2008-04-08 16:00:16 | REVIEW #: REV.14B AND 14C |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. PG M1-1.1: THIS SHEET CONTAINS CHANGES WHICH ARE NOT |
| MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE |
| MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE |
| REV. 12C. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON |
| PLAN. |
| ALSO, REVISIONS 12B AND 12C WHICH WERE PART OF THE |
| REVISION HISTORY ARE NOW MISSING FROM PLANS. THIS |
| INDICATES IT IS LIKELY THAT THE PLANS HAVE REVERTED TO |
| A PREVIOUS STATE BEFORE BEING REVISED AS PART OF REV |
| 14B. |
| |
| 2. PG M1-1.2: THIS SHEET CONTAINS CHANGES WHICH ARE NOT |
| MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE |
| MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE |
| REV. 12B. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON |
| PLAN. |
| ALSO, REVISION WHICH WAS PART OF THE REVISION HISTORY |
| IS NOW MISSING FROM PLANS. THIS INDICATES IT IS LIKELY |
| THAT THE PLANS HAVE REVERTED TO A PREVIOUS STATE BEFORE |
| BEING REVISED AS PART OF REV 14B AND 14C. |
| |
| 3. PG M1-1.2: THERE IS A 10 INCH ROUND DUCT PENETRATING |
| A 2-HOUR RATED WALL BETWEEN LOADING D1.106 AND CORRIDOR |
| D1.006. SHOW HOW THIS PENETRATION IS TO BE PROTECTED IN |
| ACCORDANCE WITH FBCM 607.5. |
| |
| 4. PG M1-2.1: THIS SHEET CONTAINS CHANGES WHICH ARE NOT |
| MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE |
| MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE |
| REV. 12C. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON |
| PLAN. |
| ALSO, REVISIONS 12B AND 12C WHICH WERE PART OF THE |
| REVISION HISTORY ARE NOW MISSING FROM PLANS. THIS |
| INDICATES IT IS LIKELY THAT THE PLANS HAVE REVERTED TO |
| A PREVIOUS STATE BEFORE BEING REVISED AS PART OF REV |
| 14B. |
| |
| 5. PG M1-2.2: THIS PAGE IS NOT ABLE TO BE REVIEWED. |
| THERE ARE MULTIPLE LAYERS IN MULTIPLE SCALES ON THE |
| SAME PAGE. PLEASE CORRECT THE PAGE AND RESUBMIT. |
| |
| 6. PG M1-3.1: THIS SHEET CONTAINS CHANGES WHICH ARE NOT |
| MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE |
| MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE |
| REV. 12C. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON |
| PLAN. |
| |
| 7. PG M1-3.1: THIS PAGE HAS BEEN MODIFIED BY HAND WITH |
| A PEN. THERE IS NO INDICATION ON PLANS THAT THESE |
| MODIFICATIONS WERE MADE BY THE DESIGN PROFESSIONAL OF |
| RECORD. SIGNED AND SEALED DRAWINGS SHALL NOT BE |
| MODIFIED ONCE SIGNED AND SEALED UNLESS THE |
| MODIFICATIONS ARE SIGNED AND DATED BY THE DESIGNER OF |
| RECORD. OTHERWISE, IT SHALL BE ASSUMED THAT THE |
| DRAWINGS WERE MODIFIED BY SOMEONE NOT AUTHORIZED TO DO |
| SO. |
| |
| 8. PG M1-3.1: PLAN SHOWS TWO FIRE DAMPERS IN THE WALL |
| AT VOICE/DATA A3.116. THIS WALL IS NOT SHOWN AS HAVING |
| A FIRE RESISTANCE RATING ON ARCHITECTURAL OR LIFE |
| SAFETY PLANS. THERE IS ALSO A 60X26 UNPROTECTED DUCT |
| PENETRATION SHOWN IN THE SAME ROOM. PLEASE COORDINATE |
| MECH. PLANS WITH ARCH. PLANS AND LS PLANS, SHOWING |
| PROTECTION OF PENETRATIONS WHERE NEEDED IN ACCORDANCE |
| WIT FBCM 607.5. |
| |
| 9. PG M1-3.2: THERE ARE AT LEAST FIVE DUCT PENETRATIONS |
| OF FIRE RATED WALL ASSEMBLIES WITHOUT PROTECTION AT |
| CORRIDORS C3.011 AND C3.012. SHOW HOW THESE |
| PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE WITH |
| FBCM 607.5 AND 607.5.4. |
| |
| 10. PG M1-3.2: THIS SHEET CONTAINS CHANGES WHICH ARE |
| NOT MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. |
| PLEASE MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED |
| SINCE REV. 12B. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED |
| ON PLAN. |
| ALSO, REVISION 12B WHICH WAS PART OF THE REVISION |
| HISTORY IS NOW MISSING FROM PLANS. THIS INDICATES IT IS |
| LIKELY THAT THE PLANS HAVE REVERTED TO A PREVIOUS STATE |
| BEFORE BEING REVISED AS PART OF REV 14B AND 14C. |
| |
| 11. PG M1-3.2: PLEASE SHOW SIZE OF DUCT FOR EF-3 ABOVE |
| STAIR 10 RISER BETWEEN TRANSITIONS. ALSO, SHOW SIZE OF |
| TAP AT 40X44 RETURN DUCT FOR RTU-2 NEAR STAIR 7. |
| |
| 12. THIS SHEET CONTAINS CHANGES WHICH ARE NOT MARKED OR |
| CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE MARK OR |
| CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE REV. 12A. |
| ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON PLAN. |
| |
| 13. PG M1-4.1: THE DUCT FEEDING A VAV FROM SOUTH END OF |
| SERVER ROOM IS PENETRATING A 2-HOUR RATED WALL ASSEMBLY |
| AS SHOWN ON ARCHITECTURAL AND LIFE SAFETY PLANS. PLEASE |
| COORDINATE PLANS AND SHOW PENETRATIONS TO BE PROTECTED |
| IN ACCORDANCE WITH FBCM 607.5. |
| |
| 14. PG M1-4.1: THERE IS A DELTA-13 REVISION MARK IN THE |
| RISER FOR CAHU-1. THERE IS NO REVISION 13 SHOWN ON THE |
| REVISION HISTORY FOR THIS PAGE. PLEASE CLARIFY. |
| |
| 15. PG M1-4.2: RETURN DUCT SIZE FOR AHU-3 HAS BEEN |
| REVISED ON THIS PAGE BUT THE CORRESPONDING DUCT HAS NOT |
| BEEN REVISED ON PAGE M2-2.0. PLEASE COORDINATE PLANS |
| AND RESUBMIT. |
| |
| 16. SUPPLY AND RETURN DUCT RISER SIZES FOR RTU-1 AND |
| RTU-2 HAVE BEEN REVISED ON THIS PAGE BUT HAVE NOT BEEN |
| REVISED ON PAGE M1-5.2. PLEASE COORDINATE PLANS AND |
| RESUBMIT. |
| |
| 17. PG M1-5.1: THIS SHEET CONTAINS CHANGES WHICH ARE |
| NOT MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. |
| PLEASE MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED |
| SINCE REV. 12A. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED |
| ON PLAN. |
| |
| 18. PG M2-1.0, M3-1.0, M6-1.0: THESE PAGES ARE OK BUT |
| ARE BEING RETURNED TO CONTRACTOR PER THEIR REQUEST. |
| |
| 19. PG M2-3.0: THIS SHEET CONTAINS CHANGES WHICH ARE |
| NOT MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. |
| PLEASE MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED |
| SINCE REV. 12A. |
| |