENTRY SWITCH IN THEIR SYSTEM.
 PLEASE SEE AREAS OF MEETINGS ROOMS AND COMMISSION
 CHAMBERS AREA WHICH DO NOT PROVIDE ENOUGH INFORMATION
 FOR HOW THESE WILL BE CONTROLLED. PLEASE SEE THAT THE
 NOTE ON THE PLANS FOR THIS TO BE PROVIDED BY LIGHTING
 TECHNICAL NEEDS TO BE REPLACED WITH ACTUAL DETAILS ON
 HOW THESE WILL BE ADDRESSED TO COMPLY WITH CHAPTER 13
 AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW THERE IS CONCERN OVER THE TYPE OF SYSTEM
 BEING PROPOSED AND CONTROLS OF SAID SYSTEM. PLANS CALL
 FOR A "SWEEP" EACH HOUR FOR THE SYSTEM OUT OF NORMAL
 BUSINESS HOURS AND THIS WILL TURN OFF ANY AND ALL
 DEVICES. THE DEVICES WILL THEN HAVE THE ABILITY TO OVER
 RIDE THE SYSTEM IN ANY PARTICULAR AREA WHICH THE
 CIRCUIT/SWITCH IS DESIGNATED TO. PLEASE KNOW THIS
 BUILDING IN SEVERAL SECTIONS WILL BE OCCUPIED OUT OF
 THE NORMAL BUSINESS HOURS WHICH ARE SET UP AND WILL
 CAUSE DARKNESS EACH HOUR EVEN WHEN OCCUPIED. PLEASE SEE
 SPECS SHEETS AS SUBMITTED SPEAK OF THE INCLUSION OF AN
 OCCUPANT SENSOR TYPE DEVICE TO ALLEVIATE THIS.
 (UNINTENDED BLACK-OUTS). PLEASE SEE AREAS LIKE THE
 LIBRARY, COMMISSIONS CHAMBERS, OFFICE DESIGNATED FOR
 POLICE, AND OTHER AREAS.
 PLEASE SEE THE CODE ON THE OTHER HAND FOR ALL AREAS
 WHICH DURING NORMAL BUSINESS HOURS WHICH WILL REQUIRE
 ROOMS TO BE OFF. PLEASE SEE 13-415.1.ABC.1.2, FOR ALL
 ROOMS CONTAINING FLOOR TO CEILING HEIGHT PARTITIONS
 WHICH WILL REQUIRED SEPARATE CONTROL. PLEASE SEE AS
 SHOWN ON PLANS, THESE ROOMS WILL COME "ON" AT THE SET
 BUSINESS HOUR TIMES AND WILL REMAIN ON UNTIL AFTER THE
 "ONE HOUR SWEEP" AFTER THE NORMAL OPERATIONAL TIMES
 HAVE PASSED.
 PLEASE SEE CLOSETS, OFFICES, STORAGE AREAS ETC. THERE
 ARE FAR TOO NUMEROUS ROOMS TO LIST.
 PLEASE SEE THERE ARE MANY ROOMS ON PLANS WHICH DO
 INDICATE "OC" TYPE DEVICES; HOWEVER THERE IS NOT DETAIL
 ON THE LIGHTING CONTROL RISER HOW THESE WILL BE
 CONNECTED OR TIED IN.
 PLEASE SEE BATHROOMS ETC.
 PLEASE KNOW THIS TYPE OF DEVICE WILL WORK IN MANY AREAS
 IN THIS BUILDING; HOWEVER THERE ARE AREAS WHICH WILL
 NOT MEET CODE OR THE INTENT IN SEPARATE SPACES. PLEASE
 KNOW AT THIS TIME, AS SHOWN THERE ARE SEVERAL ITEMS
 WHICH WILL BE REQUIRED TO BE ADJUSTED. PLEASE ALSO
 OBTAIN A LETTER FROM THE "SENTRY SWITCH" MANUFACTURE
 WHICH PERMITS THIS TYPE OF DEVICE TO BE USED WITH THE
 LUTRON GRAFIK PANEL.
 110.3, 90.7 NEC.
  
 9) NOTE: OK/NO, PLEASE SEE COORDINATION OF NUMERICAL
 IDENTIFICATION SEEMS TO BE BETTER; HOWEVER PLEASE SEE
 SEVERAL AREAS AND ROOM HAVE THEIR DESIGNATION COVERED
 BY A DEVICE, FIXTURE OR SOME OTHER ITEM.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THERE ARE SEVERAL ROOM NUMERICAL
 DESIGNATIONS ON CALCULATIONS WHICH COULD NOT BE LOCATED
 ON PLANS. PLEASE SEE GARAGE PLANS.
 PLEASE SEE SOME WHERE THE ROOM DESIGNATION IS THERE
 HOWEVER IT SEEMS TO BE VERY LIGHT IN COLOR AND CAN NOT
 BE EASILY READ. PLEASE SEE OTHER AREAS WHICH THE
 FIXTURE DESIGNATION COVERS THE ROOM IDENTIFICATION OR
 VICE VERSA, THE FIXTURE TYPE COULD NOT BE SEEN DUE TO
 THE OVER LAY OF THE NUMERICAL DESIGNATION.
 PLEASE COORDINATE. A1-116-2-1.610 ETC
 FBC ADMIN SECTION 106.1.2, 106.1.3
  
 10) NOTE: OK, HOWEVER PLEASE KNOW BASED ON FURTHER
 COMMENTS, ADJUSTMENTS IN FIXTURE TYPES AND DESIGNATIONS
 WILL BE NEEDED.
  
 11) NOTE:NO, PLEASE SEE THERE ARE SEVERAL ROOMS WHICH
 STILL DO NOT INDICATE A BATTERY BACK UP FIXTURE OF SOME
 SORT WHICH WILL BE REQUIRED.
 FIRE PUMP ROOMS, MAIN ELECTRICAL ROOM, MAIN MECHANICAL
 ROOM, THE MAIN MECHANICAL ROOM ELECTRICAL ROOM,
 ELEVATOR EQUIPMENT ROOM. ETC.
 PLEASE ALSO SEE NEW NOTES FOR ROOF TOP/ELEVATOR
 EQUIPMENT ROOM AND OUTSIDE AREA TO STAIR TWO. PLEASE
 ALSO SEE GARAGE STAIR TOWERS WILL ALSO BE REQUIRED TO
 CONTAIN MINIMUM BATTERY BACK UP FOR FIXTURES AS OTHER
 STAIR TOWERS IN MAIN BUILDING ARE DONE.
 ** PLEASE ALSO SEE FIRE REVIEW COMMENTS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT BATTERY BACK UP FIXTURES OF SOME TYPE
 WILL BE REQUIRED FOR THE FOLLOWING LOCATIONS. SOME ARE
 SHOWN ALREADY, HOWEVER NOT ALL. THE MAIN ELECTRICAL
 ROOM, THE FIRE COMMAND CENTER, BOTH FIRE PUMP ROOMS,
 ELEVATOR EQUIPMENT ROOM, AND AT THE LOCATION OF THE
 ROOF TOP GENERATOR WILL ALL REQUIRE THIS. PLEASE SEE
 THAT ALL STAIR TOWERS AND EGRESS PATHS SHALL ALSO
 INCLUDE SOME SORT OF BATTERY BACK UP FIXTURE. THERE ARE
 MANY LOCATIONS WHICH INCLUDE THIS; HOWEVER AS SOME OF
 THE FIXTURE INFORMATION IS NOT CLEAR AT THIS TIME THIS
 CAN NOT BE VERIFIED. THIS BUILDING IS EXPECTED TO BE
 OCCUPIED IN THE TIME OF POWER OUTAGES AND IN THE EVENT
 OF THE TRIPPING OF A SINGLE MEANS OF OVER CURRENT
 PROTECTION (EMSB1) OR GEN MAIN, THIS WILL PLACE MANY
 AREAS IN COMPLETE DARKNESS WHICH IS NOT PERMITTED. NEC
 700.12E, 700.16, LS 101 7.9.
  
 12) NOTE: OK.
  
 13) NOTE: OK.
  
 14) NOTE: NO, PLEASE SEE COMMENTS WITH RESPECT TO STAIR
 TOWERS IN GARAGE AND OTHER ROOMS WITH THESE
 DESIGNATIONS WHICH MAY BE CHANGED OR ADJUSTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FIXTURE "E", PLEASE SEE IT APPEARS TO BE
 BATTERY BACK UP, BUT NOT ENOUGH INFORMATION IS
 PROVIDED. PLEASE SEE FIXTURES, Z,ETC.
  
 15) NOTE: OK.
  
 16) NOTE: NO, PLEASE SEE RESPONSE LETTER MENTIONS THIS
 IS TO BE DONE BY THE STRUCTURAL ENGINEER/DESIGNER OF
 RECORD HOWEVER COULD NOT LOCATED ANY DETAIL FOR THIS ON
 THE S SHEETS. PLEASE SEE THE SAME DETAIL FOR GROUND
 LEVEL POLES IS BEING USED FOR ROOF TOP MOUNTING? PLEASE
 SEE NEW NOTES WITH RESPECT TO THE S SHEETS AND TITLE
 BLOCKS MISSING AND OTHER NOT CONTAIN ANY CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED. SEE NEW ELECTRICAL
 NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE ALL MINIMUM WIND LOADING FOR SITE
 LIGHTING LIGHT POLES, AND THAT OF THE POLES ON GARAGE
 ROOF STRUCTURE. PLEASE KNOW A DETAIL ON HOW THESE WILL
 BE ATTACHED ON PARKING DECK OF THE GARAGE AND POLE
 DETAIL FOR GROUND MOUNTED/BURIED POLES WILL BE
 REQUIRED. PLEASE KNOW ALL SHOW MEET THE FBC 140MPH
 (3SEC GUST) 120MPH SUSTAINED.
 THE STRUCTURAL CALCULATIONS WILL BE REVIEWED BY THE
 BUILDING PLAN REVIEWER.
 FBC 106.1.2 ADMIN SECT.
  
 17) NOTE: OK.
  
 18) NOTE: OK.
  
 19) NOTE:NO, THIS IS STILL UNCLEAR HOW THE SHORTER
 LENGTHS OF CONDUCTORS OUT TO FIXTURES ACTUALLY CONTAIN
 A HIGHER VOLTAGE DROP.
 PLEASE SEE OTHER COMMENTS ON THE FOLLOWING NOTE #20.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE THE VOLTAGE DROP ON THIS SAME CIRCUIT AS
 NOTED ABOVE IN NOTE # 18, PLEASE SEE FIXTURE SA
 INDICATE #8'S, AND YET SB WHICH CONTAIN A LONGER RUN
 AND MORE FIXTURES ONLY INCREASE UP TO A #10 AWG. PLEASE
 SEE FBC 13-413.1.ABC.1.2.
  
 20) NOTE:NO, COULD NOT LOCATE ANY FOR BRANCH
 CIRCUITING. ONLY LOCATED THE FEEDERS ON RISER.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE A WORST CASE FOR BOTH FEEDER AND BRANCH
 CIRCUIT.
 13-413.1ABC.1.
 IT IS NOTEDTHAT ON MANY OF THE PANEL SCHEDULES A VD %
 IS ALREADY SHOWN, HOWEVER PLEASE BE SURE TO INDICATE
 THE ABOVE. (CAN BE DONE ON A SIMPLE TYPICAL TABLE). FBC
 106.1.2.
  
 21) NOTE: NO, SAME NOTE. PLEASE SEE THE FS SHEETS STILL
 INDICATE ELECTRICAL FIRE PUMPS ALONG WITH DIFFERENT
 SIZES OF EQUIPMENT THAN THAT SUBMITTED IN THE
 ELECTRICAL SUBMITTAL BOOKS. PLEASE SEE DIFFERENT
 MANUFACTURE, ETC.
 PLEASE SEE THAT BASED ON THE COMMENTARY PROVIDED FOR
 FUEL USAGE, THE FUEL FOR ONE APPEARS TO BE OK, HOWEVER
 THE OTHER (110HP) DOES NOT MEET THE MINIMUM LEVEL OF
 FUEL REQUIRED. PLEASE SEE AS TWO DIFFERENT SIZE PUMPS
 ARE SUBMITTED, I AM UNABLE TO REVIEW WHICH THE ONE FOR
 INSTALLATION AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE 100% FIRE SPRINKLER PLANS SUBMITTED DO
 NOT CORRELATE WITH THE FA OR ELECTRICAL PLANS SUBMITTED
 WITH RESPECT TO THE FIRE PUMPS. PLEASE SEE THE FS
 SHEETS WHICH INDICATE ELECTRIC, ELECTRICAL/ DIESEL AND
 DIESEL. PLEASE SEE THE ELECTRICAL PLANS AND THE
 MANUFACTURE SPECS/CUT SHEETS SUBMITTED ONLY INDICATE
 DIESEL.
 PLEASE SEE THE MINIMUM FUEL TANK SIZE SHALL BE
 SUFFICIENT FOR A MINIMUM OF 8HRS AT 100% LOADS. IF
 ELECTRICAL AND BEING DRIVEN BY THE BACK UP POWER OF AN
 EMERGENCY GENERATOR, THE ON-SITE FUEL SUPPLY SHALL BE
 BASED ON THE 100% LOAD OF THE FIRE PUMP AND ALL OTHER
 LEGAL AND EMERGENCY STAND-BY LOADS AT 100% FOR TIMES
 REQUIRED.
 PLEASE SEE 2002 NFPA-110, TEXT EXTRACTED FORM THE
 CODE:
 9.6.2.2 THE FUEL SUPPLY CAPACITY SHALL BE SUFFICIENT
 TO PROVIDE 8 HOURS OF FIRE PUMP OPERATION AT 100
 PERCENT OF THE RATED PUMP CAPACITY IN ADDITION TO THE
 SUPPLY REQUIRED FOR OTHER DEMANDS.
 PLEASE SEE NFPA-20 2003 IF DIESEL DRIVEN AND THE SAME
 AMOUNT OF FUEL REQUIRED WHICH EQUALS 1GAL PER HP PER
 HOUR PLUS 5% FOR SUMP AND 5% FOR EXPANSION. PLEASE SEE
 THE FOLLOWING THE CODE.
 11.4.3.1 FUEL SUPPLY TANK(S) SHALL HAVE A CAPACITY AT
 LEAST EQUAL TO 5.07 L PER KW (1 GAL PER HP), PLUS 5
 PERCENT VOLUME FOR EXPANSION AND 5 PERCENT VOLUME FOR
 SUMP AND THE COMMENTARY SECTION AS FOLLOWS, A.11.4.3
 THE QUANTITY 5.07 L PER KW (1 GAL PER HP) IS EQUIVALENT
 TO 0.634 L PER KW (1 PINT PER HP) PER HOUR FOR 8
 HOURS. WHERE PROMPT REPLENISHMENT OF FUEL SUPPLY IS
 UNLIKELY, A RESERVE SUPPLY SHOULD BE PROVIDED ALONG
 WITH FACILITIES FOR TRANSFER TO THE MAIN TANKS.
  
 22) NOTE: OK.
  
 23) NOTE: OK/NO, PLEASE SEE AS SOME AREAS ARE NOT CLEAR
 UNABLE TO VERIFY ANY GFI NOTATION. PLEASE SEE SOME ARE
 SHOWN WITH THE GFI IDENTIFICATION AND IF THE SYMBOLS
 WERE A LITTLE MORE CLEAR THE SYMBOL LEGEND ON E0.10 MAY
 BE IF USE.
 PLEASE ALSO SEE SHEET E1.-1.2 WHICH SHOULD BE A SECTION
 OF THE BUILDING WHICH WOULD BE LARGER IN SIZE. IT SEEMS
 SOMETHING WITH THE PRINTING OF SHEET CAUSED SHEET TO BE
 MUCH SMALLER. PLEASE SEE KITCHEN AREAS WHICH ARE
 LOCATED ON THIS SHEET COULD NOT BE VERIFIED AT THIS
 TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NEC 210.8B3 FOR ALL RECEPTACLES IN KITCHENS
 IN OTHER THAN DWELLING UNITS. PLEASE SEE THIS WOULD BE
 REQUIRED FOR CAFE/ KITCHENETTE AREAS AS SHOWN ON
 PLANS.
  
 24) NOTE: OK.
  
 25) NOTE: NO, PLEASE SEE PHOTO-METRICS ARE CONFUSING.
 PLEASE SEE THE GARAGE STAIRS SEEM TO NOW BE SHOWN,
 HOWEVER THERE IS NO SPECIFIED UNDER NORMAL OR UNDER
 EMERGENCY. PLEASE SEE DESIGNATIONS ON ALL OTHER STAIRS
 AND LABELING OF AREAS DOES NOT CORRELATE WITH ACTUAL
 PLANS AND STAIR TOWERS AS SHOWN. PLEASE KNOW THIS
 COMMENT IS NOT JUST FOR GARAGE STAIRS AS PREVIOUS
 COMMENT WAS TO ADDRESS ALL PHOTO-METRICS. PLEASE SEE
 MISSING STAIR 13, MEZZ STAIRS, PLEASE SEE OTHER STAIR
 DESIGNATIONS NOT LABELED ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING THE PHOTO-METRICS FOR THE GARAGE
 STAIR TOWERS. PLEASE SEE THE PHOTO-METRICS AS SUBMITTED
 ARE A LITTLE CONFUSING. PLEASE PREVIOUS COMMENTS ONLY
 REQUESTED EGRESS PATHS OF LEVELS SURFACES/ CORRIDORS
 AND EGRESS PATHS THAT OF THE STAIR TOWERS. PLEASE SEE
 THERE MUCH INFORMATION SUBMITTED GIVING FIXTURE
 DESIGNATIONS AND ROOM BY ROOM LEVELS? PLEASE PROVIDE
 THE EGRESS PATHS INFORMATION INDICATING THE CLEAR
 NORMAL AND EMERGENCY LEVELS AS NEEDED AND REQUIRED BY
 CODE.
 PLEASE PROVIDE A BREAKDOWN OF THE NORMAL AND EMERGENCY
 AVERAGE. PLEASE SEE THAT INFORMATION OF WHICH IS
 SUPPLIED ON EACH "OVER-ALL" SHEET DOES NOT SUPPLY THE
 INFORMATION AS NEEDED.
 PLEASE SEE 9-4.1 WHICH INDICATES IN TITLE BLOCK,
 EMERGENCY/ NORMAL?
  
 26) NOTE: OK.
  
 27) NOTE: NO, PLEASE SEE SOME ARE STILL SHOWING THIS
 DESIGNATION.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE CLARIFY GARAGE LIGHTING WHICH SHOWS "ON" NEXT
 TO SOME FIXTURES ON PLANS. (RAMP AREAS) THIS IS UNCLEAR
 AT THIS TIME WHAT IS MEANT BY THIS.
 FBC 106.1.2 ADMIN SECTION
  
 28) NOTE: OK.
  
 29) NOTE: OK.
  
 30) NOTE: OK/NO, PLEASE SEE ROOM LAYOUT DESIGNATION ON
 SHEET E1-1.3 INDICATES SHEET E4-1.0, WHEN IT SHOULD BE
 E- 1.1
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING THE ELECTRICAL ROOM FOR 1HMGB AND
 1HMGA ON THE LAYOUTS FOR THE ELECTRICAL ROOMS. PLEASE
 PROVIDE. 106.1.2,
 NEC 110.26
  
 31) NOTE: NO/OK, PLEASE SEE THE DOOR SWINGS SEEM TO BE
 OK, HOWEVER PLEASE SEE NO NOTE FOR PANIC HARDWARE AS
 REQUIRED COULD BE LOCATED ON PLANS. THIS WILL BE
 REQUIRED FOR MAIN ELECTRICAL ROOM AND MAIN ELECTRICAL
 EQUIPMENT FOR MECHANICAL MAIN ELECTRICAL EQUIPMENT
 ROOMS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MAIN ELECTRICAL ROOM AND THE MISSING
 ELECTRICAL ROOM FROM NOTE #30 ABOVE WHICH IS STILL
 INDICATING DOORS WITH AN "IN-SWING" WHICH IS NOT
 PERMITTED. PLEASE ALSO BE SURE TO ADD A NOTE WITH
 RESPECT TO PANIC HARDWARE REQUIRED FOR ALL DOORS AS
 REQUIRED PER 110.26. (MAIN ELECTRICAL ROOM/ AND ROOM
 NOTED ON NOTE #30).
 PLEASE SEE THE DOOR SWINGS WERE NOTED ON ALL OF THE
 REVIEWS BASED ON THE 50%, 90% AND THIS REVIEW. PLEASE
 GO OVER ALL PLANS AND DOORS.
  
 32) NOTE: NO, PLEASE SEE SEVERAL OF THESE UNITS ARE
 BEING SHOWN ON PLANS AT JANITOR CLOSET LOCATIONS,
 HOWEVER NOT ALL OF THESE ROOMS CONTAIN THESE. PLEASE
 ALSO SEE SEVERAL KITENETTE AREA WHICH ALSO INCLUDES
 THESE HOWEVER MANY DO NOT? IN EITHER CASE PLEASE SEE NO
 SPECS WERE SUBMITTED AND NO DISCONNECTING MEANS FOR ALL
 UNITS COULD BE LOCATED ON PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS FOR AL
 THE TANK-LESS WATER HEATER UNITS. THESE MAY ALSO BE
 LABELED AS INSTA-HOTS. PLEASE SEE MISSING DISCONNECTS
 AS REQUIRED ON THESE UNITS. THESE COULD NOT BE LOCATED
 ON PLANS.
 PLEASE SEE SIZING OF THE OVER CURRENT DEVICES,
 DISCONNECTS AND ETC SHALL BE BASED ON EACH UNIT. PLEASE
 SEE 422.31, 110.3, AND 90.7.
  
 33) NOTE:NO, SAME NOTE. PLEASE VERIFY ALL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE SOME TWH UNITS WHICH ARE SHOWN ON PLANS ARE
 MISSING THE REQUIRED CIRCUITING. CAN NOT REVIEW FOR
 COMPLIANCE OF LOAD, CONDUCTOR SIZE, OCP ETC AT THIS
 TIME.
 PLEASE COMPLETE. 240.4, 310.16, 408.4, FBC 106.1.2
  
 34) NOTE: OK.
  
 35) NOTE: OK.
  
 36) NOTE: OK
  
 37) NOTE: OK.
  
 38) NOTE: OK.
  
 39) NOTE: OK.
  
 40) NOTE: OK.
  
 41) NOTE: OK, HOWEVER SEE NOTE FOR CORRELATION OF ROOM
 A5.107
  
 42) NOTE: OK.
  
 43) NOTE: NO? SAME AS SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE "SHADED" AREAS ON MEZZANINE LEVEL PLANS
 E-1.1.4, PLEASE CLARIFY
 106.1.2 FBC ADMIN SECTION.
  
 44) NOTE: OK.
  
 45) NOTE: OK.
  
 45) NOTE: NO/OK, PLEASE SEE WALL AS LOCATED, HOWEVER
 SEPARATE LIGHTING CONTROLS FOR SEPARATE SPACES AS
 REQUIRED COULD NOT BE LOCATED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE WHAT APPEARS TO BE MISSING WALLS, DOORS
 SEPARATION E-1-1.2, LIBRARY/MUSEUM/ STORE? PLEASE SHOW
 AS THE REQUIREMENTS FOR CHAPTER 13 CAN NOT VERIFIED FOR
 CONTROL OF LIGHTING. LIGHTING OF SOME TYPE INCLUDING
 EXIT/EMERGENCY LIGHTS ARE STILL REQUIRED IN SPACE, EVEN
 IF FOR FUTURE BUILD OUT. PLEASE SEE LS 101 7.8, 7.9 AND
 POSSIBLE COMMENTS FROM FIRE MARSHAL?S OFFICE.
 13-415.1.ABC.1.ABC.1.1, .1.2, .1.3
  
 46) NOTE: OK.
  
 47) NOTE: NO/OK, SOME OF THESE WERE DONE BY THE CHANGES
 IN THE UNDER GROUND TO OTHER SECTIONS OF BUILDING,
 HOWEVER NOT DETAIL FOR THE ENCASED FEEDERS FROM
 GENERATOR COULD BE LOCATED. PLANS MENTIONS TO SEE
 ARCHITECTURAL PLANS; HOWEVER NO INFORMATION FOR WHICH
 SHEET OR DETAIL THIS IS COULD BE FOUND. PLEASE PROVIDE
 THE DETAIL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE AN ELEVATION/DETAIL FOR ALL ELECTRICAL
 CONDUITS BEING RUN FROM GARAGE TO THE MAIN BUILDING.
 THIS BUILDING IS BEING CONSIDERED "ATTACHED" AND ONE "
 BUILDING" BY DEFINITION, HOWEVER DUE THE UNDERSTANDING
 OF MANY OF THE CONDUITS ARE NOW BEING INSTALLED IN THE
 SLAB OR UNDER GROUND AND THE AMOUNT OF OTHER CONDUITS,
 PIPING, BEING INSTALLED IN THIS SAME AREA, IT IS OF
 CONCERN FOR THE SPACE REQUIREMENTS FOR BUNDLING OF
 CONDUITS, DE-RATING OF CONDUCTOR AMPACITIES. ETC. (THIS
 CAN BE A DETAIL LIKE A DUCT-BANK DETAIL)
 FBC 106.1.2, 310.16, 300.8, 300.10, 310.10, 310.15,
 310.16, 300.17 ETC.
 THERE ARE MANY SECTIONS WHICH COULD BE REFERENCED.
 PLEASE ALSO SEE COMMENT WITH RESPECT TO WIRING METHODS
 OF EMERGENCY FEEDERS ETC.
  
 48) NOTE: OK, HOWEVER SEE NEW NOTES DUE TOP HAND DRAWN
 CHANGES MADE TO PLANS.
  
 49) NOTE: NO, PLEASE SEE THE RATING OF THIS ROOM IS
 STILL REQUIRED. THIS COMMENT WILL BE IN REVIEWS FROM
 MULTIPLE REVIEWERS AND AS THIS WILL CHANGE THE BACK
 GROUND OF WALL DETAIL PLEASE ADDRESS AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE KNOW AS NO INFORMATION FOR THE IT ROOM EQUIPMENT
 IS BEING SUBMITTED WITH THIS RECORD SET OF PLANS,
 PLEASE PLACE NOTE AND CLOUD ON 4TH FLOOR POWER PLANS
 THAT ALL ELECTRICAL EQUIPMENT, UPS, SERVER EQUIPMENT
 ETC IN THE IT ROOM SHALL BE UNDER A SEPARATE PERMIT,
 PLANS, AND FEES BASED ON THE EQUIPMENT BEING INSTALLED
 IN THIS ROOM. REVIEW FOR CODE COMPLIANCE FOR THIS ROOM
 CAN NOT BE COMPLETED AT THIS TIME. THE REQUIREMENTS FOR
 THE CONSTRUCTION OF THIS ROOM IS REQUIRED AT THIS TIME,
 INCLUDING THE MINIMUM 1HR RATING, THE FIRE DAMPERS ETC
 (IF APPLICABLE) AND THE SHUT DOWN OF AN AND ALL A/C
 EQUIPMENT.
 NEC 645, NFPA-75
  
 50) NOTE: OK.
  
 51) NOTE: OK.
  
 52) NOTE: OK.
  
 53) NOTE:OK/NO, THIS NOTE WILL REMAIN AS IT IS THIS
 REVIEWERS UNDERSTANDING THAT THERE WILL BE COMMENTS
 FROM OTHER TRADES WHICH WILL SUBSTANTIALLY AFFECT
 BACKGROUNDS AND LAYOUTS OF SAID PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COORDINATE ALL OVER-LAYS AND LAYOUTS FOR
 ELECTRICAL, MECHANICAL, PLUMBING, BUILDING AND ALL
 OTHER TRADE PLANS. PLEASE KNOW THE ELECTRICAL 100%
 PLANS DO NOT SHOW THE SAME ELECTRICAL ROOMS AND
 EQUIPMENT AS THE 100% MECHANICAL PLANS, PLUMBING OR
 BUILDING PLANS ALONG WITH OTHER SHEETS FROM OTHER
 TRADES.
 REVIEW OF ALL APPLICABLE ITEMS WILL STILL NEED TO BE
 DONE AS REQUIREMENTS FOR ELECTRICAL AND OTHER TRADES
 WILL MOST CONTAIN CLEAR CONFLICTS WHICH MAY OR MAY NOT
 BE PERMITTED.
 110.26, 240.24 NEC.
 FBC 106.3.5.1.1 ADMIN SECTION FOR ALL TRADES FOR
 COMMERCIAL PLANS.
  
 54) NOTE:NO, SAME NOTE. PLEASE SEE PLANS IN SEVERAL
 LOCATIONS 6-1.0,1-6.3,5-1.1 ETC INDICATE 800KW AND
 SUBMITTALS ARE 900KW.
 PLEASE ALSO SEE SHEET WHICH STILL INDICATES ONLY 5
 GALLON SPILL CONTAINMENT. THIS MAY BE PART OF THE FIRE
 OR MECHANICAL REVIEW NOTES, IF NOT PLEASE SEE THIS
 NEEDS TO BE VERIFIED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE THE PLANS WITH THE MANUFACTURE
 SPECS/CUT SHEETS FOR THE GENERATOR WHICH IS BEING
 SUBMITTED AS A LARGER UNIT IN THE SPEC BOOK AS SHOWN ON
 PLANS. THIS WILL AFFECT THE FUEL SUPPLY, AND THE FUEL
 LINE SUPPLY FOR THE PROPOSED NATURAL GAS LINE. 90.7,
 110.3,
 FBC 106.1.2
  
 55) NOTE: OK.
  
 56) NOTE: OK.
  
 57) NOTE:OK/NO, PLEASE SEE PREVIOUS COMMENT WITH
 RESPECT TO HOW THIS WILL ACTUALLY BE DESIGNED AND
 INSTALLED. THIS COMMENT WILL REMAIN AT THIS TIME AS A
 REMINDER.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE SOME BATHROOMS CONTAIN OC SENSORS AND MANY
 DO NOT, PLEASE EXPLAIN AND PLEASE SEE OTHER COMMENTS
 FOR TYPE OF DEVICES WHICH WILL BE REQUIRED.
 13-415.1.ABC.1.2
  
 58) NOTE: NO, PLEASE SEE MOST WERE DONE, HOWEVER PLEASE
 SEE 2-2.2, 2-3.1,2-4.2 AND ANY OTHER LARGER BATHROOMS
 OTHER THAN A SINGLE POINT OF USE OCCUPIED ROOM.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW SOME SORT OF BATTERY BACK UP FIXTURE WILL
 BE REQUIRED IN THE LARGER BATHROOMS (ROOM OTHER THAN
 SINGLE POINT OF USE).
 PLEASE SEE LS 101 7.8., 7.9
 THIS WAS DISCUSSED WITH THE FIRE MARSHAL CHIEF AND WILL
 BE REQUIRED BOTH BY THIS OFFICE AND THE FIRE MARSHAL'S
 OFFICE IN THE INTEREST OF LIFE SAFETY AND CODE AS
 REFLECT.
  
 59) NOTE: OK.
  
 60) NOTE: OK.
  
 61) NOTE: NO, PLEASE SEE RESPONSE MENTIONS MINIMUM
 LIGHTING REQUIRED FOR EGRESS, HOWEVER PLEASE KNOW THE
 AREA OF THE LOBBY AFTER HOURS WOULD REQUIRE OVER RIDE
 FOR NORMAL LIGHTING. ONLY WOULD THEY NEED THESE
 FIXTURES TO BE BATTERY BACK UP FOR AN EMERGENCY. THIS
 WAS DISCUSSED WITH THE DESIGNER, HOWEVER THE NUMBER OF
 FIXTURES EXCEED ANY REASONABLE AMOUNT PERMITTED TO BE
 LEFT ON FOR THE EXCEPTIONS AS PERMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THERE ARE SOME LOCATIONS ON PLANS WHICH ARE
 SHOWING "NL'S" (NIGHT LIGHTS) BEING PART OF A PERMANENT
 ON SCENARIO; HOWEVER THE NUMBERS OF FIXTURES BEING
 PROPOSED TO REMAIN ON AS NIGHT LIGHTS ARE OVER WHAT IS
 BEING CONSIDERED AS NORMAL. PLEASE KNOW THIS CAN BE
 GONE OVER, HOWEVER PLEASE SEE SOME AREAS WHERE THERE
 ARE 10-20PLUS LIGHTS BEING LEFT ON.
 THE INTENT OF CHAPTER 13 AND ALSO THE INTEREST OF LIFE
 SAFETY SHOULD BE CONSIDERED. PLEASE CALL TO OVER. SEE
 SHEET E2-1.2 FOR EXAMPLE IN LOBBY AREA.
  
 62) NOTE:NO/OK, PROJECT MANUALS ARE TO BE REVIEWED
 FOR ALL OF THESE ITEMS AND DOCUMENTATION WILL BE
 REQUIRED BEFORE FINAL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NFPA-20 11.3, 11.3.2, 11.3.2.3 AND FLORIDA
 FIRE PREVENTION CODE , NFPA-1 7-4FOR OTHER REQUIREMENTS
 FOR FIRE PUMPS AND ROOMS IN WHICH THEY ARE LOCATED.
 PLEASE ALSO SEE 11.4.6.2 FUEL PIPING SHALL NOT BE
 GALVANIZED STEEL OR COPPER.
 PLEASE KNOW AS PART OF THE COMPLETED TESTING AND
 ACCEPTANCE AS REQUIRED IN CHAPTER 14, DOCUMENTATION FOR
 TESTING FOR FIRE PUMP ON A WEEKLY BASIS IS REQUIRED TO
 THE OWNER OF RECORD.CODE TEXT FROM NFPA-20: 11.6.1.1
 ENGINES SHALL BE STARTED NO LESS THAN ONCE A WEEK AND
 RUN FOR NO LESS THAN 30 MINUTES TO ATTAIN NORMAL
 RUNNING TEMPERATURE.
  
 63) NOTE:NO, RESPONSE MENTIONS INFORMATION GIVEN TO
 ARCHITECT AND STRUCTURAL ENGINNER WHICH IS OK, HOWEVER
 COULD NOT LOCATE ANY INFORMATION OR DETAIL FOR THIS.
 THIS UNIT AND ITS SIZE IS BEING PLACED ON THE ROOF OF
 THE GARAGE AND IT IS OF THE UTMOST IMPORTANCE THAT THE
 INFORMATION IS PROVIDED A THIS TIME AS IT MAY AFFECT
 PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NFPA-110 CHAPTER 7 FOR THE INSTALLATION OF
 THE GENERATOR. PLEASE SEE 7.4 AND 7.5, PROVIDE DETAIL
 FOR MOUNTING OF UNIT TO ALLEVIATE ANY INTEGRITY
 INTERFERENCE OF THE STRUCTURE.
  
 64) NOTE: NO, PLEASE SEE THE SAME SPECS WHICH CONTAIN
 HAND WRITTEN INFORMATION WAS SUBMITTED BACK FOR REVIEW.
 PLEASE KNOW, THIS SYSTEM AS SUBMITTED IS NOT ACCEPTABLE
 TO THIS AHJ WITHOUT THE FAIL SAFE OPERATION TO
 COMPLETELY PREVENT INADVERTENT SIMULTANEOUS OPERATION.
 PLEASE KNOW THERE ARE NUMEROUS OF THE TYPES OF SYSTEMS
 ON THE MARKET WHICH WILL PERMIT BOTH SIDE BEING ON AT
 THE SAME TIME. PLEASE KNOW AS PER KNOWLEDGE OF THIS
 REVIEWER MR. MARK ODE FROM UL WAS IN DISCUSSION WITH
 SAID COMPANY TO START WITH THE PROCEEDINGS TO HAVE
 THEIR EQUIPMENT LISTED AS TRANSFER EQUIPMENT PER UL
 1081. PLEASE KNOW AT THIS TIME, EITHER PROVIDE THE
 NEEDED INFORMATION OR CHANGE EQUIPMENT TO AN ACCEPT
 UNIT WHICH IS LISTED BY A NRTL. (NATIONALLY RECOGNIZED
 TESTING LABORATORY).
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE SPEC/CUT SHEET FOR THE PROPOSED MTS.
 THE "KIRK KEY" AS SHOWN AND HAND WRITTEN ON SPECS IS
 NOT ACCEPTED AT THIS TIME. THERE ARE MANY OF THESE
 SYSTEMS ON THE MARKET WHICH WILL PERMIT THE POWER FROM
 TWO SOURCES AT ONCE WHICH IS STRICTLY PROHIBITED.
 PLEASE SEE 700.6, 701.7, 110.3, AND 90.7 CAN NOT VERIFY
 AT THIS TIME. PLEASE ALSO SEE THE FOLLOWING COMMENT.
  
 65) NOTE: NO/OK, PLEASE SEE SPECS SUBMITTED INDICATE
 4-POLE UNITS, HOWEVER EACH ATS ON RISER WHEN SUBMITTED
 FOR THE 90% REVIEW CONTAINED DESIGNATION NEXT TO EACH
 UNIT TO BE 4-POLE. PLEASE PLACE THIS MEANS OF
 IDENTIFICATION/DESIGNATION ON RISER AT THIS TIME TO
 AVOID ANY CONFUSION OF WHAT TYPE OF UNITS ARE TO BE
 INSTALLED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE RISER AND PLANS WERE REVISED FROM THE 50%
 AND 90% PLANS CHANGING ALL ATS UNITS TO 3-POLE UNITS.
 PLEASE SEE ALTHOUGH GF PROTECTION IS NOT REQUIRED ON
 THE EMERGENCY SIDE OF THE EMERGENCY SYSTEM AND LEGALLY
 REQUIRED SYSTEMS, PROPER GROUND FAULT SENSING IS
 REQUIRED. PLEASE KNOW DOCUMENTATION FROM MORE THAN ONE
 MANUFACTURE WAS SENT TO THE ENGINEER PRIOR TO THE
 REVIEW WHEN THE PLANS WERE SUBMITTED ON THE 7TH OF NOV.
 PLEASE SEE NFPA-110 6.2.15** ISOLATION OF NEUTRAL
 CONDUCTORS. PROVISIONS SHALL BE INCLUDED FOR ENSURING
 CONTINUITY, TRANSFER, AND ISOLATION OF THE PRIMARY AND
 THE EPS NEUTRAL CONDUCTORS WHEREVER THEY ARE SEPARATELY
 GROUNDED TO ACHIEVE GROUND-FAULT SENSING.
 PLEASE SEE AN ATTACHED BRIEF EXPLANATION FROM"ASCO"
 WHITE PAPER: WHERE GROUND FAULT PROTECTION IS TRIGGERED
 BY THE CODE AND AN ALTERNATE POWER SUPPLY IS INCLUDED,
 SWITCHING OF THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT
 SHOWN ABOVE ILLUSTRATES SUCH A CIRCUMSTANCE. THE
 SERVICE IS LARGER THAN 1,000 AMPS. CONSEQUENTLY, GROUND
 FAULT PROTECTION IS REQUIRED AT THE MAIN SERVICE
 DISCONNECT AT A MINIMUM. IF IT IS INSTALLED THERE AND
 THE GENERATOR NEUTRAL GROUNDING WAS THROUGH A SOLID
 CONNECTION TO THE MAIN SERVICE NEUTRAL, A GROUND FAULT
 WHEN THE GENERATOR IS FEEDING THE LOAD WILL CAUSE THE
 MAIN SERVICE DISCONNECT TO OPEN. THIS WILL NOT
 DISCONNECT THE ARCING FAULT FROM THE GENERATOR.
 COORDINATION IS THUS LOST."
 PLEASE KNOW BASED ON THE INFORMATION FROM SEVERAL
 MANUFACTURES AND THE CODE PLEASE ADJUST AS REQUIRED.
 PLEASE ALSO SEE GENERATOR GROUNDING DETAIL WILL BE
 REQUIRED TO BE REVISED.
 PLEASE SEE E5-1.1.18 WHICH NOTES A #3 CONDUCTOR, WHICH
 WOULD NOT BE LARGE ENOUGH.
 PLEASE SEE 250.20, 250.30, 250.66, 240.13, 230.95,
 700.7D, 700.26
 PLEASE SEE THE MTS.
  
 66) NOTE: OK, HOWEVER PLEASE SEE SOME OF THESE ARE
 BEING SHOWN ATTACHED DIRECTLY TO CIRCUITS WHICH SEEMED
 TO BE CONTROLLED BY LIGHTING CONTROL SYSTEM OR DEVICES.
 THE NOTES ON PLANS MENTION TO BE SURE TO CONNECT AHEAD
 OF ANY CONTROL OR SWITCHING DEVICES HOWEVER PLEASE
 VERIFY THIS ON THE PLANS AT THIS TIME AS SHOWN. PLEASE
 SEE THERE ARE STILL SOME EXIT LIGHT FIXTURES ON PLANS
 WHICH STILL DO NOT SHOW ANY CONNECTION TO LOCAL
 CIRCUITS E2-3.2,E2-4.2
  
 PLEASE SEE THERE ARE MANY EXIT/EMERGENCY LIGHTS WHICH
 DO NOT SHOW ANY CONNECTION TO ANY LOCAL CIRCUIT IN
 ANYWAY. PLANS NOTE THIS AND MANY ARE SHOWN THIS WAY,
 HOWEVER NOT ALL. PLEASE GO THROUGH PLANS. PLEASE SEE
 700.12E WHICH REQUIRES THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES.
  
 67) NOTE:NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE OVER ALL 3RD FLOOR PLANS, WHICH SEEM TO BE
 SHOWING LIGHTING OF SOME KIND ON GARAGE PLANS? PLEASE
 ALSO SEE E2-4.0
 FBC 106.1.2 ADMIN SECTION.
  
 68) NOTE: NO, PLEASE SEE THE LOCATION AS SHOWN WOULD
 NOT BE AN ACCEPTABLE LOCATION. PLEASE THE RUNNING OF
 CABLES IN THE EGRESS PATH IS NOT PERMITTED IN FRONT OF
 DOOR WAYS AND ANY OTHER EGRESS PATHS. PERHAPS CONDUITS
 TO A J-BOX OF SOME TYPE TO THE OUTSIDE WALL ON THE
 NORTH SIDE OF BUILDING. PLEASE KNOW TRIPPING HAZARDS
 UNDER THE REQUIREMENTS IN THE CODE FOR TEMPORARY
 INSTALLATIONS IS STILL NOT PERMITTED. PLEASE SECTIONS
 AS PREVIOUSLY GIVEN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NOTE #2 ON RISER WITH RESPECT TO THE MTS
 WHICH IS TO PROVIDE FUTURE PROVISIONS FOR POSSIBLE
 PORTABLE GENERATOR TO RUN THE EMERGENCY SYSTEMS, PLEASE
 KNOW A DETAIL TO A LOCATION AND HOW THIS CONNECTION
 WILL BE MADE IS REQUIRED.THE RUNNING OF CORDS,
 CONDUCTORS ETC SHALL BE PERMITTED TO TRAVEL THROUGH THE
 ELECTRICAL ROOM DOORS, ON SIDEWALK AREAS OR ANY
 LOCATIONS PROVIDING A TRIPPING HAZARD OR NOT SECURING
 LIVE PARTS ETC.
 PLEASE PROVIDE A DETAIL AS THIS CONNECTION POINT WILL
 BE SUBSTANTIAL IN NATURE. (J-BOX) ETC ON THE OUTSIDE OF
 BUILDING ETC.
 110.26, 110.27, NEC 527.
  
 69) NOTE: OK.
  
 70) NOTE: OK.
  
 71) NOTE: OK, PLEASE KNOW ALL LOW VOLTAGE WILL NOT BE
 INCLUDED IN THIS PERMIT. NOTE WILL REMAIN ONLY AS
 INFORMATION AS TO WHAT WILL BE REQUIRED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW IF IT IS THE INTENT TO UTILIZE THESE PLANS
 FOR FUTURE LOW VOLTAGE WORK FOR LOCATIONS OF PHONE,
 DATE DROP ETC, PLEASE COMPLETE PLANS AS SUBMITTED
 SHOWING ALL LOCATIONS FOR DROPS.PLEASE SEE MANY AREAS
 WHICH LOW VOLTAGE DATE/PHONE DROPS WILL BE REQUIRED OR
 INSTALLED, HOWEVER THESE LOCATIONS ARE NOT BEING SHOWN
 AT THIS TIME.
 IF THE LV SCOPE IS PART OF THE PERMITTED PLANS AS
 SUBMITTED PLEASE REMOVE AND NOTE AS UNDER SEPARATE
 PERMIT PLANS AND FEES.
  
 72) NOTE: OK.
  
 73) NOTE:OK/NO, PLEASE SEE PREVIOUS NOTE #47, WHERE
 THE DETAIL FOR THE FEEDERS IN GARAGE WAS NOT PROVIDED.
 THE DETAIL FOR UNDERGROUND IS OK.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 700.9D FOR THE FEEDERS FROM THE GENERATOR TO
 THE EMSB1 AND THE FEEDERS OUT TO SYSTEMS WHICH MAY BE
 CONSIDERED INSIDE THE BUILDING. PLEASE SEE THE CODE AS
 THERE ARE WAYS TO MEET THE INSTALLATION OF THESE
 FEEDERS, HOWEVER PLANS SHALL INDICATE WHICH WILL BE
 USED. (TYPE OF CABLE, ENCASED IN 2INCHES OF CONCRETE,
 FULLY SPRINKLED ETC)
 PLEASE KNOW AS THE REQUIREMENT OF FULLY SPRINKLED IS
 OFTEN MISTAKEN AS A BUILDING CONTAINING SPRINKLERS.
 THIS IS NOT THE CASE. PLEASE SEE THE INTENT OF 700.9D
 FOR THIS HAS ALWAYS BEEN THAT ALL AREAS CONTAINING
 THESE FEEDERS BE SPRINKLED IF INSTALLED IN OPEN OR
 ABOVE CEILINGS. PLEASE KNOW A COMMENTARY IN THE 2005
 NEC MAKES IS CLEAR WHAT THE INTENT OF THE CODE AND THE
 FURTHER EXPLANATION IS PROVIDED.
  
 74) NOTE: OK.
  
 75) NOTE: OK..
  
 76) NOTE: NO, COULD NOT LOCATE. RESPONSE MENTIONS TO
 SEE SHEETS; HOWEVER THIS WAS REQUESTED FOR RISER TO
 SHOW THIS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE THE SIZE OF THE CONDUCTOR ON THE
 GROUNDING ELECTRODE RISER AS PROVIDED. PLEASE SEE THE
 GROUNDING ELECTRODE DETAIL SHOWS A 4/0'S, HOWEVER
 PLEASE SEE E5-2.0.
 250.50, 250.58
  
 77) NOTE: NO, PLEASE SEE RESPONSE MENTIONS ALL
 TERMINATE IN OCP. YES, THIS IS TRUE, HOWEVER AS STATED
 IN PREVIOUS REVIEW PER 240.21C THE OCP SHALL LIMIT THE
 LOAD ON CONDUCTORS.
 PLEASE SEE E5-1.0 WHICH SHOWS A 45KVA TRANSFORMER, WHEN
 E6-1.0 SHOWS 1/0'S FOR THE TYPICAL 45 KVA TRANSFORMER
 ON THE SECONDARY SIDE, THIS WOULD MEAN THE OCP WOULD BE
 LIMITED TO 150A?S. PLEASE SEE 6-1.0 FOR 1LD2 WHICH
 INDICATES 225A OCP AS THE SECONDARY MCB. PLEASE SEE
 6-7.0 1HD WHICH SHOWS 1/0'S ON THE SECONDARY SIDE OF
 THE FEEDERS.
 PLEASE ADJUST.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE SIZE OF THE CONDUCTORS ON THE SECONDARY
 SIDE OF ANY TRANSFORMER SHALL BE SIZED AND TERMINATE IN
 OVER-CURRENT PROTECTION WHICH LIMITS THE LOAD ON THE
 CONDUCTORS. PLEASE SEE 240.21C, 310.16. PLEASE SEE
 1LD2
  
 78) NOTE: OK.
  
 79) NOTE: NO, PLEASE CLARIFY WHERE CONTINUOUS LOADS AND
 LARGEST MOTOR LOADS ARE SHOWN AT 125%.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT LOAD CALCULATIONS. PLEASE INDICATE AND
 SHOW ALL CONTINUOUS LOADS AND LARGEST MOTOR LOADS AT
 125%.
 220.3, 220.10, 220.11, 220.13, 215.3,230.42 ETC
  
 80) NOTE: OK.
  
 81) NOTE:NO, PLEASE KNOW BASED ON THE PREVIOUS NOTES
 ABOVE WITH RESPECT TO PHOTO-METRICS, THIS COMMENT WILL
 REMAIN DUE TO POSSIBLE CHANGES IN PLANS.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PREVIOUS NOTES WITH RESPECT TO MINIMUM FOOT
 CANDLES REQUIRED. PLEASE SEE GARAGE SHALL CONTAIN
 EGRESS PATHS WHICH MEET THIS MINIMUM. BASED ON SOME
 AREAS SHOWN ON PHOTO-METRICS, IT DOES NOT APPEAR THIS
 IS MET.
 PLEASE SEE LIFE SAFETY CODE NFPA-101 2003 7.8.1.3,
 7.9.2.2
  
 82) NOTE: OK.
  
 83) NOTE:NO/OK, PLEASE SEE MOST WERE DONE, HOWEVER
 PLEASE SEE ROOM A1.507 WHICH SHOWS 75K ON RISER AND 45K
 ON ROOM PLANS.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE CORRELATE THE TRANSFORMERS ON THE ELECTRICAL
 ROOM LAYOUTS AND THE ELECTRICAL RISER. PLEASE SEE THERE
 ARE MANY WHICH ARE SHOWN AS 15KVA ON ONE SHEET AND
 45KVA ON OTHER SHEETS OR 45KVA ON ONE AND 75KAV ON
 ANOTHER. PLEASE ALSO SEE RISER.
 PLEASE SEE SOME BELOW AS NOTED, THIS IS ONLY SOME AND
 IS IN NO WAY ALL POSSIBLE.
 1HB, 75KVA ON RISER, 45KVA IN ELECTRICAL ROOM. 2HB,
 75KVA ON RISER, 45KAV IN ELECTRICAL ROOM. 1GLA-1GHA,
 45K ON RISER, 15K ON ELECTRICAL ROOM PLANS. ETC
  
 84) NOTE: OK,
  
 85) NOTE: NO, PLEASE SEE NOTE NOTES COULD BE LOCATED ON
 FA SHEETS, IN FACT SHEETS STILL ONLY NOTE NFPA72 FOR
 LEVELS.
 PLEASE ADJUST ALL SHEETS AND NOTES ACCORDINGLY AS
 PREVIOUSLY REQUESTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC 2004 CHAPTER 11 FOR REQUIREMENTS FOR ADA
 WITH RESPECT TO HORNS, AND STROBES. THE AUDIBLE LEVELS
 SHALL BE PER BOTH FBC CHAPTER 11 AND NFPA-72 AS NOTED,
 HOWEVER THE MORE STRINGENT SHALL APPLY.
 PLEASE SEE 11-4.28.1, 11-4.28.2 AND 11-4.28.3(4).
 PLEASE BE SURE THE LEVELS ARE INDICATED ON PLANS.
 PLEASE KNOW THE LIGHTING CANDELA LEVELS AS REQUIRED IN
 THE FBC ARE FAR GREATER THAN THAT OF NFPA-72. THE
 MINIMUM LEVELS FOR VISUAL SHALL BE 75 CANDELAS. PLEASE
 ADJUST AND PLACE REQUIREMENTS ON PLANS. PLEASE SEE ALL
 FA SHEETS WHICH ONLY INDICATE NFPA-72.
  
  
 86) NOTE:OK, PLEASE DO THE SAME. NOTE WILL REMAIN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW A RESPONSE LETTER/NOTES WERE PROVIDED,
 HOWEVER AS THIS REVIEW WAS MORE OF A REVIEW FOR CODE
 COMPLIANCE, A MORE DETAILED RESPONSE WOULD GREATLY HELP
 IN THE REVIEW PROCESS. THIS RESPONSE COULD INDICATE THE
 SHEETS/LOCATIONS OF CHANGES, CORRECTIONS OR ANY
 COMMENTS RELATED TO AND RESPECT TO THIS REVIEWERS
 NOTES.
  
 ********** NEW NOTES FOR THIS REVIEW************
  
 87) NOTE: PLEASE SEE FLORIDA STATUTES WITH RESPECT TO
 THE ENGINEER OF RECORD SIGNING AND SEALING DOCUMENTS IN
 471.025. PLEASE SEE SHEETS SIGNED OTHER THAN MR. MINDUR
 CONTAINS WHAT APPEARS TO BE MORE THAN ONE SIGNATURE FOR
 THE SAME ENGINEER. PLEASE KNOW AS STATED BY THE
 PLUMBING REVIEWER FOR PLUMBING SHEETS, THE SAME APPLIES
 TO FS SHEETS AND OTHER DOCUMENTS SIGNED AND SEALED.
 PLEASE KNOW UNTIL LEGAL SIGNATURE VERIFICATION CAN BE
 DONE, THE ENERGY CALCULATIONS WHICH ARE SIGNED AND
 SEALED ALSO BY OTHER THAN MR. MINDUR CAN NOT BE
 ACCEPTED AT THIS TIME.
 FAC 61G15-23.002
 PLEASE BE SURE LETTER FOR LEGAL SIGNATURE VERIFICATION
 FOR MR. WU IS CORRECTLY NOTARIZED PER FLORIDA STATUTES
 117.05.
  
 88) NOTE: PLEASE KNOW AS COMMENTS FROM ELECTRICAL
 ENGINEER MENTIONED TO SEE S SHEETS FOR INFORMATION,
 UPON REVIEW OF SAID SHEETS THIS REVIEW NOTICE MANY
 SHEETS WHICH WERE DATED IN DECEMBER NOT CONTAINING ANY
 TITLE BLOCKS FOR THE ENGINEERING FIRM OF RECORD. PLEASE
 SEE SOME SHEETS WHICH WERE DATED FROM OCTOBER WHICH DO
 CONTAIN THE TITLE BLOCKS FOR FIRM DO NOT CONTAIN THE
 CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED UNDER
 FS 471.023 AND FAC 61G15-23.002. THIS IS REQUIRED FOR S
 SHEETS WHETHEROR NOT COMMENT IS MADE BY ANY OTHER
 TRADE.
  
 89) NOTE: PLEASE SEE ENERGY CALCULATIONS WHICH ARE NOW
 SUBMITTED ONLY INDICATE 3 FIXTURES FOR EXTERIOR
 LIGHTING? HOW IS THIS POSSIBLE? PLEASE CORRELATE WITH
 PLANS AND FIXTURES AS SHOWN ON PLANS.
 PLEASE ALSO CORRELATE WITH THE WATTAGES AS SHOWN ON
 LIGHTING POWER DENSITIES AND PLANS.
 PLEASE CLARIFY ZONES IN ENERGY CALCULATIONS AS SHOWN.
 PLEASE SEE FBC 13-415.1.AB.1, 13-415.2
  
 90) NOTE: PLEASE SEE NOTES ON LIGHTING SEQUENCE OF
 OPERATION SHEETS. PLEASE SEE NOTE #11 ON E5-3.0 WHICH
 MENTIONS PHOTO-CELL FOR CONTROL OF ROOMS? PLEASE SEE
 THE SAME ROOMS AND NOTE #3 ON 5-3.1 WHICH MENTIONS
 DIFFERENT CONTROLS.
  
 91) NOTE: PLEASE SEE WATER COOLERS LOCATIONS OF
 RECEPTACLES. PLEASE SEE MANY INDICATE THE RECEPT TO BE
 LOCATED AT THE CEILING LEVEL AND MANY INDICATE AT WC
 LEVEL. PLEASE EXPLAIN THE INDICATION FOR DEVICE AT
 CEILING. PLEASE ALSO SEE AREAS WHERE MORE THAN TWO
 WATER COOLERS ARE BEING SHOWN HOWEVER ONLY ONE DUPLEX
 RECEPT IS BEING SHOWN. PLEASE ADJUST TO QUAD AND PLEASE
 VERIFY LOAD ON THESE UNITS WHICH ARE NOT TO EXCEED
 RATING OF DEVICE AND CIRCUIT. THIS WAS NOT COMMENTED ON
 THE PREVIOUS REVIEW.
 240.4, 310.16, 210.25, 2210.21B2 ETC.
  
 92) NOTE: PLEASE PLACE NOTE ON E0-2.1 FOR SECTIONS OF
 314PART IV , SECTIONS 314.50-314.59 TO BE MET.
 NOT ON PREVIOUS REVIEW.
  
 93) NOTE: PLEASE SEE UPON REVIEW OF PROJECT MANUAL,
 PLEASE SEE COLOR CODING SHALL BE BROWN, PURPLE, YELLOW
 FOR 277/480V SYSTEMS. PLEASE SEE THE CODE DOES NOT
 PROVIDE COLOR CODING FOR MOST SYSTEMS, HOWEVER ORANGE
 AS BEING NOTED FOR THIS IS FOR A HIGH-LEG SYSTEM WHICH
 IS NOT WHAT IS BEING INSTALLED. PLEASE KNOW AS PER
 LOCAL AMENDMENTS FOR 3 DECADES OR SO UNDER THE 2004 FBC
 THE CITY OF WEST PALM BEACH ALONG WITH PALM BEACH
 COUNTY HAD THIS COLOR SCENARIO FOR 277/480V SYSTEMS AND
 WILL BE REQUIRED TO REMAIN THE SAME FOR ALL OTHER
 BUILDING BEING PROPOSED. PLEASE PLACE A NOTE ON RISER
 FOR COLOR CODING.
 90.4., FBC ADMIN SECTION 104.6
  
 94) NOTE:PLEASE SEE BUILDING REVIEW NOTES AND
 CLARIFY THE TWO PULL BOXES BEING SHOWN ON E0-2.1 WHICH
 SEEM TO BE DIRECTLY LOCATED IN THE WALL OR FOOTER.
 PLEASE CLARIFY THESE AT THE LOCATIONS AS SHOWN AND
 PLEASE ADJUST PLANS AS NEEDED. PLEASE SEE CODE FOR
 ACCESSIBILITY.
 110.26
  
 95) NOTE: PLEASE CLARIFY THE FUEL TANK ROOM AS BEING
 SHOWN ON THE GARAGE PLANS NEXT TO THE FIRE PUMP ROOM.
 PLEASE KNOW IT WAS BEING ASSUMED THIS WAS THE LOCATION
 OF THE TANK FOR THE FIRE PUMP; HOWEVER IT HAS COME TO
 OUR ATTENTION THAT THIS IS NOT THE CASE. PLEASE PROVIDE
 INFORMATION FOR THIS FOR MECHANICAL AND FIRE REVIEW AS
 WELL AS ELECTRICAL REVIEW. PLEASE SEE NEC 500. SPECIFIC
 SECTIONS CAN NOT BE GIVEN AT THIS TIME, AS THE USE AND
 RATING OF ROOM ETC IS NOT KNOWN AT THIS TIME.
 FBC ADMIN SECTION 106.1.2 (MORE INFORMATION). NFPA-70,
 72, 30? ETC.
  
 96) NOTE: PLEASE SEE ELEVATOR EQUIPMENT ROOM
 DISCONNECTS ARE BEING SHOWN WITH 3-WAY SWITCH NOTATIONS
 INSTEAD OF DISCONNECTS OR MOTOR RATED SYMBOL.
 NOT ON PREVIOUS REVIEW.
 PLEASE ADJUST. 620.51, 620.61, 620.62 ETC
 FBC 106.1.2,
  
 97) NOTE: PLEASE SEE ANY HAND DRAWN CHANGES WHICH MAY
 HAVE BEEN DONE BY THE ENGINEER AFTER PLANS WERE SIGNED,
 DATED AND SEALED, SHOULD BE REVISED AT THIS TIME. ONLY
 THE ENGINEER OF RECORD MAY MAKE CHANGES TO SAID PLANS
 WHICH ARE SIGNED AND SEALED. FS 471.025 PLEASE KNOW AS
 PLANS ARE SEALED, MANY OF THE SEALS ARE NOT CLEAR AND
 VISIBLE WITH INFORMATION ON SAID SEAL. PLEASE BE SURE
 PLANS ARE SEALED TO SEE INFORMATION. FS 471.025
  
  
 IF ANY OF THESE COMMENTS ARE NOT CLEAR IN ANY FASHION
 OR IF ANY ITEMS ARE NOT UNDERSTOOD IN ANY WAY?PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
  
 ** PLEASE KNOW AS THERE IS SOME INFORMATION NOT YET
 SUBMITTED PLEASE BE SURE TO GO OVER ALL.
  
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. ONCE AGAIN IF THERE
 ARE ANY QUESTIONS , PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-12-25 08:06:402006-12-25 08:06:40
 IN PROGRESS
2006-12-24 20:14:292006-12-24 20:14:29
 REVIEW STOPPED. TO CONTINUE ON 12/25
2006-12-24 18:11:342006-12-24 18:11:34
 ONE ROLL OF MEP'S IN ELECTRIC FOR REVIEW ALONG WITH ONE
 COPY OF RESPONSE LETTERS AND ONE COPY OF SUBMITTIALS
 FOR REVIEW.
 REVIEW IN PROGRESS.