2008-03-25 15:54:45 | ** DENIEDREVISIONS ** |
| CITY CENTER REV 15A ON LIGHTING SHEETS |
| |
| ** PLEASE SEE REDLINED PLANS AND NOTES BELOW AS THERE |
| IS MUCH NEED OF COORDINATION WITH CIRCUITING FOR |
| EMERGENCY AND EXIT LIGHTING. |
| PLEASE ALSO SEE THAT COORDINATION IS ALSO NEEDED FOR |
| OTHER NORMAL LIGHTING CIRCUITS. |
| PLEASE SEE NOTES BELOW WITH RESPECT TO OCCUPATION OF |
| BUILDING UNDER EMERGENCY POWER. |
| |
| |
| 1) NOTE: PLEASE SEE THAT PER ON-SITE MEETING BATHROOM |
| LIGHTING WILL BE REQUIRED TO BE UPDATED. |
| |
| 2) NOTE: PER ON-SITE AND CONVERSATIONS SEVERAL MONTHS |
| AGO, IN AREAS OF BUILDING WHICH ARE GOING TO BE USED OR |
| OCCUPIED FOR NORMAL OPERATING/CONDITIONS UNDER |
| EMERGENCY POWER SHALL CONTAIN BATTERY BACK UP FIXTURES |
| FOR THOSE AREAS FOR EGRESS AND EXISTING FROM BUILDING |
| IN THE EVENT OF THE LOSS OF EMERGENCY GENERATOR. |
| 7.8, 7.9 LS 101 2003 |
| AREAS SUCH AS CALL CENTER AND EXITS, TRAINING ROOMS AND |
| EGRESS, SERVER ROOM AND EGRESS, ETC |
| PLEASE ALSO SEE STUDIO AND POLICE SUB-STATION ROOMS |
| WHICH DO NOT SHOW ANY EMERGENCY LIGHTS ON EM CIRCUITS. |
| THESE MAY NOT BE REQUIRED BY CODE, HOWEVER PLEASE |
| VERIFY WITH OWNER THE INTENT OF USING THESE ROOMS. |
| |
| 3) NOTE: PLEASE SEE THERE ARE NUMEROUS LOCATIONS ON |
| PLANS IN WHICH CIRCUITING IS NON-EXISTENT, CIRCUITED TO |
| OTHER CIRCUITS OR SOME OF THE SAME CIRCUITS IN |
| DIFFERENT AREAS WHICH FEED THE SAME ITEMS. |
| PLEASE SEE SOME OF THE ITEMS BELOW FOR EXAMPLE; |
| THESE ARE IN NO WAY ALL LOCATIONS. PLEASE ALSO SEE SOME |
| SHEETS ARE BEING NOTED BELOW AS MANY ROOM AND AREA |
| DESIGNATIONS WERE REMOVED FROM PLANS. |
| 1HEB-5 AND 1HEB-3 TIED TOGETHER IN A1.804, A1.008. |
| SEE 1HEA-2 AT A1.206 AND A1.302 |
| SEE 1HEA-6 AND HED-2 TIED TOGETHER |
| SEE 1HED-4WHICH IS REPEATED, SEE AREAS D1.104, |
| D1.005 |
| SEE 1HB-7 IN D1.201 SHOWN ON AS NORMAL CIRCUIT OR |
| NOTING TO TIE TO. |
| SEE 1HEC-3 AND 1HEC5 TIED TOGETHER. |
| SEE CAF?, 1LC2, 8-10 AND 1LEC 6,8 TO SAME LIGHTS. |
| SEE 2HEA-3 AND 2HEA-1 TIED TOGETHER ON SHEET E-2.2.1 |
| SEE EXIT LIGHT IN AREA A2.302 WHICH SHOWS NO CIRCUIT. |
| SEE EXIT LIGHT AT DOOR IN FUTURE SPACE (SHELL AREA) |
| WHICH NEEDS TO BE CIRCUITED PER 700.12E |
| SEE AREA ON SHEET E2.3.2 *SUPPORT SPACE/FILE PRODUCTION |
| AND CORRIDOR AREA IS MISSING CIRCUIT FOR EMERGENCY AND |
| EXIT LIGHTS. |
| SEE LIGHTING CONTROL IN SOME ROOMS SUCH AS PROGRAM |
| MEETING ROOM WHICH SHOWS NORMAL OC DEVICE. THIS IS THE |
| SAME IN OTHER LOCATIONS ALSO ONE SHEET E2.3.2/ |
| COLLECTION/ PROGRAM ROOM. |
| SEE EMERGENCY AND EXIT LIGHTS IN ROOMS SUCH AS A4.420, |
| 4.419,4.421 ETC WHICH DOES NOT SHOW ANY CIRCUIT. |
| SEE THIS SAME LOCATION AS THERE ARE SWITCHES LOCATED IN |
| THE MIDDLE OF THE *AIR* AND NOT LOCATED ON ANY WALL. |
| SEE 4HEB-1 IN A4.416 WHICH SHOWS THIS BEING TIED TO |
| NORMAL AND EMERGENCY LIGHTS. |
| SEE EMERGENCY LIGHTS/EXIT LIGHTS OUTSIDE A4.304 WHICH |
| DOES NOT SHOW CIRCUIT. (PUBLIC UTILIZES AREA 03) |
| SEE A5.531, EMERGENCY NOT CONNECTED. |
| SEE A5.508, 5.505 ETC WHICH DOES NOT SHOW ANY CIRCUITS |
| FOR EMERGENCY LIGHT FIXTURES. |
| SEE 5HA-17 WHICH IS SHOWN TIED TO EMERGENCY LIGHTS AND |
| NOT NORMAL LIGHTING. |
| SEE A5.401 AND AREA WHICH INDICATES EMERGENCY AND EXIT |
| LIGHTS WITH NO CIRCUITS. |
| SEE A5.412 WHICH SHOWS NORMAL CIRCUIT TIED TO EMERGENCY |
| LIGHT. |
| SEE A5.503,504,505, A5.413 EMERGENCY AND EXIT LIGHTS |
| WITH NO CIRCUITING. |
| |
| ** PLEASE SEE THAT MANY OF THE AREAS ABOVE ARE NOTED |
| HOWEVER AS STATED ABOVE ARE IN NO WAY ALL POSSIBLE |
| LOCATIONS. |
| SEE REDLINED AND HIGHLIGHTED PLANS AS MOST OF THESE |
| AREAS INDICATE THE NOTES ABOVE. |
| |
| |
| |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |