Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop FIRE
Sequence Number 11
Notes
Date Text
2007-12-24 12:20:541. THE WORDING ON THE REVISED NOTE # 26 IS INCORRECT.
 THE WORD DISPLAY SHOULD READ TRANSMIT. FOUR DISTINCT
 SIGNALS WATERFLOW, GENERAL ALARM, TROUBLE AND
 SUPERVISORY SHALL BE TRANSMITTED TO THE CENTRAL STATION
 APPROVED FOR CENTRAL STATION SERVICE.
  
 2. THE REVISED DRAWINGS THAT REFLECT A COMPLETE SMOKE
 DETECTION SYSTEM FOR THE BUILDING SHALL BE SUBMITTED TO
 THE CONSTRUCTION SERVICES DEPARTMENT AS A SEPARATE
 ENTITY AS SHOP DRAWINGS. THESE SHOP DRAWINGS SHALL
 PROVIDE PRODUCT INFORMATION CUT SHEETS, BATTERY
 CALCUALTIONS, RISER DIAGRAMS AND FLOORS PLANS
 ILLUSTRATING DEVICE PLACEMENT FOR THE ENTIRE FIRE ALARM
 SYSTEM.
  
 3. THERE APPEARS TO BE SOME CONFUSION WITH REGARDS TO
 THE FIRE RATING REQUIRED FOR THE FIRE COMMAND ROOM. THE
 FIRE COMMAND ROOM IS REQUIRED TO BE SEPARATED FROM
 OTHER AREAS OF THE BUILDING BY AT LEAST ONE HOUR FIRE
 RATED CONSTRUCTION. SOME DOCUMENTATION PROVIDED WITH
 DRAWINGS INDICATES THAT NO FIRE DAMPER IS NEEDED FOR
 THE ROOM SINCE IT IS NOT FIRE RATED. THIS IS INCORRECT.
 NFPA 1, SECTION 11.9.2 REQUIRES THAT "THE EMERGENCY
 COMMAND CENTER SHALL BE SEPARATED FROM THE REMAINDER OF
 THE BUILDING BY A FIRE BARRIER HAVING A FIRE RESISTANCE
 RATING OF NOT LESS THAN 1 HOUR".
  
 APPROVED PROVISIO:
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREA OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX