2007-12-22 14:42:09REVIEW #: REV.14
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M1-1.1: THE 36/24 SUPPLY DUCT FROM CAHU-1 HAS AT
 LEAST ONE UNPROTECTED OPENING IN THE WALL AT ALCOVE
 A1.104. SHOW OPENING PROTECTIVES (FIRE/SMOKE DAMPER) AS
 REQUIRED BY FBC, M 607.5.
  
 2. M1-1.1: THE 16/14 EXHAUST DUCT CROSSING CORRIDOR
 A1.013 HAS 2 FIRE DAMPERS WHICH HAVE BEEN CHANGED TO
 FIRE/SMOKE DAMPERS. WHY HAVE THESE CHANGED? SMOKE
 DAMPERS ARE NOT REQUIRED IN THIS DUCT AS IT MEETS
 EXCEPTION #3 UNDER FBC, M 607.5.4.
  
 3. M1-2.1: EF 17 EXHAUST DUCT HAS NO SIZE SHOWN ON
 PLANS AND THE CORRESPONDING KEY NOTE #1 IS INCORRECTLY
 IDENTIFYING THE RETURN DUCT AS EXHAUST DUCT. ALSO, ADD
 KEY NOTE #6 TO FIRE/SMOKE DAMPERS WHERE SMOKE EXHAUST
 DUCTS EXIT THE SHAFT ENCLOSURE, AS STATED IN PREVIOUS
 REVIEW OF THIS PAGE. KEY NOTE #2 IS ALSO IN THE
 INCORRECT LOCATION TO BE ASSOCIATED WITH THE SMOKE
 EXHAUST DUCT.
  
 4. M1-3.1 KEY NOTE #3, M1-4.1 KEY NOTE #5, M1-5.1 KEY
 NOTE #3, M2-3.0 KEY NOTE #6 AND M6-1.0 KEY NOTE #1 CALL
 FOR SMOKE DETECTORS AT SHAFT PENETRATIONS, PRESUMABLY
 FOR CONTROL OF FIRE/SMOKE DAMPERS. AS OF REV 12B, THESE
 DAMPERS ARE TO BE ACTUATED BY AREA SMOKE DETECTORS IN
 ACCORDANCE WITH FBC, M 607.3.2.1(5). THESE KEY NOTES
 ARE IN CONFLICT WITH REVISION 12B.
  
 5. M5-2.0: DETAIL 09, DUCT WRAP INSULATION IS SHOWN
 STOPPING AT BOTH SIDES OF THE WALL WITH AN INTERRUPTION
 OF THE VAPOR RETARDER. WHERE DUCTS USED FOR COOLING ARE
 EXTERNALLY INSULATED (WRAPPED RATHER THAN INTERNALLY
 LINED), THE INSULATION SHALL BE COVERED WITH A VAPOR
 RETARDER AND ALL JOINTS AND SEAMS SHALL BE SEALED TO
 MAINTAIN THE CONTINUITY OF THE VAPOR RETARDER IN
 ACCORDANCE WITH FBC, M 604.11 AND 304.1.
 NOTE: THE INSTALLATION OF AN AIR DISTRIBUTION SYSTEM
 SHALL NOT AFFECT THE FIRE PROTECTION REQUIREMENTS
 SPECIFIED IN THE BUILDING CODE IN ACCORDANCE WITH FBC,
 M 603.1. THEREFORE THESE REQUIREMENTS DO NOT APPLY WHEN
 THE DUCT PENETRATION OF A RATED WALL ASSEMBLY IS
 PROTECTED BY OPENING PROTECTIVES SUCH AS FIRE DAMPERS,
 SMOKE DAMPERS OR COMBINATION FIRE/SMOKE DAMPERS.
  