Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop P
Sequence Number 1
Notes
Date Text
2006-11-14 17:40:40DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
  
 1. SHT P0-1.0 WATER HEATER SCHEDULE. TWH-1, TWH-2,
 TWH-3, SUBMIT MANUF. SPECIFICATION SHEETS THAT SHOW
 LISTING. SECTION 303.4.
 ****RESPONSE NOTED, WILL BE IN THE SUBMITTAL PACKAGE.
  
 2. SHT P0-1.0 PUMP SCHEDULE. SUBMIT MANUF.
 SPECIFICATION SHEETS THAT SHOW LISTING. SECTION 303.4.
 ****RESPONSE NOTED, WILL BE IN THE SUBMITTAL PACKAGE.
  
 3. SHT P1-1.1 PUMP ROOM A1-112. RPZV BACKFLOW SHALL BE
 INSTALLED A MAXIMUM OF 4' ABOVE THE FLOOR FOR
 CERTIFICATION AND SERVICE.
 ****RESPONSE NOTED, HEIGHT TO BE INDICATED FOR THE
 BACKFLOWS TO BE A MAXIMUM OF 4' ABOVE THE FLOOR.
  
 4. SHTS P1-1.1 THRU P1-5.1 INDICATE RISER NUMBER FOR
 THE SANITARY, STORM, AND WATER RISERS TO TRACK RISERS
 THRU THE BUILDING. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT SOME RISERS INDICATED ON THE
 UPPER FLOORS ARE NOT INDICATED ON THE FIRST FLOOR.
 EXAMPLE P/6 STARTS ON THE FIRST FLOOR, BUT P/8 ALSO
 DRAINS THRU P/6. LABEL P/8 WITH P/6 ON THE FIRST FLOOR.
 ALSO WHY DOES P5 TURN INTO P9?
  
 5. SHTS P1-1.1 THRU P1-1.3 CLEANOUTS REQUIRED BY
 SECTIONS 708.3.1, 708.3.2, 708.3.4, 708.3.5 AND 11-8.1
 (FOR STORM) SHALL BE SHOWN ON THE PLANS. ****RESPONSE
 NOTED, BUT COMMENT NOT ADDRESSED. MANY CLEANOUTS
 REQUIRED ARE NOT INDICATED. MANY CLEANOUTS REQUIRED ARE
 NOT SHOWN. CLEANOUTS AT THE BASE OF STACKS AS SHOWN ARE
 INCORRECT. THEY DO NOT CLEANOUT THE BASE OF THE STACK.
 ALSO SHOW THE CLEANOUTS REQUIRED ON THE RISER
 DIAGRAMS.
  
 6.OK
 7.OK
 8.OK
 9.OK
 10. OK
 11. OK
 12. OK
 13. OK
  
 14. SHT P1-6.0 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF EACH
 AREA, AND SHOW 1/2 AREA OF ALL VERTICAL WALLS,
 INCLUDING PARAPETS, AS WELL AS ALL AREAS OF ROOFS
 DRAINING ONTO THE ROOF FROM ABOVE IN THE CALCULATIONS.
 SECTIONS 1106, AND 1107 WITH ALL SUBSECTIONS. SHOW THE
 LOCATION OF ALL SECONDARY ROOF DRAINS AND OR EMERGENCY
 OVERFLOW SCUPPERS. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT NO CALCULATIONS WERE
 SUBMITTED.
  
 15. OK
 16. OK (SHOWN ON SHT P2-1.0U)
 17. OK
 18. OK
 19. OK
 20. OK
  
 21. SHT P2-2.0 ALL DETAILS, SHOW ALL PIPE SIZES FOR ALL
 SYSTEMS. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT PIPE SIZES ARE NOT SHOWN FOR
 MANY SECTIONS OF PIPES. ALSO SEE TABLES 710.1(1) &
 710.1(2).
  
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
 28. OK
 29. OK
 30. OK
 31. OK
 32. OK
  
 33. SHT P2-3.0 ALL DETAILS, SHOW ALL PIPE SIZES IN ALL
 SYSTEMS. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT PIPE SIZES ARE NOT SHOWN FOR
 MANY SECTIONS OF PIPES. ALSO SEE TABLES 710.1(1) &
 710.1(2).
  
 34. SHT P4-1.0 DETAIL #12 CONDENSATE DRAIN, DETAIL NOT
 APPROVED AS SHOWN. CLARIFY OPEN NIPPLE. CLARIFY GAP
 BETWEEN PIPE AND FLOOR. WHY USE A TEE AT THE BOTTOM OF
 THE TRAP? SECTION 106.1.1.
 ****RESPONSE NOTED, BUT DETAIL NOT EXPLAINED OR REVISED
 AS NOTED. COMMENT NOT ADDRESSED.
  
 35. SHT P4-1.0 DETAIL #13 WATER HEATER DETAIL. PLEASE
 SHOW COMPLIANCE WITH SECTION 607.3.2, THERMAL EXPANSION
 CONTROL. - A SHUT OFF VALVE IS REQUIRED ON EACH SIDE OF
 THE CIRCULATING PUMP. - SUBMIT PUMP MANUF.
 SPECIFICATIONS SHEETS. PUMP SHALL BE LISTED. SECTION
 303.4.
 ****RESPONSE NOTED, BUT THERMAL EXPANSION CONTROL HAS
 NOT BEEN ADDRESSED. CIRCULATION PUMP SPECIFICATIONS
 SHALL BE SUBMITTED WITH SUBMITTAL PACKAGE.
  
 36. SUBMIT A SANITARY HORIZONTAL RISER ISOMETRIC AND
 VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, TRAPS,
 VENTS, CLEANOUTS, OFFSETS, RISER NUMBERS AND DFU'S AS
 THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3.
 ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN,
 ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND DFU'S ARE NOT
 SHOWN AS THEY ACCUMULATE IN THE SYSTEM. ALSO INDICATE
 ON THE FIRST FLOOR WHERE ALL RISERS BEGIN IN THE
 SYSTEM.
  
 37. SUBMIT A STORM HORIZONTAL RISER ISOMETRIC DIAGRAM &
 VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, OFFSETS,
 & CLEANOUTS AND INDICATE THE RISER NUMBERS. SHOW THE
 SQUARE FOOTAGE AS IT ACCUMULATES IN THE SYSTEM. SECTION
 106.3.5.1.3.
 ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN,
 ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND SQUARE
 FOOTAGE AS IT ACCUMULATES IN THE SYSTEM IS NOT
 INDICATED.
  
 38. SUBMIT A WATER RISER ISOMETRIC DIAGRAM. SHOW ALL
 PIPE SIZES, VALVES, WATER HAMMER ARRESTORS, BACKFLOW
 PROTECTION ETC. SECTION 106.3.5.1.3.
 ****RESPONSE NOTED, BUT NOT ALL PIPE SIZES ARE SHOWN,
 NOT ALL REQUIRED VALVES ARE SHOWN, AND ALL WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9, (ICE MAKERS,
 DISHWASHERS, & WASH MACHINES IF FIXTURES ARE
 PROVIDED).
  
 39. SUBMIT A CONDENSATE RISER ISOMETRIC DIAGRAM. SHOW
 ALL PIPE SIZES, VENTS, TERMINATION POINTS ETC. SECTION
 106.3.5.1.3.
 ****RESPONSE NOTED, BUT NO CONDENSATE RISER DIAGRAM
 SUBMITTED AS REQUESTED.
  
 40. ALL PME & FIRE PROTECTION SHEETS. PLANS SHALL BE
 SIGNED, SEALED, AND DATED. SECTION 106.1. ALL TITLE
 BLOCK INFORMATION REQUIRED BY FAC 61G1-23.002 AND FS
 471.025 SHALL BE SUBMITTED ON EACH SHEET. ****RESPONSE
 NOTED, BUT THE SEAL USED IS NOT APPROVED. NEW SEALS
 SHALL INDICATE THE WORD "LICENSE" IN THE SEAL. (SEE
 ATTACHED SHEET FROM THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS).
  
 **************NEW COMMENTS**************
  
 1B. SHTS P1-1.0U, P1-1.1U, P1-1.1 & P1-2.1. RWL-4 DOES
 NOT REFLECT THE SQUARE FOOTAGE SHOWN ON RISER DIAGRAM
 OR ROOF PLAN. PLEASE CORRELATE RISER, FLOOR PLAN, &
 ROOF PLAN. SECTION 106.1.1.
  
 2B. SHTS P1-1.OU & P1-1.1U ALL RWL'S THAT CONNECT TO
 RWL-4 TO BE INDICATED ON THE 1ST FLOOR. THIS WILL AID
 IN TRACING THE RWL'S THROUGH THE BUILDING AND TO VERIFY
 PIPE SIZES. SECTION 106.1.1.
  
 3B. SHTS P1-1.1U & P2-1.01 DETAIL #6 THE SINK SHALL NOT
 DRAIN THRU THE WET VENT FOR THE TOILET ROOM. THE
 DISCHARGE FOR THE SINK SHALL CONNECT DOWNSTREAM OF THE
 TOILET ROOM FIXTURES. SECTION 909.1.
  
 4B. SHT P1-1.2U FD-2 IN D1.106 LOADING REQUIRES A VENT.
 THIS DOES NOT REFLECT THE RISER DIAGRAM PIPING. THE
 FLOOR IS SLOPING AWAY FROM THE TRENCH DRAIN. PLEASE
 CLARIFY. SECTIONS 901.2.1, 106.1.1.
  
 5B. SHT P1-1.2U CLEANOUT REQUIRED AT THE BASE OF P/1 &
 P/10 RISERS, NEAR THE JUNCTION OF THE BUILDING DRAIN
 AND THE BUILDING SEWER, AND AT ALL CHANGES OF DIRECTION
 OVER 45 DEGREES. PLEASE INDICATE ON PLANS. SECTIONS.
 708.3.3, 708.3.4, 708.3.5.
  
 6B. SHTS P1-1.2U, ASSOCIATED RISER DIAGRAMS, AND
 ENLARGED FLOOR PLANS. INDICATE HOW THE STACKS P/1 &
 P/10 CAN DRAIN INTO THE TOILET GROUP FIXTURE BRANCH.
 SUBMIT A DETAIL SHOWING THE 4" CLEANOUT TEE, THE 4"
 CROSS FOR THE FIXTURE BRANCH, AND THE 4" DOUBLE
 Y/EIGHTH BEND FITTINGS STACKED ON TOP OF EACH OTHER.
 WILL THEY BE AT THE RIGHT HEIGHT FOR THE W/C'S?SEE
 SECTION 908.3 ALSO. SECTION 106.1.1. (STACKS SHOULD
 CONNECT TO THE BUILDING DRAIN AND FIXTURE GROUPS SHOULD
 CONNECT TO THE STACK SO THAT THE STACK DOES NOT RUN
 THRU THE MIDDLE OF THE FIXTURE GROUP).
  
 7B. SHTS P1-1.3U, P1-2.0, P1-2.3, P1-3.3, & P1-4.3
 RWL-6 DOES NOT REFLECT THE SQUARE FOOTAGE SHOWN ON THE
 RISER DIAGRAM, NOR ON THE ROOF PLAN. PLEASE CORRELATE
 INFORMATION. SECTION 106.1.1 & TABLE 1106.3.
  
 8B. SHT P1-1.3 THE WATER SUPPLY TO THE ICE MAKER SHALL
 CONNECT UPSTREAM OF THE MAKE-UP WATER FOR THE COOLING
 TOWERS. - SHOW THE LOCATIONS FOR RWL-6 & RWL-7. SECTION
 106.1.1 & 608.1.
  
 9B. SHT P1-2.1 RISER P/8 NOT INDICATED ON THE 1ST
 FLOOR. PLEASE SHOW WHERE RISERS START ON THE FIRST
 FLOOR. SECTION 106.1.1.
  
 10B. SHT P1-3.2 RISER P/4 SHOWN AT COL. LINE H/2 WAS
 RISER P/2 ON THE FLOOR BELOW. PLEASE CLARIFY. SECTION
 106.1.1.
  
 11B. SHT P1-4.1 C/O FOR S-1 SINK PIPING CONNECTING TO
 RISER P/7 IS NOT APPROVED AS INDICATED. SECTION 706.3.
 - RISER P/9 IS NOT INDICATED ON PREVIOUS LEVELS. PLEASE
 CLARIFY. - RISER P/5 SHOWN ON PREVIOUS LEVEL IS NOT
 INDICATED. PLEASE CLARIFY.
  
 12B. SHT P1-4.1 SHOW RISER P/3 VTR. - NOTE STATES "SEE
 01 ON DRAWING P2-3.0". INFORMATION NOT SHOWN ON DETAIL
 01. PLEASE CLARIFY. - SHOW THE VENTING TO REFLECT THE
 FLOOR PLAN FOR KINK S-1 CONNECTED TO RISER P/8. - 4"
 SANITARY - 4" VTR AT COL. LINE E/8 IS SHOWN AS AN
 OFFSET ON THE RISER DIAGRAM. PLEASE CORRELATE FLOOR
 PLAN AND SANT. RISER DIAGRAM. SECTION 106.1.1.
  
 13B. SHT P1-4.2 SANT. RISER P/2 VTR NOT SHOWN. SECTION
 106.1.1.
  
 14B. SHOW ALL PIPE SIZES PER TABLE 1106.3.
  
 15B. SHT P1-6.0 SHOW THE LOCATIONS FOR ALL VTR'S. -
 INDICATE THE RWL EACH ROOF DRAIN IS CONNECTED TO.
 SECTION 106.1.1.
  
 16B. SHT P2-1.0U DETAIL 1, FLOOR DRAINS IN C1.104 ARE
 NOT VENTED. SECTION 901.2.1. - THE PIPING AT THE LAVS
 IN ROOM C1.103 DOES NOT REFLECT THE RISER DIAGRAM.
 PLEASE CORRELATE. SECTION 106.1.1.
  
 17B. SHT P2-1.0U DETAIL 2 DOES NOT REFLECT THE PIPING
 LAYOUT SHOWN ON P1-1.2U. - SUBMIT A DETAIL FOR THE
 SANT. PIPING ARRANGEMENT FOR THE DRINKING FOUNTAINS,
 SHOW HOW THE PIPING CONNECTS THROUGH THE SIDE OF THE
 D.F. UNITS. - SUBMIT A DETAIL FOR THE FITTING
 ARRANGEMENT WHERE THE TOILET ROOM FIXTURES CONNECT TO
 THE BLDG. DRAIN. SECTION 106.1.1.
  
 18B. SHT P2-1.0U DETAILS 3 & 4, SUBMIT A DETAIL FOR THE
 PIPING ARRANGEMENT FOR THE D.F.'S. SECTION 106.1.1.
  
 19B. SHT P2-1.0U DETAIL 6, SINK SHALL CONNECT
 DOWNSTREAM OF THE WET VENTED FIXTURES IN THE TOILET
 ROOM. SECTION 909.1.
  
 20B. SHT P2-1.0 DETAIL 1 DOES NOT REFLECT THE FLOOR
 PLAN OR RISER DIAGRAM. NO WATER PIPING TO WH'S SHOWN.
 SECTION 106.1.1.
  
 21B. SHT P2-1.0 DETAIL 2 DOES NOT REFLECT THE FLOOR
 PLAN. SHOWS 2" WATER SUPPLY. SECTION 106.1.1.
  
 22B. SHT P2-1.0 DETAIL 4 DOES NOT REFLECT THE FLOOR
 PLAN. NO WATER TO WH'S & SHOWS 2" WATER SUPPLY. SECTION
 106.1.1.
  
 23B. SHT P2-1.0 DETAIL 6 DOES NOT REFLECT THE FLOOR
 PLAN FOR SANT. TO LAVS. FLOOR DRAINS NOT VENTED.
 SECTIONS 106.1.1 & 901.2.1.
  
 24B. SHT P2-2.0 DETAIL 1, INDICATE RISER NUMBERS.
 SECTION 106.1.1.
  
 25B. SHT P2-2.0 DETAIL 2, SUBMIT A DETAIL FOR SANT.
 PIPING TO D.F'S. - DOES NOT REFLECT THE RISER DIAGRAM.
 SECTION 106.1.1.
  
 26B. SHT P2-2.0 DETAIL 3, SUBMIT A DETAIL FOR SANT.
 PIPING TO D.F.'S - INDICATE RISERS FOR COLD WATER
 DOWNSTREAM OF LAST W/C'S. HOT WATER LINE NOT SHOWN THRU
 BATHROOM FIXTURES. SECTION 106.1.1.
  
 27B. SHT P2-2.0 DETAIL 4, NO PIPING TO FLOOR DRAINS
 SHOWN. SECTION 106.1.1.
  
 28B. SHT P2-2.0 DETAIL 5, SUBMIT A DETAIL FOR SANT.
 PIPING TO D.F.'S. SECTION 106.1.1.
  
 29B. SHT P2-2.0 DETAIL 6, SUBMIT A DETAIL FOR SANT.
 PIPING TO D.F.'S. SECTION 106.1.1. - SANT. RISER
 UPSTREAM OF JANITOR SINK NOT SHOWN. (SEE RISER
 DIAGRAM). SECTION 106.1.1.
  
 30B. SHT P2-3.0 DETAIL 1, INDICATE WHERE SANT. BRANCH
 LINE CONNECTS TO THE SANT. RISER. - FLOOR DRAIN SHOWS
 NO PIPING. SECTION 106.1.1.
  
 31B. SHT P2-3.0 DETAIL 2, NO PIPING SHOWN TO FLOOR
 DRAINS. - SUBMIT A DETAIL FOR D.F. SANT. PIPING.
 SECTION 106.1.1.
  
 32B. SHT P2-3.0 DETAIL 3, NO PIPING SHOWN TO FLOOR
 DRAINS. - SUBMIT A DETAIL FOR D.F. SANT. PIPING.
 SECTION 106.1.1.
  
 33B. SHT P2-3.0 DETAIL 4, NO PIPING SHOWN TO FLOOR
 DRAINS. - SUBMIT A DETAIL FOR D.F. SANT. PIPING.
 SECTION 106.1.1.
  
 34B. SHT P3.1.0 SANT RISER DIAGRAM, TRAPS ARE REQUIRED
 ON ALL DRINKING FOUNTAINS. SECTION 1002.1. - 1ST FLOOR
 LAVS PIPING DOES NOT REFLECT THE FLOOR PLAN. - FLOOR
 DRAINS DOWNSTREAM OF RISER P/1 ARE NOT VENTED. SECTION
 901.2.1. - A C/O IS REQUIRED AT THE BASE OF STACK P/1
 SECTION 708.3.4 - SHOW THE CONNECTION DETAIL AT THE
 BASE OF STACK P/1 WITH A 4" CLEANOUT, A 4" CROSS, AND
 4" WYE FITTINGS INDICATING THE HEIGHT OF THE W/C
 STUBOUT. - W/C-1 AT THE BASE OF STACK IS NOT VENTED.
 SECTION 901.2.1. -W/C ON 2ND FLOOR IS NOT VENTED.
 SECTION 901.2.1. - LAV ON 3RD FLOOR NOT VENTED. SECTION
 901.2.1. - INDICATE HOW/WHERE PIPING FOR LAVS & FLOOR
 DRAINS CONNECT TO THE RISER/BRANCH ON THE 2ND, 3RD, &
 4TH FLOORS. THE FITTINGS INDICATE THAT THE PIPING IS
 SLOPED TO THE LAVS. PLEASE CLARIFY. - MEN C4.104 DOES
 NOT REFLECT ROOM NUMBER ON THE FLOOR PLAN. - PIPING FOR
 FLOOR DRAINS & LAVS 4TH FLOOR DOES NOT REFLECT THE
 FLOOR PLAN. SECTION 106.1.1.
  
 35B. ALL RISER DIAGRAMS, ALL FLOOR PLANS FOR ALL
 SYSTEMS. INDICATE THE PIPE SIZE. SECTION 106.1.1.
  
 36B. SHT P3-2.0 JANITOR ROOM PIPING DOES NOT REFLECT
 THE FLOOR PLAN. - TRAPS REQUIRED ON ALL DRINKING
 FOUNTAINS. SECTION 1002.1. - CLEANOUTS REQUIRED AT THE
 BASE OF ALL STACKS. 708.3.4. - PIPING TO FLOOR DRAIN
 SHOWN ABOVE THE FLOOR IN ROOM D1.101. PLEASE CLARIFY. -
 PIPING AT THE BASE OF RISER P/2 DOES NOT REFLECT THE
 FLOOR PLAN. - PIPING TO FD-2 AT THE LOADING D1.106 DOES
 NOT REFLECT THE FLOOR PLAN. - PIPING FOR A1.108/A1.109
 DOES NOT REFLECT THE FLOOR PLAN. - ROOM D2.103 IS
 INDICATED AS D2.104 ON THE FLOOR PLAN. CORRELATE
 INFORMATION. - ALL VENTING AT RISER P/10 STOPS AT LEVEL
 2. SECTION 903.3 VTR REQUIRED. - TOILET ROOM A2.708 IS
 INDICATED AS A2.706 ON THE FLOOR PLAN. CORRELATE
 INFORMATION. - BATHROOM RISER DOES NOT REFLECT THE
 FLOOR PLAN. (NO FD). - PIPING TO ROOM A4.414 DOES NOT
 REFLECT THE FLOOR PLAN. - CLEANOUT PIPING DOWNSTREAM OF
 C4.101 IS NOT APPROVED AS PIPED. SECTION 706.3. -
 PIPING ON RISER DOES NOT REFLECT THE FLOOR PLAN
 UPSTREAM OF C3.105. - JANITOR SINK C3.105 IS NOT
 VENTED. SECTION 901.2.1. - FLOOR DRAIN CONNECTION AT
 BRANCH LINE 4TH FLOOR DOES NOT REFLECT THE FLOOR PLAN.
 - PIPING AT A2.107 DOES NOT REFLECT THE FLOOR PLAN. (NO
 F.D. PIPING). - PIPING AT ROOM A3.111 DOES NOT REFLECT
 THE FLOOR PLAN AT THE LAVS. - ROOM A3.111 SUBMIT A
 DETAIL FOR FITTING TO W/C & LAVS. - ROOM D2.105 SHOWN
 AS D2.106/D2.107 ON FLOOR PLANS. CORRELATE INFORMATION.
 - ROOM C3.410/C3.412 FLOOR DRAIN FITTING ARE SHOWN TO
 BE INSTALLED AGAINST THE FLOW. SECTION 706.3. - SECTION
 106.1.1.
  
 37B. SHT P3-3.0 PIPING TO A3.304 & DOWNSTREAM DOES NOT
 REFLECT THE FLOOR PLAN. - VENT PIPING FROM S-1 SINK
 DOES NOT REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN. -
 TRAPS REQUIRED ON ALL DRINKING FOUNTAINS. SECTION
 1002.1. - S-1 SINK SHALL NOT DRAIN THRU THE WET VENT OF
 THE TOILET ROOM A1.303. SINK SHALL DISCHARGE DOWNSTREAM
 OF THE W/C & LAV. SECTION 909.1. - INDICATE P/8 WITH
 P/6 AT THE BASE OF THE STACK WHERE IT BEGINS. - PIPING
 TO ROOMS A1.105/A1.106 DOES NOT REFLECT THE FLOOR PLAN.
 FLOOR DRAIN PIPING IS SHOWN AS ABOVE THE FLOOR. - P/5 &
 P/9 BEGIN AT THE BASE OF THE STACK. PLEASE INDICATE ON
 RISER DIAGRAM. - PIPING FOR A3.102/A3.103 DOES NOT
 REFLECT THE FLOOR PLAN. - CLEANOUT REQUIRED AT THE BASE
 OF P/9 STACK. - PIPING TO FLOOR DRAINS IN ROOMS
 A3.102/A3.103 ARE ABOVE THE FLOOR. -W/C AT THE BASE
 OF STACK NOT VENTED. SECTION 901.2.1. - INDICATE WHERE
 LINES TO FLOOR DRAINS IN ROOMS A4.103/A4.104 &
 A5.103/A5.104 ARE CONNECTING TO THE BRANCH/STACK. -
 PIPING FOR A4.103/A4.104 DOES NOT REFLECT THE FLOOR
 PLAN. - W/C AT RISER STACK A4.103 IS NOT VENTED.
 SECTION 901.2.1. - PIPING FOR A4.105 DOES NOT REFLECT
 THE FLOOR PLAN. SECTION 106.1.1.
  
 38B. SHT P3-4.0 GARAGE WATER RISER DIAGRAM SHOWS WH'S
 BELOW GRADE. PLEASE CLARIFY. - SHUT OFF VALVE REQUIRED
 ON WH SHOWN BELOW GRADE. SECTION 606.2(2). - A WATER
 HAMMER ARRESTOR IS REQUIRED AT THE ICE MACHINE. SECTION
 604.9. - SHUT OFF VALVES ARE REQUIRED FOR THE HOSE
 BIBBS ON THE ROOF. SECTION 606.2(2). - SANITARY RISER
 DIAGRAM, FLOOR DRAINS ARE NOT APPROVED FOR INDIRECT
 WASTE. A FLOOR SINK OR HUB DRAIN IS REQUIRED FOR THE
 ICE MACHINE. SECTIONS 802.3 & 802.3.2. - SECTION
 106.1.1.
  
 39B. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - RISER DOES NOT REFLECT
 THE FLOOR PLAN. OFFSETS BETWEEN THE
 METER AND THE RISER ARE NOT SHOWN. -
 INDICATE WHAT THE RISERS ABOVE THE TEE
 AT THE TOP OF THE RISER AND AT THE
 GENERATOR ARE FOR. FUTURE BTU LOAD AND
 DISTANCE MAY REQUIRE CHANGES IN THE
 GAS SYSTEM WHEN ADDED.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD-
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 40B. SHT P3-5.0 NO HOT WATER LINE SHOWN IN 1ST THRU 4TH
 FLOOR TOILET ROOMS OFF WATER RISER W/1. - WATER RISER
 DOES NOT REFLECT THE FLOOR PLAN AT THE LAVS. - FULL
 OPEN VALVES ARE REQUIRED ON ALL WATER DOWN-FEED LINES.
 SECTION 606.1(4). - RISER DOES NOT REFLECT THE FLOOR
 PLAN AT ROOMS C2.104/C2.103. (2 LAVS SHOWN EACH TOILET
 ROOM). - PIPE SIZE SUPPLYING ROOMS D1.101/D1.102,
 JANITOR ROOM D1.110, TOILET ROOMS A1.108/A1.109. -
 INDICATE THAT RISERS W/4, W/5, & W/8 RISERS START WITH
 RISER W/2 ON THE 1ST FLOOR. SECTION 106.1.1.
  
 41B. SHT P3-6.0 RISERS 4, 5 & 8 ARE NOT INDICATED ON
 THE 1ST FLOOR. - RISER DOES NOT REFLECT THE FLOOR PLAN
 ROOMS C3.107/C3.108 AT JAN. SINK, ROOMS C3.410/C3.412,
 AE.111, A4.103/A4.104, A4.105 AND THE TOP OF RISER W/4
 TO ROOM A5.105, PIPE SIZE AT ROOM A2.209 & SUPPLY TO
 TOILET ROOM ADJACENT, PIPE SIZE SUPPLYING RISER W/8 &
 RISER, SUPPLY LINE TO ROOMS D2.102/D2.103. - W/2 NOT
 FOUND ON 4TH FLOOR AS INDICATED ON RISER. SECTION
 106.1.1.
  
 42B. SHT P3-7.0 SIZE ALL PIPE PER SECTION 1106.3, AND
 SHOW ALL PIPE SIZES ON THE RISER. - RISER DOES NOT
 REFLECT THE FLOOR PLAN TOP FLOORS RWL/6 & RWL/7. -
 RISERS INDICATE A 5TH FLOOR, BUT FLOOR PLAN DOES NOT
 SHOW A 5TH FLOOR. - RISER SHOWS TRENCH DRAINS ON TWO
 FLOORS, BUT ONLY SHOW TRENCH DRAINS ON 1 FLOOR, (ROOF
 LEVEL), ON THE FLOOR PLAN. -RWL'S 9 THRU 14 SHOW OFFSET
 PIPING FOR ROOF DRAINS IN THE 4TH FLOOR CEILING, BUT
 INDICATE THE ROOF DRAINS TO BE ON THE 4TH LEVEL. PLEASE
 CLARIFY. - PIPE SIZING IS INCORRECT AT 8"/11,715SF,
 6"/5077SF, 6"/6657SF. TABLE 1106.3. - RWL/9 INDICATES
 PIPING IN 3RD FLOOR CEILING, BUT ROOF DRAINS ARE TO BE
 ON THE 3RD LEVEL. PLEASE CLARIFY. - RWL/15 DOES NOT
 REFLECT THE FLOOR PLAN TO 4" ROOF DRAINS. - PIPING AT
 THE 1ST FLOOR CEILING CONNECTING TO ROOF DRAINS ON THE
 1ST LEVEL. PLEASE CLARIFY. SECTION 106.1.1.
  
 43B. SHTS 1,2,3 OF 3 ARE NOT SIGNED, SEALED, & DATED AS
 REQUIRED PER FS 472.025(1). ALSO SEE SHT 1 WHICH STATES
 "NOT VALID UNLESS SEALED WITH SURVEYOR'S EMBOSSED SEAL
 AND SIGNATURE"
  
 44B. SHTS C1, C5 THRU C22 ENGINEERING CERTIFICATE OF
 AUTHORIZTION IS REQUIRED IN THE TITLE BLOCK.
 61G15-23.002(2) & FS 471.025. - AN EMBOSSED SEAL IS
 REQUIRED TO IMPRESS REQUIRED INFORMATION ON EACH SHEET.
 UNABLE TO GLEAN ALL INFORMATION REQUIRED FROM SEAL.
 PLEASE RESEAL PLANS.
  
 45B. SHTS LP-0 THRU LP-3 & IR-1 THE CERTIFICATE OF
 AUTHORIZATION IS REQUIRED IN THE TITLE BLOCK.
 61G1-16.004(1) & FS 481.319.
  
 46B. SHT LL-1 IS MISSING THE TITLE BLOCK INFORMATION
 REQUIRED IN 61G1-16.004.
  
 47B. SHT IR-1 THE CONTROLER & RAIN SENSOR LOCATIONS ARE
 REQUIRED ON PLANS. SECTION 106.1.1.
  
 48B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 2ND
 FLOOR DRINKING FOUNTAINS SHOWS 4 REQUIRED, BUT ONLY 3
 ARE REQUIRED PER TABLE 403.1. FIXTURE COUNT INDICATES
 ONLY 2 ARE PROVIDED. PLEASE PROVIDE REQUIRED AMOUNT OF
 DRINKING FOUNTAINS.
  
 49B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 3RD
 FLOOR DRINKING FOUNTAINS SHOW ONLY 3 ARE REQUIRED. PER
 TABLE 403.1, 4 DRINKING FOUNTAINS ARE REQUIRED. PLEASE
 UPDATE FIXTURE COUNT.
  
 50B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 4TH
 FLOOR DRINKING FOUNTAINS INDICATE 4 REQUIRED, BUT ONLY
 3 ARE PROVIDED. PLEASE PROVIDE 4 DRINKING FOUNTAINS.
 TABLE 403.1.
  
 51B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 1ST
 FLOOR DRINKING FOUNTAINS 2 REQUIRED PER TABLE 403.1,
 BUT READS 1 REQUIRED. PLEASE CORRECT FIXTURE COUNT
 REQUIRED.
  
 52B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 3RD
 FLOOR DRINKING FOUNTAINS 4 REQUIRED PER TABLE 403.1,
 BUT READS 2 REQUIRED. PLEASE CORRECT FIXTURE COUNT
 REQUIRED. - SHOWS 2 PROVIDED, BUT 4 ARE REQUIRED.
 PLEASE CORRECT INFORMATION.
  
 53B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 4TH
 FLOOR LAVS REQUIRED 2, INDICATED AS 1. PLEASE CORRECT
 THE FIXTURE COUNT. TABLE 403.1.
  
 54B. SHT LSO.0 LIBRARY/MUSEUM INDICATES A RESTURANT IN
 OCCUPANT LOAD 1ST FLOOR.PLEASE CONTACT LYNN MASSON,
 ENVIRONMENTAL COMPLIANCE MANAGER CONCERNING THE
 POSSIBLE REQUIREMENT FOR A GREASE INTERCEPTOR. CONTACT
 LYNN BY PHONE (561) 822-2271, OR FAX (561) 822-2279, OR
 E-MAIL [email protected].
  
 55B. SHT LSO.0 INDICATES ASSEMBLY OCCUPANCY FOR THE
 CITY HALL AND LIBRARY/MUSEUM. POTTY PARITY IS REQUIRED
 PER SECTION 403.1.1 AND HAS BEEN INDICATED IN THE 50%
 REVIEW BY PAUL SCHMITZ. THIS HAS NOT BEEN ADDRESSED.
 PLEASE SHOW COMPLIANCE WITH THIS REQUIREMENT.
  
 56B. SHT A2-0 3 AREAS SHOW STORM WATER FROM ROOF AREAS
 ABOVE THAT CONTRIBUTE TO THE MAIN ROOF AREAS BELOW. THE
 SLOPE OF THE MAIN ROOF AND THE LOCTION OF THE DOWNSPOUT
 IS SHOWING THE TOTAL AREA DRAINING TO ONE ROOF DRAIN,
 BUT THE AREA IS DIVIDED EQUALLY BETWEEN TWO ROOF
 DRAINS. THE SIZING FOR THE ROOF DRAINS WILL HAVE TO BE
 RECHECKED TO ACCOUNT FOR THE AMOUNT OF AREA DRAINING TO
 ONE DRAIN, NOT TWO. TABLE 1106.3. (SEE ROOF AREAS AT
 COL. LINES 1THRU 4/A THRU D, 7 THRU 9.1/A THRU D, AND 4
 - 5/E THRU H).
  
 57D. SHTS A2-0, A2-1, A2-2, A2-3 SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS. INDICATE THE
 CONTRUBUTION ADD FROM 1/2 AREA OF ALL VERTICAL WALLS,
 INCLUDING PARAPETS, AND ROOF AREAS FROM ABOVE ADDED TO
 THE ROOF SECTIONS. THIS IS REQUIRED FOR ALL ROOF
 LEVELS. SQUARE FOOTAGE IS SHOWN, BUT NO CALCULATIONS
 WERE SUBMITTED. CONTRIBUTING VERTICAL AREAS FOR WALLS
 IS UNCLEAR. IS THE AREA SHOWN INDICATED PER WALL, OR
 TOTAL FOR ALL WALLS SHOWN. PLEASE CLARIFY. SECTIONS
 1106.1, 1106.2, 1106.3, 1106.4.
  
 58B. SHT A2-0 UPPER ROOF BY DOME SHOWS A DETAIL
 INDICATOR 20/A2-D.1. DETAIL 20 NOT FOUND ON SHT A2-D.1.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 59B. SHT A2-D.1 DETAIL 04 SHOW HEIGHT AND WIDTH AND
 INDICATE THE MEASUREMENT FROM THE ROOF TO THE FLOW LINE
 OF THE SCUPPER. SECTIONS 106.1.1 AND 1503.4.3.
  
 60B. SHT A6-1.1 DETAILS 1 THRU 6. SHOW THE TURNING AREA
 IN THE TOILET ROOMS. NOT IN THE ACCESSIBLE STALLS.
 SECTION 11-4.22.3.
  
 61B. SHT A6-1.1 DETAIL 2, SHOW THE CLEAR FLOOR SPACE
 FOR THE URINAL. SECTION 11-4.18.3.
  
 62B. SHT A6-1.1 DETAIL 4, ACCESSIBLE W/C SHALL BE 1'6"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG.
 11-28. LAV TO BE MIN. 15" (C/L OF CLEAR FLOOR SPACE).
  
 63B. SHT A6-1.1 DETAIL 7, ACCESSIBLE W/C SHALL BE 1'6"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG.
 11-28. (SHOWS 2'2").
  
 64B. SHT A6-2.1 DETAILS 2, 6 & 7 SHOWTHE TURNING AREA
 IN THE TOILET ROOMS. NOT IN THE ACCESSIBLE STALLS.
 SECTION 11-4.22.3.
  
 65B. SHT A6-2.1 DETAIL 4, ACCESSIBLE W/C SHALL BE 1'6"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG.
 11-28.
  
 66B. SHT A6-3.1 DETAIL 1, SHOW THE TURNING AREA IN THE
 LOCKER ROOM AREA. SECTION 11-4.2.3.
  
 67B. SHT A6-3.1 DETAILS 2, 3, 4 & 6, SHOW THE TURNING
 AREA IN THE TOILET ROOMS, NOT IN THE ACCESSIBLE STALLS.
 SECTION 11-4.22.3.
  
 68B. SHT A6-4.1 DETAILS 1 & 2, SHOW THE TURINING AREA
 IN THE TOILET ROOMS, NOT IN THE ACCESSIBLE STALLS.
 SECTION 11-4.22.3.
  
 69B. SHT A6-5.1 DETAIL 1, SHOW THE TURNING AREA IN THE
 TOILET ROOM, AND SHOW THE CLEAR FLOOR SPACE FOR THE
 URINAL. SECTIONS 11-4.22.3 AND 11-4.18.3.
  
 70B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS
 C1.105, C1.106, A2.705, A2.706, A2.210, A2.211, A3.111,
 A3.114, C3.410, AND C3.412 ALL INDICATE THE WALLS TO BE
 PAINTED. PLEASE INDICATE HOW THIS COMPLIES WITH THE
 REQUIREMENT FOR "SMOOTH, HARD, NONABSORBENT WALLS AS
 REQUIRED IN SECTION 1210.2.
  
 71B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS D2.10
 & D2.104 SHOW NO WALL FINISH AND THE FLOORING/BASE
 INDICATE RUBBERIZED FLOORING. INDICATE HOW THIS
 COMPLIES WITH "SMOOTH, HARD, NONABSORBENT FLOORS AS
 REQUIRED IN SECTION 1210.1.
  
 72B. SHT A9-4.1 INDICATE THE ROOM NUMBERS THAT THE
 DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.2 CLEARANCES
 C. 11-4.19.4 EXPOSED PIPES & CLEARANCES
  
 73B. SHT A9-4.2 INDICATE THE ROOM NUMBERS THAT THE
 DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 DETAIL #1
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.2 CLEARANCES
 C. 11-4.19.4 EXPOSED PIPES & CLEARANCES
  
 DETAIL #2
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.2 CLEARANCES
 C. 11-4.19.4 EXPOSED PIPES & CLEARANCES
  
 74B. SHT A9-4.4 INDICATE THE ROOM NUMBERS THAT THE
 DETAILS ARE REFERENCING.SHOW COMPLIANCE WITH THE
 FOLLOWING:
 DETAILS #1 - #2 - #3
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
  
 75B. SHT A9-4.4 SHOW THE FOLLOWING FOR COMPLIANCE:A.
 11-4.19.2 CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 D. 11-4.21.5 CONTROLS
 E. 11-4.21.7 CURBS
  
 76B. SHTS A1.307, A1.709, A2.209, A2.315, A2.407,
 A3.109, C3.409, C3.310, A5.504 - SHOW COMPLIANCE WITH
 THE FOLLOWING
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED)
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. SUBMITTING THE RED
 LINED SET OF PLUMBING SHEETS WHEN RESUBMITTING FOR
 REVIEW WILL HELP EXPEDITE THE PERMIT ALSO. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS