Plan Review Notes For Permit 06100574 |
Permit Number |
06100574 |
|
Review Stop |
M |
Sequence Number |
13 |
|
Notes |
Date |
Text |
2008-01-02 16:21:34 | DUCT PARTIAL SHOP DRAWINGS DENIED. THE FOLLOWING ARE | | EXAMPLES OF CONDITIONS WHICH MAY EXIST THROUGHOUT THE | | DRAWINGS. THESE SHOP DRAWINGS WERE COMPARED TO HVAC | | REVISION #14. | | | | 1. PG SM-1-4: 36X24 SUPPLY DUCT IS PENETRATING A RATED | | WALL AT ALCOVE A1.104 WITHOUT REQUIRED OPENING | | PROTECTIVES IN ACCORDANCE WITH FBC, M 607.5. THE SAME | | OPENING PROTECTIVES ARE MISSING IN REV. 14 ON PR | | M1-1.1. PLEASE CHECK ALL PENETRATIONS OF RATED | | ASSEMBLIES FOR PROPER OPENING PROTECTIVES AS REQUIRED | | BY THIS SECTION. | | | | 2. PG SM-3-2: DUCTWORK IN CONFERENCE ROOMS A3.306 AND | | A3.307 DOES NOT CORRESPOND WITH WHAT IS SHOWN IN REV.14 | | ON PG M1-3.1. PLEASE CHECK ALL DUCTS SHOWN CORRESPOND | | BETWEEN SHOP DRAWINGS AND SIGNED AND SEALED PLANS. WORK | | SHALL BE INSTALLED IN ACCORDANCE WITH THE REVIEWED | | CONSTRUCTION DOCUMENTS, AND ANY CHANGES MADE DURING | | CONSTRUCTION THAT ARE NOT IN COMPLIANCE WITH THE | | REVIEWED CONSTRUCTION DOCUMENTS SHALL BE RESUBMITTED | | FOR REVIEW AS AN AMENDED SET OF CONSTRUCTION DOCUMENTS | | IN ACCORDANCE WITH FBC 106.4. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] | | |
|