Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop P
Sequence Number 17
Notes
Date Text
2008-07-18 08:54:08REVISIONS DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P1-1.0 REVISION 193R SHOWS A 2" CONDENSATE FROM
 AHU-1 CONNECTING TO A 1" CONDENSATE LINE THAT SNAKES
 OVER TO A PLANTER & DISCHARGES MINIMUM 12" AWAY FROM
 THE BUILDING WALL. FITTINGS SHOULD BE USED WHEN
 CHANGING DIRECTION ON DRAINAGE PIPE. SECTION 706.1.--
 THE SIZE OF THE DRAINAGE PIPING SHALL NOT BE REDUCED IN
 SIZE IN THE DIRECTION OF FLOW. SECTION 704.2.--MORE
 INFORMATION IS REQUIRED. IF THE CONDENSATE WILL BE
 DRAINING 24 HOURS, 365 DAYS A YEAR, WHERE WILL THE
 CONDENSATE WATER DRAINING INTO THE PLANTER GO? IS THE
 PLANTER SEALED OFF FROM THE BUILDING WALL WITH A
 FLASHING OR SOME OTHER FORM OF WATER PROOFING?--IF
 THE EXCESS WATER REMAINS IN THE PLANTER, WILL THIS
 CAUSE ROOT ROT ON THE REQUIRED PLANTS?--ALSO ALL
 CHANGES TO THE CONDENSATE SYSTEM SHALL BE REFLECTED ON
 THE CONDENSATE RISER DIAGRAM. SECTIONS 106.1.1, 106.1.2
 & 1503.6.
  
 2. SHT P1-1.0 REVISIONS 193 & 193RSHOWS THE
 CONDENSATE LINE SNAKING TO 1" DC DOWN.FITTINGS SHOULD
 BE USED WHEN CHANGING DIRECTION ON DRAINAGE PIPE.
 SECTION 706.1.
  
 3. SHT P1-1.01 PLANS STAMPED AND ISSUED 2-21-05 SHOW
 REVISIONS 1, 2, 4 & 5 IN THE REVISION INDEX. THE NEW
 REVISED SHEET SUBMITTED DOES NOT INDICATE REVISION 1
 AND SHOWS REVISIONS 12A & 193R. REVISION 12A IS NOT
 CLOUDED AND THE NUMBER IS NOT LEGIBLE IN THE TRIANGLE
 WHICH MAY OR MAY NOT BE REVISION 12A. PLEASE CLOUD ALL
 REVISIONS TO BE SUBMITTED AND MAKE SURE THE REVISION
 NUMBERS IN THE TRIANGLES ARE LEGIBLE. ALSO MAKE SURE
 THE REVISION INDEX SHOWS ALL REVISIONS RELATED TO THE
 SHEET. SECTIONS 106.1.1, 106.1.2 & 106.1.3.
  
 4. SHT P1-1.1 REVISIONS 193 & 193R FITTINGS SHOULD BE
 USED WHEN CHANGING DIRECTION ON DRAINAGE PIPE. SECTION
 706.1.
  
 5. SHT P1-1.1U REVISIONS 1 & 2 ARE NOT SHOWN ON THE
 REVISION INDEX AND REVISION 193R SHOWN ON THE FLOOR
 PLAN IS NOT SHOWN ON THE REVISION INDEX. PLEASE
 CORRELATE ALL REVISIONS AND THE REVISION INDEX. ALSO
 ALL REVISIONS ON PREVIOUSLY REVIEWED SHEETS SHALL
 REMAIN ON THE REVISION INDEX THRU THE LIFE OF THE PLANS
 TO TRACK ALL REVISIONS AND FOR PUBLIC RECORD. SECTION
 1106.1.3.
  
 6. SHT P1-1.2U REVISION 1 MISSING FROM THE REVISION
 INDEX. ALL REVISIONS ON PREVIOUSLY REVIEWED SHEETS
 SHALL REMAIN ON THE REVISION INDEX THRU THE LIFE OF THE
 PLANS TO TRACK ALL REVISIONS AND FOR PUBLIC RECORD.
 SECTION 1106.1.3.
  
 7. SHT P1-1.2 REVISIONS 11, 12 & 193 SHOWN IN THE
 REVISION INDEX ARE NOT SHOWN ON THE FLOOR PLAN. PLEASE
 CORRELATE. ALSO CLOUD AND NUMBER ALL REVISIONS
 SUBMITTED AFTER THE PREVIOUSLY REVIEWED SHEET.
  
 8. SHT P1-3.1 NO REVISION SHOWN. NO CHANGE FROM
 PREVIOUSLY REVIEWED SHEET. SECTION 106.1.3.
  
 9. SHT P1-4.0 REVISIONS NOT CLOUDED AT THE NEW ROOF
 DRAIN LOCATIONS.--ALSO THE RWL SIZE IS NOT LEGIBLE
 AT COLUUM LINES 8/L & 8/H. PLEASE CLARIFY. SECTION
 106.1.1 & TABLE 1106.3.
  
 10. SHT P1-4.1 REVISION 190 NOT FOUND ON THE FLOOR PLAN
 & REVISIONS 1 & 2 HAVE BEEN DELETED FROM THE REVISION
 INDEX. PLEASE CORRELATE AND ALL REVISIONS ON PREVIOUSLY
 REVIEWED SHEETS SHALL REMAIN ON THE REVISION INDEX THRU
 THE LIFE OF THE PLANS TO TRACK ALL REVISIONS AND FOR
 PUBLIC RECORD. SECTION 1106.1.3.
  
 11. SHT P1-4.2 REVISIONS NOT CLOUDED IN MANY AREAS. BE
 SURE TO CLOUD ALL REVISIONS SUBMITTED AFTER THE LAST
 REVIEWED/STAMPED SET OF REVISIONS. SECTION 106.1.3.
  
 12. SHT P1-5.0 NO REVISION NUMBER INDICATED FOR CLOUDED
 REVISIONS BETWEEN COLUUM LINES 1/H-L & 10/H-L. PLEASE
 NUMBER ALL REVISIONS. ALSO NO CHANGE NOTED FOR CLOUDED
 REVISION AT COLUUM LINES 6/C-D1 & B/6-8. PLEASE
 CORRELATE. SECTION 106.1.3.--PIPING FOR THE
 CONDENSATE SNAKING FROM RISER TO UNIT.FITTINGS SHOULD
 BE USED WHEN CHANGING DIRECTION ON DRAINAGE PIPE.
 SECTION 706.1.
  
 13. SHTP3-7.0 REVISIONS SHOWN ON RWL'S 5, 6 & 7 WITH
 CLOUDS OR REVISIONS NUMBERS. PLEASE SHOW CLOUDS AND
 REVISION NUMBERS FOR EACH REVISIONS. SECTION 106.1.3.
 --REVISION NUMBER 11 DOES NOT INDICATE WHAT IS
 REVISED. PLEASE CLARIFY. SECTION 106.1.1.--THE
 ADDITION OF RWL'S 11& 14 ADD UP TO 10,420SF. 10" PIPE
 IS REQUIRED PER TABLE 1106.3. 8" IS SHOWN.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  