Plan Review Notes For Permit 06100574 |
Permit Number |
06100574 |
|
Review Stop |
E |
Sequence Number |
10 |
|
Notes |
Date |
Text |
2007-11-06 10:41:16 | ** REVISION 12A ** | | | | 1) NOTE: PLEASE SEE MISSING CIRCUIT FOR RECEPTACLE ON | | E1-2.2, THIS WAS REDLINED ON PLANS. | | | | 2) NOTE: THE OUTSTANDING ISSUES WITH THE PROVISO | | PREVIOUSLY ISSUED FOR COMPLETE PHOTO-METRICS FOR | | REVISIONS AND COORDINATION STILL REMAINS. | | IT WAS REQUESTED BY THE ENGINEER OF RECORD FOR AN | | EXTENSION AS WELL AS FROM THE GC. | | | | 3) NOTE: LOW VOLTAGE PERMITS AND PLANS HAVE NOT YET | | BEEN SUBMITTED TO DATE. | | | | 4) NOTE: THE GENERATOR STILL REQUIRES RE-LISTING FOR | | UNIT. THIS WILL BE DONE AT A LATER DATE. | | | | SOME OF THESE ITEMS WERE CARRIED FORTH FROM PREVIOUS | | REVIEWS. | 2007-11-05 16:57:52 | 2007-11-05 16:57:52 | | | | REVIEW COMPLETED, PLANS ARE STILL NEEDED TO BE STAMPED | | AND NOTES NEED TO BE ENTERED AND TYPED INTO SYSTEM. | 2007-11-04 10:28:19 | 2007-11-04 10:28:19 | | | | REVIEW TO CONTINUE ON 11/5 | 2007-11-03 15:34:43 | 2007-11-03 15:10:24 | | | | ONE SET IN ELECTRICAL FOR REVIEW. |
|