2008-04-20 13:37:13REVIEW #: REV.14D
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG M1-1.1: 6 INCH ROUND SUPPLY DUCT FEEDING FILE
 ROOM A1.207 IS PENETRATING A RATED CORRIDOR WALL AND IS
 ONLY PROTECTED WITH A FIRE DAMPER. THIS PENETRATION
 REQUIRES A FIRE AND SMOKE DAMPER IN ACCORDANCE WITH
 FBCM 607.5.4(3) BECAUSE THE DUCT HAS OPENINGS IN THE
 CORRIDOR.
  
 2. PG M1-1.1: 10 INCH ROUND SUPPLY DUCT FEEDING
 VESTIBULE A1.011 IS PROTECTED WITH A FIRE/SMOKE DAMPER.
 HOWEVER, THIS VESTIBULE IS SERVING AS AN EXIT
 PASSAGEWAY FROM STAIR 02 AS DEFINED IN FBCB SECTION
 1002. THIS PENETRATION IS PROHIBITED IN ACCORDANCE WITH
 FBCB 1020.5.
  
 3. PG M1-1.1 AND MOST REV.14D PAGES: KEY NOTES WHICH
 ARE LISTED ON THE BOTTOM RIGHT OF PAGE ARE NOW MISSING
 FROM FLOOR PLANS. SOME KEY NOTES ARE NO LONGER VALID
 AND SHOULD BE REMOVED FROM PLANS. EXAMPLE: PG M1-1.2
 KEY NOTE #1 STILL CALLS FOR DUCT SMOKE DETECTORS AT
 SHAFTS FOR SMOKE DAMPERS. PLEASE SHOW RELEVANT KEY
 NOTES WHERE NEEDED ON FLOOR PLANS AND REMOVE THOSE
 WHICH ARE NO LONGER APPLICABLE.
  
 4. PG M1-1.2: IN VESTIBULE D1.005 THERE ARE TWO DUCT
 PENETRATIONS. THIS IS AN EXIT PASSAGEWAY AS DEFINED IN
 FBCB SECTION 1002. THESE PENETRATIONS ARE PROHIBITED IN
 ACCORDANCE WITH FBCB 1020.5.
  
 5. PG M1-1.2: AT VOICE/DATA ROOM D1.107 THERE IS A
 36X56 DUCT PENETRATING THE FLOOR ABOVE AND IS SHOWN IN
 THE MIDDLE OF A SMOKE PARTITION. ARCHITECTURAL PLANS
 CALL FOR THIS WALL TO BE BUILT TO THE UNDERSIDE OF THE
 FLOOR ABOVE. PLEASE SHOW HOW THIS WILL BE ACCOMPLISHED
 WITHOUT COMPROMISING THE FIRE/SMOKE DAMPER INSTALLATION
 OR THE SMOKE RATING OF THE PARTITION. FBCM 607.2, FBCB
 710.4.
  
 6. PG M1-1.2: A 14 INCH ROUND DUCT PENETRATING THE WALL
 BETWEEN VOICE/DATA ROOM C1.102 AND LOBBY C1.008 IS
 SHOWN PROTECTED WITH A FIRE DAMPER. THIS PENETRATION
 REQUIRES FIRE AND SMOKE DAMPER IN ACCORDANCE WITH FBCM
 607.5.4(3).
  
 7. PG M1-1.2: STORAGE ROOMS C1.403 AND C1.404 ARE
 ENCLOSED IN SMOKE PARTITIONS AS SHOWN ON LS1-1.2.
 MECHANICAL FLOOR PLAN SHOWS AIR TRANSFER OPENINGS IN
 EACH ROOM. THESE OPENINGS SHALL BE PROTECTED BY SMOKE
 DAMPER IN ACCORDANCE WITH FBCB 710.7.
  
 8. PG M1-1.2 THROUGH M1-5.2: STARTING IN MEN?S ROOM
 C1.104 THERE IS AN EXHAUST DUCT ENTERING WHAT APPEARS
 TO BE AN ENCLOSURE AND TRAVELS THROUGH THE 4TH FLOOR TO
 EF-4 ON THE ROOF. THIS ENCLOSURE IS NOT SHOWN TO BE
 FIRE RESISTANCE RATED AS A SHAFT ON THE ARCHITECTURAL
 OR LIFE SAFETY PLANS.A SHAFT ENCLOSURE IS REQUIRED
 WHERE DUCTS PENETRATE HORIZONTAL ASSEMBLIES IN
 ACCORDANCE WITH FBCM 607.6. SHAFT ENCLOSURES SHALL HAVE
 A FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS WHERE
 CONNECTING FOUR STORIES OR MORE IN ACCORDANCE WITH FBCB
 707.4.
  
 9. PG M1-2.1: KEY NOTE #6 NEEDS TO BE ASSOCIATED WITH
 THE FIRE/SMOKE DAMPERS LOCATED WHERE THE SMOKE EXHAUST
 DUCTS PENETRATE THE SHAFT ENCLOSURE. THESE DAMPERS NEED
 TO BE UNDER THE CONTROL OF THE SMOKE CONTROL SYSTEM TO
 ENSURE THEY ARE OPEN WHEN THE ATRIUM IS IN SMOKE
 CONTROL MODE IN ACCORDANCE WITH FBCB 909.22.1.
  
 10. PG M1-3.2: AT VOICE/DATA ROOM C3.110 THE 10X8 DUCT
 PENETRATION OF THE RATED CORRIDOR WALL REQUIRES FIRE
 AND SMOKE DAMPER IN ACCORDANCE WITH FBCM 607.5.4(3).
  
 11. PG M1-3.2: AT CORRIDOR C3.010 THE 55X18 DUCT
 PENETRATION OF THE RATED CORRIDOR WALL REQUIRES FIRE
 AND SMOKE DAMPER IN ACCORDANCE WITH FBCM 607.5.4(3).
  
 12. PG M1-3.2: AT PROGRAM/MEETING ROOM C3.306 THE 48X18
 DUCT PENETRATION OF THE RATED CORRIDOR WALL REQUIRES
 FIRE AND SMOKE DAMPER IN ACCORDANCE WITH FBCM
 607.5.4(3).
  
 13. PG M1-3.2: AT CORRIDOR C3.015 THERE IS VAV 3-1R-5.
 THE DUCTS ON BOTH SIDES OF THE VAV ARE SHOWN AS
 PROTECTED WITH FIRE DAMPERS. IF THE DUCT CONNECTION TO
 THIS VAV IS MADE BY FLEXIBLE NON-METALLIC DUCT, THESE
 DUCT PENETRATIONS WILL NOT MEET THE EXCEPTION FOR SMOKE
 DAMPER REQUIREMENT IN ACCORDANCE WITH FBCM 607.5.4(3).
 PLEASE VERIFY THAT THIS DUCT AND VAV CONNECTION ARE
 CONTINUOUS STEEL NOT LESS THAN 0.019 INCH THICKNESS (26
 GAGE) OR PROVIDE FIRE AND SMOKE DAMPER AT CORRIDOR
 PENETRATIONS IN ACCORDANCE WITH FBCM 607.5.4.
  
 14. PG M1-3.2, A1-3.2 AND LS1-3.2: THERE IS A PORTION
 OF THE WALL BETWEEN LOBBY C3.303 AND PREFUNCTION LOBBY
 C3.301 WHICH IS NOT SHOWN TO CARRY THE 1-HOUR FIRE
 RESISTANCE RATING AS REQUIRED FOR EXIT ACCESS CORRIDORS
 IN THIS AREA IN ACCORDANCE WITH FBCB TABLE 1016.1.
  
 15. PG M2-3.0 AND M1-6.0: ELEVATOR MACHINE ROOM A6.103
 REQUIRES INDEPENDENT VENTILATION IN ACCORDANCE WITH
 FBCB 3006.2. THE DUCT PENETRATION INTO THIS ROOM SHALL
 BE PROTECTED WITH FIRE/SMOKE DAMPER IN ACCORDANCE WITH
 FBCB 3006.4 AND FBCM 607.5.5.1.
  
 16. PG M2-3.0 AND M1-6.0: ELEVATOR MACHINE ROOM A6.102,
 THE 44X30 DUCT OPENING IN TO ELEVATOR 03 HOISTWAY SHALL
 BE PROTECTED WITH COMBINATION FIRE/SMOKE DAMPER IN
 ACCORDANCE WITH FBCB 3002.1.1 AND FBCM 607.5.5.1.
  
 17. PG M2-3.0 AND M1-6.0: ELEVATOR MACHINE ROOM A6.102,
 THE 18X14 DUCT PENETRATION FROM FCU-6 SHALL BE
 PROTECTED WITH COMBINATION FIRE/SMOKE DAMPER IN
 ACCORDANCE WITH FBCB 3006.4 AND FBCM 607.5.5.1.
  
 18. PG M2-3.0 AND M1-6.0: ELEVATOR MACHINE ROOM A6.102,
 THE 44X30 HOISTWAY VENT REQUIRES A MOTORIZED DAMPER IN
 ACCORDANCE WITH FBCB 13-409.1.ABC.3.1.
  
 19. PG M6-1.0: PLEASE REMOVE KEY NOTE #1 FROM PLAN AS
 IT IS NO LONGER APPLICABLE.
 FBCB 106.1.1. SEE ALSO COMMENT #3 ABOVE.
  
 NOTE: MECHANICAL REVIEW HAS BEEN COMPLETED. HOWEVER,
 BUILDING REVIEW IS PARTIALLY COMPLETE AT THIS TIME AND
 STILL PENDING. PLEASE COORDINATE ALL MECHANICAL,
 ARCHITECTURAL AND LIFE SAFETY PLANS TO ENSURE CODE
 COMPLIANCE PRIOR TO RESUBMITTAL OF PLANS.
  