2006-10-27 11:07:291. STAIR SUMMARY CHART NEEDED ON PAGE LS0.0. THIS CHART
 SHALL IDENTIFY ALL STAIRS, WIDTHS, AND EXIT
 CAPACITIES.
 2. STAIRWELL IDENTIFICATION SIGNS SHALL BE PROVIDED ON
 THE SIGNAGE LEGEND DISPLAYED ON PAGE LS0.0. THESE
 STAIRWELL IDENTIFICATION SIGNS SHALL IDENTIFY THE
 STAIR, TERMINUS, TOP AND BOTTOM, FLOOR NUMBER, ETC.
 3. STAIR # 5 ON PAGE LS1-1.0 HAS STILL NOT BEEN
 CORRECTED. PLEASE MOVE OR REMOVE WALL SECTION DIRECTLY
 IN FRONT OF EXIT STAIR DOOR TO ALLOW FOR PROPER EXIT
 DISCHARGE.
 4. EXIT SIGNS APPEAR TO BE MISSING FROM SHEET LS1-1.1.
 PLEASE SEE BACK OF HOUSE AREA IN COMMISSION CHAMBERS.
 OTHER AREAS ALSO ABSENT OF SIGNS. CONFLICTS APPEAR TO
 EXIST BETWEEN LS1-1.1 AND E2-1.1.
 5. EXIT SIGN NOTED DIRECTLY INFRONT OF ELECTRICAL ROOM
 DOOR ON PAGE E2-1.2.
 6. EXIT SIGN IN CENTER OF STAIR # 9 ON PAGE E2-1.2.
 7. EXIT SIGN WITH DIRECTIONAL ARROWS DIRECTS PERSONS TO
 GRAND STAIR ON PAGE E2-2.1.
 8. EXIT SIGN MISSING IN FRONT OF STAIR DOOR # 7 ON PAGE
 E2-2.2.
 9. EXIT SIGN CONTAINED WITHIN STAIR # 9 NOT INFRONT OF
 STAIR DOOR ON PAGE E2-2.2.
 10. EXIT SIGN CONTAINED WITHIN STAIR # 9 NOT INFRONT OF
 STAIR DOOR ON PAGE E2-3.2.
 11. EXIT SIGN INSTALLED NEAR WALL OF STAIR # 9 NOT NEAR
 DOUBLE DOORS ON PAGE E2-3.2.
 12. NO EXIT MARKINGS COULD NOT BE LOCATED ON PAGES
 E2-4.0 AND E2-4.1.
 13. EXIT SIGN MARKINGS MISSING FROM PAGE E2-4.2.
 14. SAME CONDITION EXISTS ON PAGE E2-5.1.
 15. PLEASE EXPLAIN FACP CALL OUT IN VOICE DATA ROOM ON
 PAGE E3-1.0.
 16. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF THE FIRE ALARM SYSTEM. FIRE ALARM
 SYSTEM SHALL BE UL LISTED FOR CENTRAL STATION SERVICE.
 PLEASE EXPLAIN "PROVIDE ZONED EMERGENCY VOICE
 EVACUATION"ON PAGE FA1-1. SYSTEM TO COMPLY WITH NFPA
 72, THE NATIONAL FIRE ALARM CODE, 2002 EDITION.
 17. EXIT SIGN MISSING NEAR STAIR # 2 ON PAGE E1-6.1.
 18. TRAINING ROOM AT A 4 AND 5 MISSING FIRE ALARM
 NOTIFICATION APPLIANCES ON PAGE FA1-4.
 19. PLEASE EXPLAIN NOTE # 3 FIRE PROTECTION DESIGN
 CRITERIA INFORMATION BOX ON PAGE FP0-1.0.
 20. ON PAGE FP1-1.0 AT LEAST FIVE FIRE DEPARTMENT
 CONNECTIONS ARE SHOWN. AGAIN ALL OF THESE ARE NOT
 NECESSARY.
 21. SOME FIRE SPRINKLER DRAWINGS ARE ABSENT OF FIRE
 SPRINKLER HEADS. IT IS DIFFICULT TO DETERMINE IF 100 %
 COVERAGE IS PROVIDED DUE TO INSUFFICIENT INFORMATION.
 22. ON PAGE FP1-2.1 KEY NOTE # 5 "PROVIDE WATER CURTAIN
 FOR GLASS AREAS LOCATE SPRINKLERS 6'-0 ON CENTER".
 PLEASE ILLUSTRATE WATER CURTAIN ARRANGEMENT.
 23. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FM 200
 FIRE SUPPRESSION SYSTEM PLANNED FOR THE SERVER ROOM ON
 PAGE FP1-4.0.
 24. DOUBLE DETECTOR CHECK VALVE ASSEMBLY DETAIL SHOWN
 ON PAGE FP2-1.0 DOES NOT INDICATE TAMPER SWITCHES,
 CHAIN AND LOCK.
 25. FLOOR CONTROL VALVE ASSEMBLY DETAIL SHOWN ON PAGE
 FP3-1.0 SHALL BE EQUIPPED WITH 2 1/2 TO 1 1/2
 REDUCERS.
 26. PLEASE DISPLAY HEIGHT DIMENSIONS FROM ROOF TO
 EXHAUST FAN ON PAGE M502.0.
 27. COULD NOT LOCATE WHAT THE FIREFIGHTERS SMOKE
 CONTROL PANEL FOR THE ATRIUM SYSTEM LOOKS LIKE WITH THE
 MECHANICAL DRAWINGS.
 28. ALSO COULD NOT LOCATE A SEQUENCE OF OPERATIONS
 MATRIX FOR THE ATRIUM MECHANICAL SYSTEM IN THE
 MECHANICAL DRAWINGS.
 29. NO EXIT SIGN NOTED AT THE BACK LOADING DOCK DOUBLE
 DOORS ON PAGE LS1-1.2.
 30. ALL MECHANICAL, ELECTRICAL, AND STORAGE ROOM DOORS
 ARE TO BE SMOKE RESISTANT. PLEASE ESNURE THAT THE PLANS
 ARE REVISED TO REFLECT THIS CHANGE.
 31. OCCUPANT LOAD TAG FOR GROUP B BUSINESS ON PAGE
 LS1-2.0 SHOULD READ 25 OCCUPANTS INSTEAD OF 40
 OCCUPANTS.
 32. PROGRAM MEETING ROOM ON PAGE LS1-3.2 THAT CONTAINS
 50 SEATS DOES NOT CONTAIN ANY EXIT SIGNS.
 33. OCCUPANT LOAD TAG FOR GROUP B BUSINESS OCCUPANCY ON
 PAGE LS1-4.0 SHOULD READ 270 PERSONS NOT 278
 OCCUPANTS.
 34. ILLUMINATED EXIT SIGN IN SERVER ROOM LOCATED ON
 PAGE LS1-4.1 IS NOT LOCATED INFRONT OF ANY EXIT DOOR.
 35. EXIT SEPARATION LINE IN TRAINING ROOM ON PAGE
 LS1-4.1 IS DRAWN TO A DOOR ABSENT OF AN EXIT SIGN.
 36. A FIRE EXTINGUISHER CABINET IS LOCATED ON PAGE
 LS1-4.1 NEAR MEN'S ROOM BUT DOES NOT APPEAR TO BE
 AFFIXED TO ANYTHING.
 37. IT APPEAR THAT A FIRE EXTINGUISHER CABINET IS
 MOUNTED ON A DOOR TO THE SERVER ROOM ON PAGE LS1-4.1.
 38. EXIT SIGN ON PAGE LS1.6.1 IS NOT LOCATED NEAR STAIR
 DOOR.
 39. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR ALL HANDRAILS, GUARDRAILS, TEMPERED GLASS WALLS
 CABLE RAILINGS, AND PRE-ENGINEERED RAILINGS.
 40. ON PAGE ID2-4.2 A SOLID WALL EXISTS WHERE A DOOR
 EXISTS FOR THE STAIRWELL.
 41. SEVERAL BUILDING ADDRESSES NOTED ON TWO DIFFFERENT
 ELEVATIONS ON PAGE A4-1.0. THE ADDRESSES SHALL ONLY BE
 LISTED ON THE PROPER ELEVATION.
 42.ALL PROPOSED WORK STATIONS IN OPEN WORK AREAS
 SHALL PROVIDE FOR A MINIMUM OF AT LEAST 44" INCHES.
 43. ALL FIRE DAMPERS WILL BE REQUIRED TO BE DROP TESTED
 AFTER INSTALLATION TO ENSURE PROPER OPERATION.
 44. CHAIRS LOCATED IN ENTRY/WAITING A2.009 MAY
 INTERFERE WITH DOORS ON PAGE ID2-2.0.
 45. PLEASE EXPLAIN EXIT ACCESS FOR MEETING ROOM ON PAGE
 ID2-3.2 ESPECIALLY NEAR THE FOUR COLUMNS.
 46. PLEASE PROVIDE A STAIR SECTION FOR THE PROPOSED
 ALTERNATING TREAD STAIRS SHOWN ON THE DRAWINGS.
 47. PLEASE DISPLAY THE REQUIRED 1/2 MAXIMUM AT ALL EXIT
 DOOR LOCATIONS.
 48. THE SERVER ROOM SHALL COMPLY WITH NFPA 75, THE
 STANDARD FOR THE PROTECTION OF INFORMATION TECHNOLOGY
 EQUIPMENT.
 49. SOME OF THE ITEMS IDENTIFIED AT THE PREVIOUS
 REVIEWS STILL SEEM TO EXIST AT THIS PERMIT REVIEW.
 PLEASE REVIEW ALL PREVIOUS COMMENTS PROVIDED BY CITY
 STAFF AND ESNURE THAT PREVIOUS ITEMS IDENTIFIED HAVE
 BEEN CORRECTED AND PROPERLY COORDINATED ON THE
 APPROPRIATE SHEETS.
  