2007-09-02 08:48:58 | BUILDING PLAN REVIEW |
| PERMIT: 06100574 |
| ADD: 401 CLEMATIS ST |
| CONT: CATALFUMO |
| TEL: (561)307-4746 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVISION # 11-12REVIEW |
| ACTION: DENIED |
| |
| 1) GARAGE MAIN ELECTRIC ROOM B1.103THE FLOOR IS NOW |
| DROPPED DOOR B1-103-AIS INDICATED WITH A PAIR OF 3'-0" |
| OUTSWING DOORS AND A LANDING AND STAIR THAT IS ONLY |
| 3'-0" WIDE. |
| THE PLAN DOESN'T INDICATE THE PRESENCE OF A HANDRAIL |
| SYSTEM OR NOTE AS SUCH. THE PLAN ALSO INDICATES THE (2) |
| RISERS TO BE 6 7/16" INCHES AND TREAD DEPTH OF 11". |
| 1003.5.1 |
| WHERE A CHANGE IN LEVEL MEANS OF EGRESS NOT EXCEEDING |
| 21 INCHES (533 MM) IS ACHIEVED BY A STAIR, THE MINIMUM |
| TREAD DEPTH OF SUCH STAIR SHALL BE 13 INCHES (330 MM) |
| AND THE PRESENCE AND LOCATION OF EACH STEP SHALL BE |
| READILY APPARENT. |
| |
| 2)BOTH THE ELECTRIC ROOM AND MECHANICAL ROOM INDICATE |
| THE FLOOR SLAB IS NOW RECESSED 6" PLEASE PROVIDE THE |
| INFORMATION HOW **READILY APPARENT** WILL BE |
| ACCOMPLISHED IN SECTION 1003.5.1. |
| |
| 3) GARAGE MAIN ELECTRIC ROOM B1.103 DOOR B1-103-B IS AN |
| OUTSWING DOOR WITH AUTOMATIC CLOSER WITH LATCHSEE |
| A8-0.1 NOTES D & E AND SEE A8-0.2DOOR SCHEDULE. WITH |
| THE DOOR |
| HAVING A CLOSER AND LATCH THE LANDING ON THE INTERIOR |
| OF THE ROOM SHOULD EXTEND A MINIMUM OF 12" SEE |
| MANEUVERING CLEARENCE AT DOORS FIGURE 25(A) THE LANDING |
| WOULD NEED TO BE A MINIMUM OF 48" DEEP.11-4.13.6 |
| MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING |
| CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC OR |
| POWER-ASSISTED SHALL BE AS SHOWN IN |
| FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE REQUIRED |
| CLEARANCES SHALL BE CLEAR & LEVEL. |
| 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| REQUIREMENT, THE SPECIFIC |
| REQUIREMENT SHALL BE APPLICABLE. |
| |
| 4) SHEET S1-1.0THE EXTERIOR OF THE MAIN ELECTRIC ROOM |
| IN THE GARAGE PORTION OF THE PLAN INDICATES A SINGLE |
| 3'-0" DOORWAY WHERE AS THE ARCHITECTURAL SHEETS |
| INDICATE A PAIR OF DOORS. |
| PLEASE CORRELATE PLAN DETAILS.106.1.2*ADDITIONAL |
| INFORMATION REQUIRED. |
| |
| 5) ONE SET OF PLANS IS MISSING SHEET A1-GA.1 THERE ARE |
| (2) A1-GA.3 IN SET. |
| |
| BUILDING PLAN REVIEW |