Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop P
Sequence Number 15
Notes
Date Text
2008-05-29 15:05:51REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHTS P1-1.0 & P1-1.1 REVISION 193. SHOW THE 2"
 CONDENSATE RISER INDICATED ON THE REVISION. PLANS SHOW
 CONDENSATE CONNECTION TO THE 4" SANITARY LINE. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 2. SHTS P1-3.0 & P1-3.1 CONDENSATE SHALL NOT CONNECT TO
 THE RAIN WATER LEADER OTHER THAN AT THE ROOF DRAINS.
 THE CONDENSATE SHALL DRAIN SEPARATELY FROM THE BUILDING
 BY A DEDICATED CONDENSATE RISER AND CONNECT TO A
 DRYWELL, A CATCH BASIN, A STORM LINE OR INTO A PLANTED
 AREA. IF CONNECTING TO THE STORM DRAIN OUTSIDE THE
 BUILDING, A RELIEF VENT OR GOOSENECK IS REQUIRED AS THE
 CONDENSATE EXITS THE BUILDING. SECTION 314.2.1.
  
 3. SHT P1-4.0 RISER RWL/12 TOTAL SQUARE FOOTAGE DOES
 NOT REFLECT THE TOTAL OF BOTH ROOF DRAINS. TABLE
 1106.3.--SHOW THE LOCATION OF RWL/9. PIPING APPEARS
 TO BE CONNECTING TO THE SANITARY RISER P/2. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 4. SHT P1-4.2 RISER RWL/12 TOTAL SQUARE FOOTAGE DOES
 NOT REFLECT THE TOTAL OF BOTH ROOF DRAINS. TABLE
 1106.3.--SHOW THE LOCATION OF RWL/9. PIPING APPEARS
 TO BE CONNECTING TO THE SANITARY RISER P/2. PLEASE
 CLARIFY.--ALSO REVISION NUMBER 5 IS NOT INDICATED
 ON THE REVISION INDEX. PLEASE SHOW ALL REVISIONS ON THE
 INDEX. SECTIONS 106.1.2 & 106.1.3.
  
 5. SHT P1-5.0 CHANGES TO THE ROOF DRAINS & OVERFLOW
 DRAIN ARE NOT INDICATED AS CHANGES. PLEASE CLOUD AND
 NUMBER ALL REVISIONS SUBMITTED. SECTION 106.1.3.
  
 6. SHT P3-1.0 RISER DIAGRAM DOES NOT REFLECT THE FLOOR
 PLAN FOR THE NEW SINK AT THE CONNECTION AND ROUTING OF
 THE PIPING. PLEASE CORRELATE. SECTION 106.1.1.
  
 7. SHT P3-7.0 RISER DOES NOT REFLECT THE FLOOR PLAN AT
 RWL'S 11 THRU 14. ALSO RECHECK THE SQUARE FOOTAGE AT
 EACH ROOF DRAIN AND THE TOTAL SQUARE FOOTAGE FOR EACH
 RWL. THIS INFORMATION SHALL REFLECT THE FLOOR PLAN.
 SECTION 106.1.1 & TABLE 1106.3.--ALSO CONDENSATE
 SHALL NOT CONNECT TO THE RAIN WATER LEADER OTHER THAN
 AT THE ROOF DRAINS. THE CONDENSATE SHALL DRAIN
 SEPARATELY FROM THE BUILDING BY A DEDICATED CONDENSATE
 RISER AND CONNECT TO A DRYWELL, A CATCH BASIN, A STORM
 LINE OR INTO A PLANTED AREA. IF CONNECTING TO THE STORM
 DRAIN OUTSIDE THE BUILDING, A RELIEF VENT OR GOOSENECK
 IS REQUIRED AS THE CONDENSATE EXITS THE BUILDING.
 SECTION 313.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  