2007-09-19 11:17:05 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| |
| 1. SHT P1-1.3U MANY REVISIONS #11 SHOWN. THE PREVIOUS |
| REVISION NUMBER REVIEWED WAS REVISION #4. NO REVISIONS |
| SUBMITTED OR APPROVED AFTER THAT. CLOUD AND NUMBER ALL |
| REVISIONS AFTER REVISION #4. REVISIONS #10 & #11 ARE |
| NOT INDICATED ON THE REVISION INDEX, BUT ARE INDICATED |
| ON THE PLANS. THESE REVISIONS ARE NOT CLOUDED.FOR |
| EXAMPLE SEE CHANGES IN THE TOILET ROOM B1.108 NOT |
| INDICATED AS A REVISION AS WELL AS CHANGES IN THE |
| SANITARY AND CHANGES IN THE STORM AND CHANGES IN THE |
| LOCATION OF THE FLOOR DRAINS IN THE PUMP ROOMS. THE |
| COLUMN LINES HAVE BEEN CHANGED ALSO, (DELETED SOME). |
| THESE HAVE NOT BEEN INDICATED AS REVISIONS.--ALL |
| CHANGES IN THE SYSTEMS SHALL BE REFLECTED ON THE RISER |
| DIAGRAMS TO REFLECT THESE CHANGES. SECTION 106.1.1. |
| |
| 2. SHT P1-5.0 MANY CHANGES ARE NOT INDICATED BY CLOUDS |
| OR REVISION NUMBERS. THE LAST REVISION #5, SIGNED, |
| SEALED & DATED 2-5-7. ALL CHANGES FROM THE STAMPED |
| PLANS SHALL BE CLOUDED AND INDICATED WITH A REVISION |
| NUMBER. (PLEASE TURN OFF ALL PREVIOUS CLOUDS AND |
| REVISION NUMBERS FROM SHEETS THAT HAVE BEEN APPROVED |
| PRIOR TO SUBMITTING NEW REVISIONS. -- LEAVING ON |
| PREAPPROVED REVISION CLOUDS AND REVISION NUMBERS ADDS |
| TIME TO EACH REVIEW). |
| |
| 3. SHT P1-5.1 REVISION #12 HAS NOT BEEN FOUND. PLEASE |
| INDICATE WITH A CLOUD AND A REVISION NUMBER AND PLEASE |
| TURN OFF THE CLOUDS AND REVISION NUMBERS FROM |
| PREVIOUSLY APPROVED REVISIONS. |
| |
| 4. SHT P3-7.0 ISOMETRIC RISER DIAGRAM FOR RWL-7 DOES |
| NOT REFLECT THE FLOOR PLAN. CLEANOUT NOT SHOWN ON THE |
| FLOOR PLAN. CLEANOUTS TO BE INSTALLED PER SECTION |
| 1101.8. SECTION 106.1.1. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |