2008-08-29 13:57:45 | REVISIONS DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| NFPA-101 |
| |
| 1. SHTS P1-1.0 & P1-1.0U. REVISION 12A NOT FOUND, NOT |
| CLOUDED. REVISION NUMBER SHALL BE LEGIBLE ON FLOOR |
| PLAN. ALL REVISIONS SHALL BE CLOUDED. SEE COMMENT 3 |
| FROM PREVIOUS REVIEW. SECTION 106.1.3. |
| |
| 2. SHTS P1-1.0U, P1-1.0 & P1-1.2. SUBMIT A DETAIL FOR |
| THE PLANTER ON THE WEST SIDE OF THE COURTYARD. INDICATE |
| HOW THE STORM WATER AND THE CONDENSATE WILL NOT DRAIN |
| TO THE FOOTER AREA OF THE OUTSIDE WALL TO COMPLY WITH |
| SECTION 1503.6. BY HAVING THE PLANTER OPEN AT THE |
| BOTTOM, THE INTENT OF THE CODE IS NOT BEING MET. |
| |
| 3. SHTS P1-4.0, P1-4.2 & P3-7.0. PIPING FROM THE ROOF |
| DRAIN, (6" RD 1865SF), NOT APPROVED IN THE EXIT |
| STAIRWELL. NFPA 101 SECTION 7.1.3.2.1(6). |
| |
| 4. SHT P1-5.1. REVISION 193 SUBMITTED AND PLANS SIGNED, |
| SEALED & DATED ON 05-09-08 NOT SHOWN ON REVISION |
| SUBMITTED ON 08-21-08. ALSO CHANGES TO LATEST REVISION |
| ARE NOT CLOUDED NOR NUMBERED WITH A REVISION NUMBER. |
| (HUB DRAINS DELETED). SECTION 106.1.3. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |