2008-04-08 16:00:16REVIEW #: REV.14B AND 14C
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG M1-1.1: THIS SHEET CONTAINS CHANGES WHICH ARE NOT
 MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE
 MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE
 REV. 12C. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON
 PLAN.
 ALSO, REVISIONS 12B AND 12C WHICH WERE PART OF THE
 REVISION HISTORY ARE NOW MISSING FROM PLANS. THIS
 INDICATES IT IS LIKELY THAT THE PLANS HAVE REVERTED TO
 A PREVIOUS STATE BEFORE BEING REVISED AS PART OF REV
 14B.
  
 2. PG M1-1.2: THIS SHEET CONTAINS CHANGES WHICH ARE NOT
 MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE
 MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE
 REV. 12B. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON
 PLAN.
 ALSO, REVISION WHICH WAS PART OF THE REVISION HISTORY
 IS NOW MISSING FROM PLANS. THIS INDICATES IT IS LIKELY
 THAT THE PLANS HAVE REVERTED TO A PREVIOUS STATE BEFORE
 BEING REVISED AS PART OF REV 14B AND 14C.
  
 3. PG M1-1.2: THERE IS A 10 INCH ROUND DUCT PENETRATING
 A 2-HOUR RATED WALL BETWEEN LOADING D1.106 AND CORRIDOR
 D1.006. SHOW HOW THIS PENETRATION IS TO BE PROTECTED IN
 ACCORDANCE WITH FBCM 607.5.
  
 4. PG M1-2.1: THIS SHEET CONTAINS CHANGES WHICH ARE NOT
 MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE
 MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE
 REV. 12C. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON
 PLAN.
 ALSO, REVISIONS 12B AND 12C WHICH WERE PART OF THE
 REVISION HISTORY ARE NOW MISSING FROM PLANS. THIS
 INDICATES IT IS LIKELY THAT THE PLANS HAVE REVERTED TO
 A PREVIOUS STATE BEFORE BEING REVISED AS PART OF REV
 14B.
  
 5. PG M1-2.2: THIS PAGE IS NOT ABLE TO BE REVIEWED.
 THERE ARE MULTIPLE LAYERS IN MULTIPLE SCALES ON THE
 SAME PAGE. PLEASE CORRECT THE PAGE AND RESUBMIT.
  
 6. PG M1-3.1: THIS SHEET CONTAINS CHANGES WHICH ARE NOT
 MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE
 MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE
 REV. 12C. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON
 PLAN.
  
 7. PG M1-3.1: THIS PAGE HAS BEEN MODIFIED BY HAND WITH
 A PEN. THERE IS NO INDICATION ON PLANS THAT THESE
 MODIFICATIONS WERE MADE BY THE DESIGN PROFESSIONAL OF
 RECORD. SIGNED AND SEALED DRAWINGS SHALL NOT BE
 MODIFIED ONCE SIGNED AND SEALED UNLESS THE
 MODIFICATIONS ARE SIGNED AND DATED BY THE DESIGNER OF
 RECORD. OTHERWISE, IT SHALL BE ASSUMED THAT THE
 DRAWINGS WERE MODIFIED BY SOMEONE NOT AUTHORIZED TO DO
 SO.
  
 8. PG M1-3.1: PLAN SHOWS TWO FIRE DAMPERS IN THE WALL
 AT VOICE/DATA A3.116. THIS WALL IS NOT SHOWN AS HAVING
 A FIRE RESISTANCE RATING ON ARCHITECTURAL OR LIFE
 SAFETY PLANS. THERE IS ALSO A 60X26 UNPROTECTED DUCT
 PENETRATION SHOWN IN THE SAME ROOM. PLEASE COORDINATE
 MECH. PLANS WITH ARCH. PLANS AND LS PLANS, SHOWING
 PROTECTION OF PENETRATIONS WHERE NEEDED IN ACCORDANCE
 WIT FBCM 607.5.
  
 9. PG M1-3.2: THERE ARE AT LEAST FIVE DUCT PENETRATIONS
 OF FIRE RATED WALL ASSEMBLIES WITHOUT PROTECTION AT
 CORRIDORS C3.011 AND C3.012. SHOW HOW THESE
 PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE WITH
 FBCM 607.5 AND 607.5.4.
  
 10. PG M1-3.2: THIS SHEET CONTAINS CHANGES WHICH ARE
 NOT MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS.
 PLEASE MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED
 SINCE REV. 12B. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED
 ON PLAN.
 ALSO, REVISION 12B WHICH WAS PART OF THE REVISION
 HISTORY IS NOW MISSING FROM PLANS. THIS INDICATES IT IS
 LIKELY THAT THE PLANS HAVE REVERTED TO A PREVIOUS STATE
 BEFORE BEING REVISED AS PART OF REV 14B AND 14C.
  
 11. PG M1-3.2: PLEASE SHOW SIZE OF DUCT FOR EF-3 ABOVE
 STAIR 10 RISER BETWEEN TRANSITIONS. ALSO, SHOW SIZE OF
 TAP AT 40X44 RETURN DUCT FOR RTU-2 NEAR STAIR 7.
  
 12. THIS SHEET CONTAINS CHANGES WHICH ARE NOT MARKED OR
 CLOUDED FROM PREVIOUS PASSED PLANS. PLEASE MARK OR
 CLOUD ALL CHANGES WHICH HAVE OCCURRED SINCE REV. 12A.
 ONE EXAMPLE OF SUCH CHANGES IS CIRCLED ON PLAN.
  
 13. PG M1-4.1: THE DUCT FEEDING A VAV FROM SOUTH END OF
 SERVER ROOM IS PENETRATING A 2-HOUR RATED WALL ASSEMBLY
 AS SHOWN ON ARCHITECTURAL AND LIFE SAFETY PLANS. PLEASE
 COORDINATE PLANS AND SHOW PENETRATIONS TO BE PROTECTED
 IN ACCORDANCE WITH FBCM 607.5.
  
 14. PG M1-4.1: THERE IS A DELTA-13 REVISION MARK IN THE
 RISER FOR CAHU-1. THERE IS NO REVISION 13 SHOWN ON THE
 REVISION HISTORY FOR THIS PAGE. PLEASE CLARIFY.
  
 15. PG M1-4.2: RETURN DUCT SIZE FOR AHU-3 HAS BEEN
 REVISED ON THIS PAGE BUT THE CORRESPONDING DUCT HAS NOT
 BEEN REVISED ON PAGE M2-2.0. PLEASE COORDINATE PLANS
 AND RESUBMIT.
  
 16. SUPPLY AND RETURN DUCT RISER SIZES FOR RTU-1 AND
 RTU-2 HAVE BEEN REVISED ON THIS PAGE BUT HAVE NOT BEEN
 REVISED ON PAGE M1-5.2. PLEASE COORDINATE PLANS AND
 RESUBMIT.
  
 17. PG M1-5.1: THIS SHEET CONTAINS CHANGES WHICH ARE
 NOT MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS.
 PLEASE MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED
 SINCE REV. 12A. ONE EXAMPLE OF SUCH CHANGES IS CIRCLED
 ON PLAN.
  
 18. PG M2-1.0, M3-1.0, M6-1.0: THESE PAGES ARE OK BUT
 ARE BEING RETURNED TO CONTRACTOR PER THEIR REQUEST.
  
 19. PG M2-3.0: THIS SHEET CONTAINS CHANGES WHICH ARE
 NOT MARKED OR CLOUDED FROM PREVIOUS PASSED PLANS.
 PLEASE MARK OR CLOUD ALL CHANGES WHICH HAVE OCCURRED
 SINCE REV. 12A.
  