2008-05-05 19:53:11 | ** PROVISO ** | | | | ** THE BELOW IS TO HAVE PLANS REVISED AS SOON AS | | POSSIBLE. ANY INSTALLATIONS AND INSPECTIONS ARE AT | | RISK. PLANS ARE CODE COMPLIANT AT THIS TIME ****WITHOUT | | ANY NORMAL OCCUPANCY *** UNDER GENERATOR POWER. | | | | | | 1) NOTE: THIS REVIEWER ALONG WITH THE FIRE MARSHAL IS | | ONCE AGAIN STATING THE FACT THAT ALL LOCATIONS IN | | BUILDING WHICH MAY BE IN USE UNDER EMERGENCY POWER AS A | | NORMAL OCCUPANCY. THERE ARE SEVERAL LOCATIONS WHICH ARE | | ALREADY KNOWN TO THIS OFFICE WHICH WILL REQUIRE BATTERY | | BACK UP FIXTURES TO MEET MINIMUM LIGHTING LEVELS UNDER | | THE LIFE SAFETY CODE 7.8 AND 7.9. | | PLANS STILL NEED TO BE REVISED TO INCLUDE THE NEW | | FIXTURES FOR ALL AREAS. PLANS ARE STAMPED REVIEWED FOR | | INSPECTIONS OF OTHER AREAS OTHER THAN KNOWN LOCATIONS. | | THIS WILL BE AT CONTRACTOR RISK FOR ALL LOCATIONS | | INCLUDING ANY NEW AREAS ADDED. PLANS ARE CODE COMPLIANT | | AT THIS TIME WITHOUT ANY *NORMAL OCCUPANCY* UNDER | | GENERATOR POWER. | | | | ** IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS | | OFFICE/REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|