Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop FIRE
Sequence Number 10
Notes
Date Text
2007-10-23 12:31:091. SOME SUGGESTED IMPROVED WORDING IS PROVIDED FOR NOTE
 # 26 ON PAGE FAO.1. "THE FIRE ALARM SYSTEM SHALL BE
 ABLE TO TRANSMIT THE FOLLOWING ALARMS TO THE UL LISTED
 CENTRAL STATION APPROVED FOR CENTRAL STATION SERVICE.
  
 A) WATERFLOW
 B) GENERAL ALARM
 C) SUPERVISORY SIGNAL
 D) TROUBLE SIGNAL
  
 2. ANY SPECIAL LOCKING ARRANGEMENTS ON EXIT DOORS SHALL
 COMPLY WITH WITH CHAPTER 7 OF THE LIFE SAFETY CODE,
 101.
  
 3. THE PLANS SEEM TO SUGGEST "PROVIDE AND INSTALL SMOKE
 DETECTORS PER FLORIDA MECHANICAL CODE (FMC) 607.5.4.1
 AT EACH SMOKE DAMPER. SINCE NO FIRE ALARM SYSTEM SHOP
 DRAWINGS HAVE BEEN SUBMITTED IT IS UNKNOWN IF A
 COMPLETE SMOKE DETECTION SYSTEM IS TO BE INSTALLED
 WITHIN THE BUILDING. IN FMC 607.3.2.1 PROVIDES
 INFORMATION ON HOW SMOKE DAMPER ACTUATION METHODS CAN
 BE PERFORMED USING 1-5. PLEASE ADVISE THE MECHANICAL
 SECTION OF THE CONSTRUCTION SERVICES DEPARTMENT AND
 THIS OFFICE IF A COMPLETE SMOKE DETECTION SYSTEM IS
 PLANNED FOR THE BUILDING AND IT THIS SYSTEM IS PLANNED
 TO ACTUATE THE SMOKE DAMPERS. PLEASE COORDINATE ALL
 FIRE/ SMOKE DAMPERS AND FIRE DAMPERS WITH THE
 MECHANICAL DIVISION OF THE CONSTRUCTION SERVICES
 DEPARTMENT.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX