2008-05-29 15:05:51 | REVISION DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| |
| 1. SHTS P1-1.0 & P1-1.1 REVISION 193. SHOW THE 2" |
| CONDENSATE RISER INDICATED ON THE REVISION. PLANS SHOW |
| CONDENSATE CONNECTION TO THE 4" SANITARY LINE. PLEASE |
| CLARIFY. SECTION 106.1.1. |
| |
| 2. SHTS P1-3.0 & P1-3.1 CONDENSATE SHALL NOT CONNECT TO |
| THE RAIN WATER LEADER OTHER THAN AT THE ROOF DRAINS. |
| THE CONDENSATE SHALL DRAIN SEPARATELY FROM THE BUILDING |
| BY A DEDICATED CONDENSATE RISER AND CONNECT TO A |
| DRYWELL, A CATCH BASIN, A STORM LINE OR INTO A PLANTED |
| AREA. IF CONNECTING TO THE STORM DRAIN OUTSIDE THE |
| BUILDING, A RELIEF VENT OR GOOSENECK IS REQUIRED AS THE |
| CONDENSATE EXITS THE BUILDING. SECTION 314.2.1. |
| |
| 3. SHT P1-4.0 RISER RWL/12 TOTAL SQUARE FOOTAGE DOES |
| NOT REFLECT THE TOTAL OF BOTH ROOF DRAINS. TABLE |
| 1106.3.--SHOW THE LOCATION OF RWL/9. PIPING APPEARS |
| TO BE CONNECTING TO THE SANITARY RISER P/2. PLEASE |
| CLARIFY. SECTION 106.1.1. |
| |
| 4. SHT P1-4.2 RISER RWL/12 TOTAL SQUARE FOOTAGE DOES |
| NOT REFLECT THE TOTAL OF BOTH ROOF DRAINS. TABLE |
| 1106.3.--SHOW THE LOCATION OF RWL/9. PIPING APPEARS |
| TO BE CONNECTING TO THE SANITARY RISER P/2. PLEASE |
| CLARIFY.--ALSO REVISION NUMBER 5 IS NOT INDICATED |
| ON THE REVISION INDEX. PLEASE SHOW ALL REVISIONS ON THE |
| INDEX. SECTIONS 106.1.2 & 106.1.3. |
| |
| 5. SHT P1-5.0 CHANGES TO THE ROOF DRAINS & OVERFLOW |
| DRAIN ARE NOT INDICATED AS CHANGES. PLEASE CLOUD AND |
| NUMBER ALL REVISIONS SUBMITTED. SECTION 106.1.3. |
| |
| 6. SHT P3-1.0 RISER DIAGRAM DOES NOT REFLECT THE FLOOR |
| PLAN FOR THE NEW SINK AT THE CONNECTION AND ROUTING OF |
| THE PIPING. PLEASE CORRELATE. SECTION 106.1.1. |
| |
| 7. SHT P3-7.0 RISER DOES NOT REFLECT THE FLOOR PLAN AT |
| RWL'S 11 THRU 14. ALSO RECHECK THE SQUARE FOOTAGE AT |
| EACH ROOF DRAIN AND THE TOTAL SQUARE FOOTAGE FOR EACH |
| RWL. THIS INFORMATION SHALL REFLECT THE FLOOR PLAN. |
| SECTION 106.1.1 & TABLE 1106.3.--ALSO CONDENSATE |
| SHALL NOT CONNECT TO THE RAIN WATER LEADER OTHER THAN |
| AT THE ROOF DRAINS. THE CONDENSATE SHALL DRAIN |
| SEPARATELY FROM THE BUILDING BY A DEDICATED CONDENSATE |
| RISER AND CONNECT TO A DRYWELL, A CATCH BASIN, A STORM |
| LINE OR INTO A PLANTED AREA. IF CONNECTING TO THE STORM |
| DRAIN OUTSIDE THE BUILDING, A RELIEF VENT OR GOOSENECK |
| IS REQUIRED AS THE CONDENSATE EXITS THE BUILDING. |
| SECTION 313.2.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |