Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop P
Sequence Number 10
Notes
Date Text
2007-09-19 11:17:05DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P1-1.3U MANY REVISIONS #11 SHOWN. THE PREVIOUS
 REVISION NUMBER REVIEWED WAS REVISION #4. NO REVISIONS
 SUBMITTED OR APPROVED AFTER THAT. CLOUD AND NUMBER ALL
 REVISIONS AFTER REVISION #4. REVISIONS #10 & #11 ARE
 NOT INDICATED ON THE REVISION INDEX, BUT ARE INDICATED
 ON THE PLANS. THESE REVISIONS ARE NOT CLOUDED.FOR
 EXAMPLE SEE CHANGES IN THE TOILET ROOM B1.108 NOT
 INDICATED AS A REVISION AS WELL AS CHANGES IN THE
 SANITARY AND CHANGES IN THE STORM AND CHANGES IN THE
 LOCATION OF THE FLOOR DRAINS IN THE PUMP ROOMS. THE
 COLUMN LINES HAVE BEEN CHANGED ALSO, (DELETED SOME).
 THESE HAVE NOT BEEN INDICATED AS REVISIONS.--ALL
 CHANGES IN THE SYSTEMS SHALL BE REFLECTED ON THE RISER
 DIAGRAMS TO REFLECT THESE CHANGES. SECTION 106.1.1.
  
 2. SHT P1-5.0 MANY CHANGES ARE NOT INDICATED BY CLOUDS
 OR REVISION NUMBERS. THE LAST REVISION #5, SIGNED,
 SEALED & DATED 2-5-7. ALL CHANGES FROM THE STAMPED
 PLANS SHALL BE CLOUDED AND INDICATED WITH A REVISION
 NUMBER. (PLEASE TURN OFF ALL PREVIOUS CLOUDS AND
 REVISION NUMBERS FROM SHEETS THAT HAVE BEEN APPROVED
 PRIOR TO SUBMITTING NEW REVISIONS. -- LEAVING ON
 PREAPPROVED REVISION CLOUDS AND REVISION NUMBERS ADDS
 TIME TO EACH REVIEW).
  
 3. SHT P1-5.1 REVISION #12 HAS NOT BEEN FOUND. PLEASE
 INDICATE WITH A CLOUD AND A REVISION NUMBER AND PLEASE
 TURN OFF THE CLOUDS AND REVISION NUMBERS FROM
 PREVIOUSLY APPROVED REVISIONS.
  
 4. SHT P3-7.0 ISOMETRIC RISER DIAGRAM FOR RWL-7 DOES
 NOT REFLECT THE FLOOR PLAN. CLEANOUT NOT SHOWN ON THE
 FLOOR PLAN. CLEANOUTS TO BE INSTALLED PER SECTION
 1101.8. SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]