Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop E
Sequence Number 18
Notes
Date Text
2008-03-25 15:54:45** DENIEDREVISIONS **
 CITY CENTER REV 15A ON LIGHTING SHEETS
  
 ** PLEASE SEE REDLINED PLANS AND NOTES BELOW AS THERE
 IS MUCH NEED OF COORDINATION WITH CIRCUITING FOR
 EMERGENCY AND EXIT LIGHTING.
 PLEASE ALSO SEE THAT COORDINATION IS ALSO NEEDED FOR
 OTHER NORMAL LIGHTING CIRCUITS.
 PLEASE SEE NOTES BELOW WITH RESPECT TO OCCUPATION OF
 BUILDING UNDER EMERGENCY POWER.
  
  
 1) NOTE: PLEASE SEE THAT PER ON-SITE MEETING BATHROOM
 LIGHTING WILL BE REQUIRED TO BE UPDATED.
  
 2) NOTE: PER ON-SITE AND CONVERSATIONS SEVERAL MONTHS
 AGO, IN AREAS OF BUILDING WHICH ARE GOING TO BE USED OR
 OCCUPIED FOR NORMAL OPERATING/CONDITIONS UNDER
 EMERGENCY POWER SHALL CONTAIN BATTERY BACK UP FIXTURES
 FOR THOSE AREAS FOR EGRESS AND EXISTING FROM BUILDING
 IN THE EVENT OF THE LOSS OF EMERGENCY GENERATOR.
 7.8, 7.9 LS 101 2003
 AREAS SUCH AS CALL CENTER AND EXITS, TRAINING ROOMS AND
 EGRESS, SERVER ROOM AND EGRESS, ETC
 PLEASE ALSO SEE STUDIO AND POLICE SUB-STATION ROOMS
 WHICH DO NOT SHOW ANY EMERGENCY LIGHTS ON EM CIRCUITS.
 THESE MAY NOT BE REQUIRED BY CODE, HOWEVER PLEASE
 VERIFY WITH OWNER THE INTENT OF USING THESE ROOMS.
  
 3) NOTE: PLEASE SEE THERE ARE NUMEROUS LOCATIONS ON
 PLANS IN WHICH CIRCUITING IS NON-EXISTENT, CIRCUITED TO
 OTHER CIRCUITS OR SOME OF THE SAME CIRCUITS IN
 DIFFERENT AREAS WHICH FEED THE SAME ITEMS.
 PLEASE SEE SOME OF THE ITEMS BELOW FOR EXAMPLE;
 THESE ARE IN NO WAY ALL LOCATIONS. PLEASE ALSO SEE SOME
 SHEETS ARE BEING NOTED BELOW AS MANY ROOM AND AREA
 DESIGNATIONS WERE REMOVED FROM PLANS.
 1HEB-5 AND 1HEB-3 TIED TOGETHER IN A1.804, A1.008.
 SEE 1HEA-2 AT A1.206 AND A1.302
 SEE 1HEA-6 AND HED-2 TIED TOGETHER
 SEE 1HED-4WHICH IS REPEATED, SEE AREAS D1.104,
 D1.005
 SEE 1HB-7 IN D1.201 SHOWN ON AS NORMAL CIRCUIT OR
 NOTING TO TIE TO.
 SEE 1HEC-3 AND 1HEC5 TIED TOGETHER.
 SEE CAF?, 1LC2, 8-10 AND 1LEC 6,8 TO SAME LIGHTS.
 SEE 2HEA-3 AND 2HEA-1 TIED TOGETHER ON SHEET E-2.2.1
 SEE EXIT LIGHT IN AREA A2.302 WHICH SHOWS NO CIRCUIT.
 SEE EXIT LIGHT AT DOOR IN FUTURE SPACE (SHELL AREA)
 WHICH NEEDS TO BE CIRCUITED PER 700.12E
 SEE AREA ON SHEET E2.3.2 *SUPPORT SPACE/FILE PRODUCTION
 AND CORRIDOR AREA IS MISSING CIRCUIT FOR EMERGENCY AND
 EXIT LIGHTS.
 SEE LIGHTING CONTROL IN SOME ROOMS SUCH AS PROGRAM
 MEETING ROOM WHICH SHOWS NORMAL OC DEVICE. THIS IS THE
 SAME IN OTHER LOCATIONS ALSO ONE SHEET E2.3.2/
 COLLECTION/ PROGRAM ROOM.
 SEE EMERGENCY AND EXIT LIGHTS IN ROOMS SUCH AS A4.420,
 4.419,4.421 ETC WHICH DOES NOT SHOW ANY CIRCUIT.
 SEE THIS SAME LOCATION AS THERE ARE SWITCHES LOCATED IN
 THE MIDDLE OF THE *AIR* AND NOT LOCATED ON ANY WALL.
 SEE 4HEB-1 IN A4.416 WHICH SHOWS THIS BEING TIED TO
 NORMAL AND EMERGENCY LIGHTS.
 SEE EMERGENCY LIGHTS/EXIT LIGHTS OUTSIDE A4.304 WHICH
 DOES NOT SHOW CIRCUIT. (PUBLIC UTILIZES AREA 03)
 SEE A5.531, EMERGENCY NOT CONNECTED.
 SEE A5.508, 5.505 ETC WHICH DOES NOT SHOW ANY CIRCUITS
 FOR EMERGENCY LIGHT FIXTURES.
 SEE 5HA-17 WHICH IS SHOWN TIED TO EMERGENCY LIGHTS AND
 NOT NORMAL LIGHTING.
 SEE A5.401 AND AREA WHICH INDICATES EMERGENCY AND EXIT
 LIGHTS WITH NO CIRCUITS.
 SEE A5.412 WHICH SHOWS NORMAL CIRCUIT TIED TO EMERGENCY
 LIGHT.
 SEE A5.503,504,505, A5.413 EMERGENCY AND EXIT LIGHTS
 WITH NO CIRCUITING.
  
 ** PLEASE SEE THAT MANY OF THE AREAS ABOVE ARE NOTED
 HOWEVER AS STATED ABOVE ARE IN NO WAY ALL POSSIBLE
 LOCATIONS.
 SEE REDLINED AND HIGHLIGHTED PLANS AS MOST OF THESE
 AREAS INDICATE THE NOTES ABOVE.
  
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]