2008-08-29 13:57:45REVISIONS DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 NFPA-101
  
 1. SHTS P1-1.0 & P1-1.0U. REVISION 12A NOT FOUND, NOT
 CLOUDED. REVISION NUMBER SHALL BE LEGIBLE ON FLOOR
 PLAN. ALL REVISIONS SHALL BE CLOUDED. SEE COMMENT 3
 FROM PREVIOUS REVIEW. SECTION 106.1.3.
  
 2. SHTS P1-1.0U, P1-1.0 & P1-1.2. SUBMIT A DETAIL FOR
 THE PLANTER ON THE WEST SIDE OF THE COURTYARD. INDICATE
 HOW THE STORM WATER AND THE CONDENSATE WILL NOT DRAIN
 TO THE FOOTER AREA OF THE OUTSIDE WALL TO COMPLY WITH
 SECTION 1503.6. BY HAVING THE PLANTER OPEN AT THE
 BOTTOM, THE INTENT OF THE CODE IS NOT BEING MET.
  
 3. SHTS P1-4.0, P1-4.2 & P3-7.0. PIPING FROM THE ROOF
 DRAIN, (6" RD 1865SF), NOT APPROVED IN THE EXIT
 STAIRWELL. NFPA 101 SECTION 7.1.3.2.1(6).
  
 4. SHT P1-5.1. REVISION 193 SUBMITTED AND PLANS SIGNED,
 SEALED & DATED ON 05-09-08 NOT SHOWN ON REVISION
 SUBMITTED ON 08-21-08. ALSO CHANGES TO LATEST REVISION
 ARE NOT CLOUDED NOR NUMBERED WITH A REVISION NUMBER.
 (HUB DRAINS DELETED). SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  