Date |
Text |
2006-11-14 17:40:40 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| FROM PREVIOUS REVIEW: |
| |
| 1. SHT P0-1.0 WATER HEATER SCHEDULE. TWH-1, TWH-2, |
| TWH-3, SUBMIT MANUF. SPECIFICATION SHEETS THAT SHOW |
| LISTING. SECTION 303.4. |
| ****RESPONSE NOTED, WILL BE IN THE SUBMITTAL PACKAGE. |
| |
| 2. SHT P0-1.0 PUMP SCHEDULE. SUBMIT MANUF. |
| SPECIFICATION SHEETS THAT SHOW LISTING. SECTION 303.4. |
| ****RESPONSE NOTED, WILL BE IN THE SUBMITTAL PACKAGE. |
| |
| 3. SHT P1-1.1 PUMP ROOM A1-112. RPZV BACKFLOW SHALL BE |
| INSTALLED A MAXIMUM OF 4' ABOVE THE FLOOR FOR |
| CERTIFICATION AND SERVICE. |
| ****RESPONSE NOTED, HEIGHT TO BE INDICATED FOR THE |
| BACKFLOWS TO BE A MAXIMUM OF 4' ABOVE THE FLOOR. |
| |
| 4. SHTS P1-1.1 THRU P1-5.1 INDICATE RISER NUMBER FOR |
| THE SANITARY, STORM, AND WATER RISERS TO TRACK RISERS |
| THRU THE BUILDING. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT SOME RISERS INDICATED ON THE |
| UPPER FLOORS ARE NOT INDICATED ON THE FIRST FLOOR. |
| EXAMPLE P/6 STARTS ON THE FIRST FLOOR, BUT P/8 ALSO |
| DRAINS THRU P/6. LABEL P/8 WITH P/6 ON THE FIRST FLOOR. |
| ALSO WHY DOES P5 TURN INTO P9? |
| |
| 5. SHTS P1-1.1 THRU P1-1.3 CLEANOUTS REQUIRED BY |
| SECTIONS 708.3.1, 708.3.2, 708.3.4, 708.3.5 AND 11-8.1 |
| (FOR STORM) SHALL BE SHOWN ON THE PLANS. ****RESPONSE |
| NOTED, BUT COMMENT NOT ADDRESSED. MANY CLEANOUTS |
| REQUIRED ARE NOT INDICATED. MANY CLEANOUTS REQUIRED ARE |
| NOT SHOWN. CLEANOUTS AT THE BASE OF STACKS AS SHOWN ARE |
| INCORRECT. THEY DO NOT CLEANOUT THE BASE OF THE STACK. |
| ALSO SHOW THE CLEANOUTS REQUIRED ON THE RISER |
| DIAGRAMS. |
| |
| 6.OK |
| 7.OK |
| 8.OK |
| 9.OK |
| 10. OK |
| 11. OK |
| 12. OK |
| 13. OK |
| |
| 14. SHT P1-6.0 SUBMIT CALCULATIONS FOR PRIMARY AND |
| SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF EACH |
| AREA, AND SHOW 1/2 AREA OF ALL VERTICAL WALLS, |
| INCLUDING PARAPETS, AS WELL AS ALL AREAS OF ROOFS |
| DRAINING ONTO THE ROOF FROM ABOVE IN THE CALCULATIONS. |
| SECTIONS 1106, AND 1107 WITH ALL SUBSECTIONS. SHOW THE |
| LOCATION OF ALL SECONDARY ROOF DRAINS AND OR EMERGENCY |
| OVERFLOW SCUPPERS. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT NO CALCULATIONS WERE |
| SUBMITTED. |
| |
| 15. OK |
| 16. OK (SHOWN ON SHT P2-1.0U) |
| 17. OK |
| 18. OK |
| 19. OK |
| 20. OK |
| |
| 21. SHT P2-2.0 ALL DETAILS, SHOW ALL PIPE SIZES FOR ALL |
| SYSTEMS. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT PIPE SIZES ARE NOT SHOWN FOR |
| MANY SECTIONS OF PIPES. ALSO SEE TABLES 710.1(1) & |
| 710.1(2). |
| |
| 22. OK |
| 23. OK |
| 24. OK |
| 25. OK |
| 26. OK |
| 27. OK |
| 28. OK |
| 29. OK |
| 30. OK |
| 31. OK |
| 32. OK |
| |
| 33. SHT P2-3.0 ALL DETAILS, SHOW ALL PIPE SIZES IN ALL |
| SYSTEMS. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT PIPE SIZES ARE NOT SHOWN FOR |
| MANY SECTIONS OF PIPES. ALSO SEE TABLES 710.1(1) & |
| 710.1(2). |
| |
| 34. SHT P4-1.0 DETAIL #12 CONDENSATE DRAIN, DETAIL NOT |
| APPROVED AS SHOWN. CLARIFY OPEN NIPPLE. CLARIFY GAP |
| BETWEEN PIPE AND FLOOR. WHY USE A TEE AT THE BOTTOM OF |
| THE TRAP? SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT DETAIL NOT EXPLAINED OR REVISED |
| AS NOTED. COMMENT NOT ADDRESSED. |
| |
| 35. SHT P4-1.0 DETAIL #13 WATER HEATER DETAIL. PLEASE |
| SHOW COMPLIANCE WITH SECTION 607.3.2, THERMAL EXPANSION |
| CONTROL. - A SHUT OFF VALVE IS REQUIRED ON EACH SIDE OF |
| THE CIRCULATING PUMP. - SUBMIT PUMP MANUF. |
| SPECIFICATIONS SHEETS. PUMP SHALL BE LISTED. SECTION |
| 303.4. |
| ****RESPONSE NOTED, BUT THERMAL EXPANSION CONTROL HAS |
| NOT BEEN ADDRESSED. CIRCULATION PUMP SPECIFICATIONS |
| SHALL BE SUBMITTED WITH SUBMITTAL PACKAGE. |
| |
| 36. SUBMIT A SANITARY HORIZONTAL RISER ISOMETRIC AND |
| VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, TRAPS, |
| VENTS, CLEANOUTS, OFFSETS, RISER NUMBERS AND DFU'S AS |
| THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3. |
| ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN, |
| ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND DFU'S ARE NOT |
| SHOWN AS THEY ACCUMULATE IN THE SYSTEM. ALSO INDICATE |
| ON THE FIRST FLOOR WHERE ALL RISERS BEGIN IN THE |
| SYSTEM. |
| |
| 37. SUBMIT A STORM HORIZONTAL RISER ISOMETRIC DIAGRAM & |
| VERTICAL RISER DIAGRAMS. SHOW ALL PIPE SIZES, OFFSETS, |
| & CLEANOUTS AND INDICATE THE RISER NUMBERS. SHOW THE |
| SQUARE FOOTAGE AS IT ACCUMULATES IN THE SYSTEM. SECTION |
| 106.3.5.1.3. |
| ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN, |
| ALL REQUIRED CLEANOUTS ARE NOT SHOWN, AND SQUARE |
| FOOTAGE AS IT ACCUMULATES IN THE SYSTEM IS NOT |
| INDICATED. |
| |
| 38. SUBMIT A WATER RISER ISOMETRIC DIAGRAM. SHOW ALL |
| PIPE SIZES, VALVES, WATER HAMMER ARRESTORS, BACKFLOW |
| PROTECTION ETC. SECTION 106.3.5.1.3. |
| ****RESPONSE NOTED, BUT NOT ALL PIPE SIZES ARE SHOWN, |
| NOT ALL REQUIRED VALVES ARE SHOWN, AND ALL WATER HAMMER |
| ARRESTORS REQUIRED BY SECTION 604.9, (ICE MAKERS, |
| DISHWASHERS, & WASH MACHINES IF FIXTURES ARE |
| PROVIDED). |
| |
| 39. SUBMIT A CONDENSATE RISER ISOMETRIC DIAGRAM. SHOW |
| ALL PIPE SIZES, VENTS, TERMINATION POINTS ETC. SECTION |
| 106.3.5.1.3. |
| ****RESPONSE NOTED, BUT NO CONDENSATE RISER DIAGRAM |
| SUBMITTED AS REQUESTED. |
| |
| 40. ALL PME & FIRE PROTECTION SHEETS. PLANS SHALL BE |
| SIGNED, SEALED, AND DATED. SECTION 106.1. ALL TITLE |
| BLOCK INFORMATION REQUIRED BY FAC 61G1-23.002 AND FS |
| 471.025 SHALL BE SUBMITTED ON EACH SHEET. ****RESPONSE |
| NOTED, BUT THE SEAL USED IS NOT APPROVED. NEW SEALS |
| SHALL INDICATE THE WORD "LICENSE" IN THE SEAL. (SEE |
| ATTACHED SHEET FROM THE FLORIDA BOARD OF PROFESSIONAL |
| ENGINEERS). |
| |
| **************NEW COMMENTS************** |
| |
| 1B. SHTS P1-1.0U, P1-1.1U, P1-1.1 & P1-2.1. RWL-4 DOES |
| NOT REFLECT THE SQUARE FOOTAGE SHOWN ON RISER DIAGRAM |
| OR ROOF PLAN. PLEASE CORRELATE RISER, FLOOR PLAN, & |
| ROOF PLAN. SECTION 106.1.1. |
| |
| 2B. SHTS P1-1.OU & P1-1.1U ALL RWL'S THAT CONNECT TO |
| RWL-4 TO BE INDICATED ON THE 1ST FLOOR. THIS WILL AID |
| IN TRACING THE RWL'S THROUGH THE BUILDING AND TO VERIFY |
| PIPE SIZES. SECTION 106.1.1. |
| |
| 3B. SHTS P1-1.1U & P2-1.01 DETAIL #6 THE SINK SHALL NOT |
| DRAIN THRU THE WET VENT FOR THE TOILET ROOM. THE |
| DISCHARGE FOR THE SINK SHALL CONNECT DOWNSTREAM OF THE |
| TOILET ROOM FIXTURES. SECTION 909.1. |
| |
| 4B. SHT P1-1.2U FD-2 IN D1.106 LOADING REQUIRES A VENT. |
| THIS DOES NOT REFLECT THE RISER DIAGRAM PIPING. THE |
| FLOOR IS SLOPING AWAY FROM THE TRENCH DRAIN. PLEASE |
| CLARIFY. SECTIONS 901.2.1, 106.1.1. |
| |
| 5B. SHT P1-1.2U CLEANOUT REQUIRED AT THE BASE OF P/1 & |
| P/10 RISERS, NEAR THE JUNCTION OF THE BUILDING DRAIN |
| AND THE BUILDING SEWER, AND AT ALL CHANGES OF DIRECTION |
| OVER 45 DEGREES. PLEASE INDICATE ON PLANS. SECTIONS. |
| 708.3.3, 708.3.4, 708.3.5. |
| |
| 6B. SHTS P1-1.2U, ASSOCIATED RISER DIAGRAMS, AND |
| ENLARGED FLOOR PLANS. INDICATE HOW THE STACKS P/1 & |
| P/10 CAN DRAIN INTO THE TOILET GROUP FIXTURE BRANCH. |
| SUBMIT A DETAIL SHOWING THE 4" CLEANOUT TEE, THE 4" |
| CROSS FOR THE FIXTURE BRANCH, AND THE 4" DOUBLE |
| Y/EIGHTH BEND FITTINGS STACKED ON TOP OF EACH OTHER. |
| WILL THEY BE AT THE RIGHT HEIGHT FOR THE W/C'S?SEE |
| SECTION 908.3 ALSO. SECTION 106.1.1. (STACKS SHOULD |
| CONNECT TO THE BUILDING DRAIN AND FIXTURE GROUPS SHOULD |
| CONNECT TO THE STACK SO THAT THE STACK DOES NOT RUN |
| THRU THE MIDDLE OF THE FIXTURE GROUP). |
| |
| 7B. SHTS P1-1.3U, P1-2.0, P1-2.3, P1-3.3, & P1-4.3 |
| RWL-6 DOES NOT REFLECT THE SQUARE FOOTAGE SHOWN ON THE |
| RISER DIAGRAM, NOR ON THE ROOF PLAN. PLEASE CORRELATE |
| INFORMATION. SECTION 106.1.1 & TABLE 1106.3. |
| |
| 8B. SHT P1-1.3 THE WATER SUPPLY TO THE ICE MAKER SHALL |
| CONNECT UPSTREAM OF THE MAKE-UP WATER FOR THE COOLING |
| TOWERS. - SHOW THE LOCATIONS FOR RWL-6 & RWL-7. SECTION |
| 106.1.1 & 608.1. |
| |
| 9B. SHT P1-2.1 RISER P/8 NOT INDICATED ON THE 1ST |
| FLOOR. PLEASE SHOW WHERE RISERS START ON THE FIRST |
| FLOOR. SECTION 106.1.1. |
| |
| 10B. SHT P1-3.2 RISER P/4 SHOWN AT COL. LINE H/2 WAS |
| RISER P/2 ON THE FLOOR BELOW. PLEASE CLARIFY. SECTION |
| 106.1.1. |
| |
| 11B. SHT P1-4.1 C/O FOR S-1 SINK PIPING CONNECTING TO |
| RISER P/7 IS NOT APPROVED AS INDICATED. SECTION 706.3. |
| - RISER P/9 IS NOT INDICATED ON PREVIOUS LEVELS. PLEASE |
| CLARIFY. - RISER P/5 SHOWN ON PREVIOUS LEVEL IS NOT |
| INDICATED. PLEASE CLARIFY. |
| |
| 12B. SHT P1-4.1 SHOW RISER P/3 VTR. - NOTE STATES "SEE |
| 01 ON DRAWING P2-3.0". INFORMATION NOT SHOWN ON DETAIL |
| 01. PLEASE CLARIFY. - SHOW THE VENTING TO REFLECT THE |
| FLOOR PLAN FOR KINK S-1 CONNECTED TO RISER P/8. - 4" |
| SANITARY - 4" VTR AT COL. LINE E/8 IS SHOWN AS AN |
| OFFSET ON THE RISER DIAGRAM. PLEASE CORRELATE FLOOR |
| PLAN AND SANT. RISER DIAGRAM. SECTION 106.1.1. |
| |
| 13B. SHT P1-4.2 SANT. RISER P/2 VTR NOT SHOWN. SECTION |
| 106.1.1. |
| |
| 14B. SHOW ALL PIPE SIZES PER TABLE 1106.3. |
| |
| 15B. SHT P1-6.0 SHOW THE LOCATIONS FOR ALL VTR'S. - |
| INDICATE THE RWL EACH ROOF DRAIN IS CONNECTED TO. |
| SECTION 106.1.1. |
| |
| 16B. SHT P2-1.0U DETAIL 1, FLOOR DRAINS IN C1.104 ARE |
| NOT VENTED. SECTION 901.2.1. - THE PIPING AT THE LAVS |
| IN ROOM C1.103 DOES NOT REFLECT THE RISER DIAGRAM. |
| PLEASE CORRELATE. SECTION 106.1.1. |
| |
| 17B. SHT P2-1.0U DETAIL 2 DOES NOT REFLECT THE PIPING |
| LAYOUT SHOWN ON P1-1.2U. - SUBMIT A DETAIL FOR THE |
| SANT. PIPING ARRANGEMENT FOR THE DRINKING FOUNTAINS, |
| SHOW HOW THE PIPING CONNECTS THROUGH THE SIDE OF THE |
| D.F. UNITS. - SUBMIT A DETAIL FOR THE FITTING |
| ARRANGEMENT WHERE THE TOILET ROOM FIXTURES CONNECT TO |
| THE BLDG. DRAIN. SECTION 106.1.1. |
| |
| 18B. SHT P2-1.0U DETAILS 3 & 4, SUBMIT A DETAIL FOR THE |
| PIPING ARRANGEMENT FOR THE D.F.'S. SECTION 106.1.1. |
| |
| 19B. SHT P2-1.0U DETAIL 6, SINK SHALL CONNECT |
| DOWNSTREAM OF THE WET VENTED FIXTURES IN THE TOILET |
| ROOM. SECTION 909.1. |
| |
| 20B. SHT P2-1.0 DETAIL 1 DOES NOT REFLECT THE FLOOR |
| PLAN OR RISER DIAGRAM. NO WATER PIPING TO WH'S SHOWN. |
| SECTION 106.1.1. |
| |
| 21B. SHT P2-1.0 DETAIL 2 DOES NOT REFLECT THE FLOOR |
| PLAN. SHOWS 2" WATER SUPPLY. SECTION 106.1.1. |
| |
| 22B. SHT P2-1.0 DETAIL 4 DOES NOT REFLECT THE FLOOR |
| PLAN. NO WATER TO WH'S & SHOWS 2" WATER SUPPLY. SECTION |
| 106.1.1. |
| |
| 23B. SHT P2-1.0 DETAIL 6 DOES NOT REFLECT THE FLOOR |
| PLAN FOR SANT. TO LAVS. FLOOR DRAINS NOT VENTED. |
| SECTIONS 106.1.1 & 901.2.1. |
| |
| 24B. SHT P2-2.0 DETAIL 1, INDICATE RISER NUMBERS. |
| SECTION 106.1.1. |
| |
| 25B. SHT P2-2.0 DETAIL 2, SUBMIT A DETAIL FOR SANT. |
| PIPING TO D.F'S. - DOES NOT REFLECT THE RISER DIAGRAM. |
| SECTION 106.1.1. |
| |
| 26B. SHT P2-2.0 DETAIL 3, SUBMIT A DETAIL FOR SANT. |
| PIPING TO D.F.'S - INDICATE RISERS FOR COLD WATER |
| DOWNSTREAM OF LAST W/C'S. HOT WATER LINE NOT SHOWN THRU |
| BATHROOM FIXTURES. SECTION 106.1.1. |
| |
| 27B. SHT P2-2.0 DETAIL 4, NO PIPING TO FLOOR DRAINS |
| SHOWN. SECTION 106.1.1. |
| |
| 28B. SHT P2-2.0 DETAIL 5, SUBMIT A DETAIL FOR SANT. |
| PIPING TO D.F.'S. SECTION 106.1.1. |
| |
| 29B. SHT P2-2.0 DETAIL 6, SUBMIT A DETAIL FOR SANT. |
| PIPING TO D.F.'S. SECTION 106.1.1. - SANT. RISER |
| UPSTREAM OF JANITOR SINK NOT SHOWN. (SEE RISER |
| DIAGRAM). SECTION 106.1.1. |
| |
| 30B. SHT P2-3.0 DETAIL 1, INDICATE WHERE SANT. BRANCH |
| LINE CONNECTS TO THE SANT. RISER. - FLOOR DRAIN SHOWS |
| NO PIPING. SECTION 106.1.1. |
| |
| 31B. SHT P2-3.0 DETAIL 2, NO PIPING SHOWN TO FLOOR |
| DRAINS. - SUBMIT A DETAIL FOR D.F. SANT. PIPING. |
| SECTION 106.1.1. |
| |
| 32B. SHT P2-3.0 DETAIL 3, NO PIPING SHOWN TO FLOOR |
| DRAINS. - SUBMIT A DETAIL FOR D.F. SANT. PIPING. |
| SECTION 106.1.1. |
| |
| 33B. SHT P2-3.0 DETAIL 4, NO PIPING SHOWN TO FLOOR |
| DRAINS. - SUBMIT A DETAIL FOR D.F. SANT. PIPING. |
| SECTION 106.1.1. |
| |
| 34B. SHT P3.1.0 SANT RISER DIAGRAM, TRAPS ARE REQUIRED |
| ON ALL DRINKING FOUNTAINS. SECTION 1002.1. - 1ST FLOOR |
| LAVS PIPING DOES NOT REFLECT THE FLOOR PLAN. - FLOOR |
| DRAINS DOWNSTREAM OF RISER P/1 ARE NOT VENTED. SECTION |
| 901.2.1. - A C/O IS REQUIRED AT THE BASE OF STACK P/1 |
| SECTION 708.3.4 - SHOW THE CONNECTION DETAIL AT THE |
| BASE OF STACK P/1 WITH A 4" CLEANOUT, A 4" CROSS, AND |
| 4" WYE FITTINGS INDICATING THE HEIGHT OF THE W/C |
| STUBOUT. - W/C-1 AT THE BASE OF STACK IS NOT VENTED. |
| SECTION 901.2.1. -W/C ON 2ND FLOOR IS NOT VENTED. |
| SECTION 901.2.1. - LAV ON 3RD FLOOR NOT VENTED. SECTION |
| 901.2.1. - INDICATE HOW/WHERE PIPING FOR LAVS & FLOOR |
| DRAINS CONNECT TO THE RISER/BRANCH ON THE 2ND, 3RD, & |
| 4TH FLOORS. THE FITTINGS INDICATE THAT THE PIPING IS |
| SLOPED TO THE LAVS. PLEASE CLARIFY. - MEN C4.104 DOES |
| NOT REFLECT ROOM NUMBER ON THE FLOOR PLAN. - PIPING FOR |
| FLOOR DRAINS & LAVS 4TH FLOOR DOES NOT REFLECT THE |
| FLOOR PLAN. SECTION 106.1.1. |
| |
| 35B. ALL RISER DIAGRAMS, ALL FLOOR PLANS FOR ALL |
| SYSTEMS. INDICATE THE PIPE SIZE. SECTION 106.1.1. |
| |
| 36B. SHT P3-2.0 JANITOR ROOM PIPING DOES NOT REFLECT |
| THE FLOOR PLAN. - TRAPS REQUIRED ON ALL DRINKING |
| FOUNTAINS. SECTION 1002.1. - CLEANOUTS REQUIRED AT THE |
| BASE OF ALL STACKS. 708.3.4. - PIPING TO FLOOR DRAIN |
| SHOWN ABOVE THE FLOOR IN ROOM D1.101. PLEASE CLARIFY. - |
| PIPING AT THE BASE OF RISER P/2 DOES NOT REFLECT THE |
| FLOOR PLAN. - PIPING TO FD-2 AT THE LOADING D1.106 DOES |
| NOT REFLECT THE FLOOR PLAN. - PIPING FOR A1.108/A1.109 |
| DOES NOT REFLECT THE FLOOR PLAN. - ROOM D2.103 IS |
| INDICATED AS D2.104 ON THE FLOOR PLAN. CORRELATE |
| INFORMATION. - ALL VENTING AT RISER P/10 STOPS AT LEVEL |
| 2. SECTION 903.3 VTR REQUIRED. - TOILET ROOM A2.708 IS |
| INDICATED AS A2.706 ON THE FLOOR PLAN. CORRELATE |
| INFORMATION. - BATHROOM RISER DOES NOT REFLECT THE |
| FLOOR PLAN. (NO FD). - PIPING TO ROOM A4.414 DOES NOT |
| REFLECT THE FLOOR PLAN. - CLEANOUT PIPING DOWNSTREAM OF |
| C4.101 IS NOT APPROVED AS PIPED. SECTION 706.3. - |
| PIPING ON RISER DOES NOT REFLECT THE FLOOR PLAN |
| UPSTREAM OF C3.105. - JANITOR SINK C3.105 IS NOT |
| VENTED. SECTION 901.2.1. - FLOOR DRAIN CONNECTION AT |
| BRANCH LINE 4TH FLOOR DOES NOT REFLECT THE FLOOR PLAN. |
| - PIPING AT A2.107 DOES NOT REFLECT THE FLOOR PLAN. (NO |
| F.D. PIPING). - PIPING AT ROOM A3.111 DOES NOT REFLECT |
| THE FLOOR PLAN AT THE LAVS. - ROOM A3.111 SUBMIT A |
| DETAIL FOR FITTING TO W/C & LAVS. - ROOM D2.105 SHOWN |
| AS D2.106/D2.107 ON FLOOR PLANS. CORRELATE INFORMATION. |
| - ROOM C3.410/C3.412 FLOOR DRAIN FITTING ARE SHOWN TO |
| BE INSTALLED AGAINST THE FLOW. SECTION 706.3. - SECTION |
| 106.1.1. |
| |
| 37B. SHT P3-3.0 PIPING TO A3.304 & DOWNSTREAM DOES NOT |
| REFLECT THE FLOOR PLAN. - VENT PIPING FROM S-1 SINK |
| DOES NOT REFLECT THE FLOOR PLAN. OFFSET NOT SHOWN. - |
| TRAPS REQUIRED ON ALL DRINKING FOUNTAINS. SECTION |
| 1002.1. - S-1 SINK SHALL NOT DRAIN THRU THE WET VENT OF |
| THE TOILET ROOM A1.303. SINK SHALL DISCHARGE DOWNSTREAM |
| OF THE W/C & LAV. SECTION 909.1. - INDICATE P/8 WITH |
| P/6 AT THE BASE OF THE STACK WHERE IT BEGINS. - PIPING |
| TO ROOMS A1.105/A1.106 DOES NOT REFLECT THE FLOOR PLAN. |
| FLOOR DRAIN PIPING IS SHOWN AS ABOVE THE FLOOR. - P/5 & |
| P/9 BEGIN AT THE BASE OF THE STACK. PLEASE INDICATE ON |
| RISER DIAGRAM. - PIPING FOR A3.102/A3.103 DOES NOT |
| REFLECT THE FLOOR PLAN. - CLEANOUT REQUIRED AT THE BASE |
| OF P/9 STACK. - PIPING TO FLOOR DRAINS IN ROOMS |
| A3.102/A3.103 ARE ABOVE THE FLOOR. -W/C AT THE BASE |
| OF STACK NOT VENTED. SECTION 901.2.1. - INDICATE WHERE |
| LINES TO FLOOR DRAINS IN ROOMS A4.103/A4.104 & |
| A5.103/A5.104 ARE CONNECTING TO THE BRANCH/STACK. - |
| PIPING FOR A4.103/A4.104 DOES NOT REFLECT THE FLOOR |
| PLAN. - W/C AT RISER STACK A4.103 IS NOT VENTED. |
| SECTION 901.2.1. - PIPING FOR A4.105 DOES NOT REFLECT |
| THE FLOOR PLAN. SECTION 106.1.1. |
| |
| 38B. SHT P3-4.0 GARAGE WATER RISER DIAGRAM SHOWS WH'S |
| BELOW GRADE. PLEASE CLARIFY. - SHUT OFF VALVE REQUIRED |
| ON WH SHOWN BELOW GRADE. SECTION 606.2(2). - A WATER |
| HAMMER ARRESTOR IS REQUIRED AT THE ICE MACHINE. SECTION |
| 604.9. - SHUT OFF VALVES ARE REQUIRED FOR THE HOSE |
| BIBBS ON THE ROOF. SECTION 606.2(2). - SANITARY RISER |
| DIAGRAM, FLOOR DRAINS ARE NOT APPROVED FOR INDIRECT |
| WASTE. A FLOOR SINK OR HUB DRAIN IS REQUIRED FOR THE |
| ICE MACHINE. SECTIONS 802.3 & 802.3.2. - SECTION |
| 106.1.1. |
| |
| 39B. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING |
| INFORMATION IS REQUIRED FOR THE GAS PERMIT: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. - RISER DOES NOT REFLECT |
| THE FLOOR PLAN. OFFSETS BETWEEN THE |
| METER AND THE RISER ARE NOT SHOWN. - |
| INDICATE WHAT THE RISERS ABOVE THE TEE |
| AT THE TOP OF THE RISER AND AT THE |
| GENERATOR ARE FOR. FUTURE BTU LOAD AND |
| DISTANCE MAY REQUIRE CHANGES IN THE |
| GAS SYSTEM WHEN ADDED. |
| |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE IF BEING USED. |
| |
| C. TYPE OF GAS, (LP OR NATURAL). |
| |
| D. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| |
| F. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| |
| G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| |
| H. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD- |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| |
| I. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| |
| 40B. SHT P3-5.0 NO HOT WATER LINE SHOWN IN 1ST THRU 4TH |
| FLOOR TOILET ROOMS OFF WATER RISER W/1. - WATER RISER |
| DOES NOT REFLECT THE FLOOR PLAN AT THE LAVS. - FULL |
| OPEN VALVES ARE REQUIRED ON ALL WATER DOWN-FEED LINES. |
| SECTION 606.1(4). - RISER DOES NOT REFLECT THE FLOOR |
| PLAN AT ROOMS C2.104/C2.103. (2 LAVS SHOWN EACH TOILET |
| ROOM). - PIPE SIZE SUPPLYING ROOMS D1.101/D1.102, |
| JANITOR ROOM D1.110, TOILET ROOMS A1.108/A1.109. - |
| INDICATE THAT RISERS W/4, W/5, & W/8 RISERS START WITH |
| RISER W/2 ON THE 1ST FLOOR. SECTION 106.1.1. |
| |
| 41B. SHT P3-6.0 RISERS 4, 5 & 8 ARE NOT INDICATED ON |
| THE 1ST FLOOR. - RISER DOES NOT REFLECT THE FLOOR PLAN |
| ROOMS C3.107/C3.108 AT JAN. SINK, ROOMS C3.410/C3.412, |
| AE.111, A4.103/A4.104, A4.105 AND THE TOP OF RISER W/4 |
| TO ROOM A5.105, PIPE SIZE AT ROOM A2.209 & SUPPLY TO |
| TOILET ROOM ADJACENT, PIPE SIZE SUPPLYING RISER W/8 & |
| RISER, SUPPLY LINE TO ROOMS D2.102/D2.103. - W/2 NOT |
| FOUND ON 4TH FLOOR AS INDICATED ON RISER. SECTION |
| 106.1.1. |
| |
| 42B. SHT P3-7.0 SIZE ALL PIPE PER SECTION 1106.3, AND |
| SHOW ALL PIPE SIZES ON THE RISER. - RISER DOES NOT |
| REFLECT THE FLOOR PLAN TOP FLOORS RWL/6 & RWL/7. - |
| RISERS INDICATE A 5TH FLOOR, BUT FLOOR PLAN DOES NOT |
| SHOW A 5TH FLOOR. - RISER SHOWS TRENCH DRAINS ON TWO |
| FLOORS, BUT ONLY SHOW TRENCH DRAINS ON 1 FLOOR, (ROOF |
| LEVEL), ON THE FLOOR PLAN. -RWL'S 9 THRU 14 SHOW OFFSET |
| PIPING FOR ROOF DRAINS IN THE 4TH FLOOR CEILING, BUT |
| INDICATE THE ROOF DRAINS TO BE ON THE 4TH LEVEL. PLEASE |
| CLARIFY. - PIPE SIZING IS INCORRECT AT 8"/11,715SF, |
| 6"/5077SF, 6"/6657SF. TABLE 1106.3. - RWL/9 INDICATES |
| PIPING IN 3RD FLOOR CEILING, BUT ROOF DRAINS ARE TO BE |
| ON THE 3RD LEVEL. PLEASE CLARIFY. - RWL/15 DOES NOT |
| REFLECT THE FLOOR PLAN TO 4" ROOF DRAINS. - PIPING AT |
| THE 1ST FLOOR CEILING CONNECTING TO ROOF DRAINS ON THE |
| 1ST LEVEL. PLEASE CLARIFY. SECTION 106.1.1. |
| |
| 43B. SHTS 1,2,3 OF 3 ARE NOT SIGNED, SEALED, & DATED AS |
| REQUIRED PER FS 472.025(1). ALSO SEE SHT 1 WHICH STATES |
| "NOT VALID UNLESS SEALED WITH SURVEYOR'S EMBOSSED SEAL |
| AND SIGNATURE" |
| |
| 44B. SHTS C1, C5 THRU C22 ENGINEERING CERTIFICATE OF |
| AUTHORIZTION IS REQUIRED IN THE TITLE BLOCK. |
| 61G15-23.002(2) & FS 471.025. - AN EMBOSSED SEAL IS |
| REQUIRED TO IMPRESS REQUIRED INFORMATION ON EACH SHEET. |
| UNABLE TO GLEAN ALL INFORMATION REQUIRED FROM SEAL. |
| PLEASE RESEAL PLANS. |
| |
| 45B. SHTS LP-0 THRU LP-3 & IR-1 THE CERTIFICATE OF |
| AUTHORIZATION IS REQUIRED IN THE TITLE BLOCK. |
| 61G1-16.004(1) & FS 481.319. |
| |
| 46B. SHT LL-1 IS MISSING THE TITLE BLOCK INFORMATION |
| REQUIRED IN 61G1-16.004. |
| |
| 47B. SHT IR-1 THE CONTROLER & RAIN SENSOR LOCATIONS ARE |
| REQUIRED ON PLANS. SECTION 106.1.1. |
| |
| 48B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 2ND |
| FLOOR DRINKING FOUNTAINS SHOWS 4 REQUIRED, BUT ONLY 3 |
| ARE REQUIRED PER TABLE 403.1. FIXTURE COUNT INDICATES |
| ONLY 2 ARE PROVIDED. PLEASE PROVIDE REQUIRED AMOUNT OF |
| DRINKING FOUNTAINS. |
| |
| 49B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 3RD |
| FLOOR DRINKING FOUNTAINS SHOW ONLY 3 ARE REQUIRED. PER |
| TABLE 403.1, 4 DRINKING FOUNTAINS ARE REQUIRED. PLEASE |
| UPDATE FIXTURE COUNT. |
| |
| 50B. SHT LSO.0 PLUMBING FIXTURE COUNT. CITY HALL 4TH |
| FLOOR DRINKING FOUNTAINS INDICATE 4 REQUIRED, BUT ONLY |
| 3 ARE PROVIDED. PLEASE PROVIDE 4 DRINKING FOUNTAINS. |
| TABLE 403.1. |
| |
| 51B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 1ST |
| FLOOR DRINKING FOUNTAINS 2 REQUIRED PER TABLE 403.1, |
| BUT READS 1 REQUIRED. PLEASE CORRECT FIXTURE COUNT |
| REQUIRED. |
| |
| 52B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 3RD |
| FLOOR DRINKING FOUNTAINS 4 REQUIRED PER TABLE 403.1, |
| BUT READS 2 REQUIRED. PLEASE CORRECT FIXTURE COUNT |
| REQUIRED. - SHOWS 2 PROVIDED, BUT 4 ARE REQUIRED. |
| PLEASE CORRECT INFORMATION. |
| |
| 53B. SHT LSO.0 PLUMBING FIXTURE COUNT. LIBRARY 4TH |
| FLOOR LAVS REQUIRED 2, INDICATED AS 1. PLEASE CORRECT |
| THE FIXTURE COUNT. TABLE 403.1. |
| |
| 54B. SHT LSO.0 LIBRARY/MUSEUM INDICATES A RESTURANT IN |
| OCCUPANT LOAD 1ST FLOOR.PLEASE CONTACT LYNN MASSON, |
| ENVIRONMENTAL COMPLIANCE MANAGER CONCERNING THE |
| POSSIBLE REQUIREMENT FOR A GREASE INTERCEPTOR. CONTACT |
| LYNN BY PHONE (561) 822-2271, OR FAX (561) 822-2279, OR |
| E-MAIL [email protected]. |
| |
| 55B. SHT LSO.0 INDICATES ASSEMBLY OCCUPANCY FOR THE |
| CITY HALL AND LIBRARY/MUSEUM. POTTY PARITY IS REQUIRED |
| PER SECTION 403.1.1 AND HAS BEEN INDICATED IN THE 50% |
| REVIEW BY PAUL SCHMITZ. THIS HAS NOT BEEN ADDRESSED. |
| PLEASE SHOW COMPLIANCE WITH THIS REQUIREMENT. |
| |
| 56B. SHT A2-0 3 AREAS SHOW STORM WATER FROM ROOF AREAS |
| ABOVE THAT CONTRIBUTE TO THE MAIN ROOF AREAS BELOW. THE |
| SLOPE OF THE MAIN ROOF AND THE LOCTION OF THE DOWNSPOUT |
| IS SHOWING THE TOTAL AREA DRAINING TO ONE ROOF DRAIN, |
| BUT THE AREA IS DIVIDED EQUALLY BETWEEN TWO ROOF |
| DRAINS. THE SIZING FOR THE ROOF DRAINS WILL HAVE TO BE |
| RECHECKED TO ACCOUNT FOR THE AMOUNT OF AREA DRAINING TO |
| ONE DRAIN, NOT TWO. TABLE 1106.3. (SEE ROOF AREAS AT |
| COL. LINES 1THRU 4/A THRU D, 7 THRU 9.1/A THRU D, AND 4 |
| - 5/E THRU H). |
| |
| 57D. SHTS A2-0, A2-1, A2-2, A2-3 SUBMIT CALCULATIONS |
| FOR PRIMARY AND SECONDARY ROOF DRAINS. INDICATE THE |
| CONTRUBUTION ADD FROM 1/2 AREA OF ALL VERTICAL WALLS, |
| INCLUDING PARAPETS, AND ROOF AREAS FROM ABOVE ADDED TO |
| THE ROOF SECTIONS. THIS IS REQUIRED FOR ALL ROOF |
| LEVELS. SQUARE FOOTAGE IS SHOWN, BUT NO CALCULATIONS |
| WERE SUBMITTED. CONTRIBUTING VERTICAL AREAS FOR WALLS |
| IS UNCLEAR. IS THE AREA SHOWN INDICATED PER WALL, OR |
| TOTAL FOR ALL WALLS SHOWN. PLEASE CLARIFY. SECTIONS |
| 1106.1, 1106.2, 1106.3, 1106.4. |
| |
| 58B. SHT A2-0 UPPER ROOF BY DOME SHOWS A DETAIL |
| INDICATOR 20/A2-D.1. DETAIL 20 NOT FOUND ON SHT A2-D.1. |
| PLEASE CLARIFY. SECTION 106.1.1. |
| |
| 59B. SHT A2-D.1 DETAIL 04 SHOW HEIGHT AND WIDTH AND |
| INDICATE THE MEASUREMENT FROM THE ROOF TO THE FLOW LINE |
| OF THE SCUPPER. SECTIONS 106.1.1 AND 1503.4.3. |
| |
| 60B. SHT A6-1.1 DETAILS 1 THRU 6. SHOW THE TURNING AREA |
| IN THE TOILET ROOMS. NOT IN THE ACCESSIBLE STALLS. |
| SECTION 11-4.22.3. |
| |
| 61B. SHT A6-1.1 DETAIL 2, SHOW THE CLEAR FLOOR SPACE |
| FOR THE URINAL. SECTION 11-4.18.3. |
| |
| 62B. SHT A6-1.1 DETAIL 4, ACCESSIBLE W/C SHALL BE 1'6" |
| OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG. |
| 11-28. LAV TO BE MIN. 15" (C/L OF CLEAR FLOOR SPACE). |
| |
| 63B. SHT A6-1.1 DETAIL 7, ACCESSIBLE W/C SHALL BE 1'6" |
| OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG. |
| 11-28. (SHOWS 2'2"). |
| |
| 64B. SHT A6-2.1 DETAILS 2, 6 & 7 SHOWTHE TURNING AREA |
| IN THE TOILET ROOMS. NOT IN THE ACCESSIBLE STALLS. |
| SECTION 11-4.22.3. |
| |
| 65B. SHT A6-2.1 DETAIL 4, ACCESSIBLE W/C SHALL BE 1'6" |
| OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. FIG. |
| 11-28. |
| |
| 66B. SHT A6-3.1 DETAIL 1, SHOW THE TURNING AREA IN THE |
| LOCKER ROOM AREA. SECTION 11-4.2.3. |
| |
| 67B. SHT A6-3.1 DETAILS 2, 3, 4 & 6, SHOW THE TURNING |
| AREA IN THE TOILET ROOMS, NOT IN THE ACCESSIBLE STALLS. |
| SECTION 11-4.22.3. |
| |
| 68B. SHT A6-4.1 DETAILS 1 & 2, SHOW THE TURINING AREA |
| IN THE TOILET ROOMS, NOT IN THE ACCESSIBLE STALLS. |
| SECTION 11-4.22.3. |
| |
| 69B. SHT A6-5.1 DETAIL 1, SHOW THE TURNING AREA IN THE |
| TOILET ROOM, AND SHOW THE CLEAR FLOOR SPACE FOR THE |
| URINAL. SECTIONS 11-4.22.3 AND 11-4.18.3. |
| |
| 70B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS |
| C1.105, C1.106, A2.705, A2.706, A2.210, A2.211, A3.111, |
| A3.114, C3.410, AND C3.412 ALL INDICATE THE WALLS TO BE |
| PAINTED. PLEASE INDICATE HOW THIS COMPLIES WITH THE |
| REQUIREMENT FOR "SMOOTH, HARD, NONABSORBENT WALLS AS |
| REQUIRED IN SECTION 1210.2. |
| |
| 71B. SHTS A9-0.1 & A9-0.2 FINISH SCHEDULES: ROOMS D2.10 |
| & D2.104 SHOW NO WALL FINISH AND THE FLOORING/BASE |
| INDICATE RUBBERIZED FLOORING. INDICATE HOW THIS |
| COMPLIES WITH "SMOOTH, HARD, NONABSORBENT FLOORS AS |
| REQUIRED IN SECTION 1210.1. |
| |
| 72B. SHT A9-4.1 INDICATE THE ROOM NUMBERS THAT THE |
| DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE |
| FOLLOWING: |
| A. 11-4.18.4 FLUSH CONTROLS |
| B. 11-4.19.2 CLEARANCES |
| C. 11-4.19.4 EXPOSED PIPES & CLEARANCES |
| |
| 73B. SHT A9-4.2 INDICATE THE ROOM NUMBERS THAT THE |
| DETAIL IS REFERENCING. SHOW COMPLIANCE WITH THE |
| FOLLOWING: |
| DETAIL #1 |
| A. 11-4.18.4 FLUSH CONTROLS |
| B. 11-4.19.2 CLEARANCES |
| C. 11-4.19.4 EXPOSED PIPES & CLEARANCES |
| |
| DETAIL #2 |
| A. 11-4.18.4 FLUSH CONTROLS |
| B. 11-4.19.2 CLEARANCES |
| C. 11-4.19.4 EXPOSED PIPES & CLEARANCES |
| |
| 74B. SHT A9-4.4 INDICATE THE ROOM NUMBERS THAT THE |
| DETAILS ARE REFERENCING.SHOW COMPLIANCE WITH THE |
| FOLLOWING: |
| DETAILS #1 - #2 - #3 |
| A. 11-4.19.2 CLEARANCES |
| B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| |
| 75B. SHT A9-4.4 SHOW THE FOLLOWING FOR COMPLIANCE:A. |
| 11-4.19.2 CLEARANCES |
| B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| C. 11-4.19.5 FAUCETS |
| D. 11-4.21.5 CONTROLS |
| E. 11-4.21.7 CURBS |
| |
| 76B. SHTS A1.307, A1.709, A2.209, A2.315, A2.407, |
| A3.109, C3.409, C3.310, A5.504 - SHOW COMPLIANCE WITH |
| THE FOLLOWING |
| A. 11-4.24.4 SINK DEPTH |
| B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH |
| REQUIRED) |
| C. 11-4.24.6 EXPOSED PIPES & SURFACES |
| D. 11-4.24.7 FAUCETS |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. SUBMITTING THE RED |
| LINED SET OF PLUMBING SHEETS WHEN RESUBMITTING FOR |
| REVIEW WILL HELP EXPEDITE THE PERMIT ALSO. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6721 |
| E-MAIL [email protected] |
| |
| |
| |
| |
| |
| |
| |