Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop E
Sequence Number 1
Notes
Date Text
2006-11-25 20:22:32**** CITY CENTER *******
  
  
 REVIEW OF 100% ELECTRICAL PLANS SUBMITTED ON NOVEMBER
 7TH, 2006.
  
 PLEASE SEE THE FOLLOWING COMMENTS ARE BASED ON THESE
 PLANS AS NOTED ABOVE AND NOT THE 100% PLANS SUBMITTED
 ON OCTOBER 17TH, 2006.
  
 1) NOTE: PLEASE KNOW WHEN SUBMITTING FOR FINAL
 PERMITTING AND STAMPING, A THIRD SET OF SIGNED, DATED
 AND SEALED PLANS WILL BE REQUIRED.
 PLEASE SEE FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE
 CITY OF WEST PALM BEACH, 106.1.2106.1.3, 109.3.6 FOR
 THRESHOLD BUILDINGS. THIS IS WILL BE REQUIRED FOR ALL
 DOCUMENTATION AND PLANS AND FOR ALL TRADES WHETHER OR
 NOT COMMENT IS MADE BY OTHER TRADES.
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13. PLEASE SEE
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE BE SURE ALL DEVICE ON PLANS CORRELATE WITH THE
 DEVICE SYMBOL LEGEND.
 PLEASE BE SURE MAX TIME OF OVER -RIDES ARE SHOWN. IF
 TIMER TYPE, (4HRS MAX), IF OCCUPANCY SENSOR TYPE (30
 MINS MAX).
 PLEASE SEE ADDITIONAL COMMENTS FOR CONTROLS AND SYSTEM
 BEING PROPOSED.
  
 3) NOTE: PLEASE PLACE A NOTE ON PLANS FOR ALL "TASK"
 LIGHTING WHICH MAY NOT BE SHOWN ON PLANS AT THIS TIME.
 13-415.1.ABC.1.3
  
 4) NOTE: PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS
 FOR THE ENTIRE BUILDING FOR REVIEW OF ALL TRADES.
 PLEASE KNOW AS NONE WERE SUBMITTED AT THIS TIME THERE
 ARE MANY ITEMS WHICH CAN NOT BE VERIFIED WITH THE
 PLANS, EQUIPMENT AND LIGHTING.
 PLEASE SEE 13-415.1.AB.1.
  
 5) NOTE: PLEASE SEE 13-415.2, 13-415.2ABC.1 FOR MINIMUM
 AND MAXIMUM PERFORMANCE CALCULATIONS. PLEASE SEE THE
 CALCULATIONS SUBMITTED SHOWING THE LIGHTING POWER
 DENSITIES (LPD) ARE NOT COMPLETE AND/OR THERE ARE ITEMS
 WHICH DO NOT CORRELATE WITH SAID PLANS.
 PLEASE SEE THERE ARE MANY ROOMS INDICATED ON PLANS
 WHICH COULD NOT BE LOCATED IN CALCULATIONS OR THERE ARE
 ROOMS ON CALCULATIONS WHICH COULD NOT BE LOCATED ON
 PLANS.
 PLEASE CORRELATE AND PLEASE SEE SOME OF THE LPD'S SEEM
 TO BE VERY HIGH FOR SOME OF THE ROOMS AND AREAS AS
 NOTED AND SHOWN.
 PLEASE SEE OFFICE IN PARKING GARAGE FOR INSTANCE.
 PLEASE SEE SOME OTHERS WHICH BASED ON THE TABLES AS
 SET-FORTH IN THE CODE MAY ALLOW 1.7, THE CALCULATIONS
 MAY SHOW 10.5 ETC.
 PLEASE REVIEW ALL AND RE-ADJUST AS REQUIRED AND
 NEEDED.
  
 6) NOTE: PLEASE SEE 13-415.2.ABC.1.3 FOR ALL EXTERIOR
 LIGHTING ALLOWANCES, INCLUDING THAT WHICH IS
 DECORATIVE. PLEASE SEE THERE ARE EXCEPTIONS FOR SOME
 AREAS; HOWEVER THESE AREAS AS LISTED WOULD BE REQUIRED
 BY SECTIONS AS LISTED. PLEASE SEE 13-415.0(3)
 (EXCEPTS).
  
 7) NOTE: PLEASE SEE PLANS SHALL INDICATE THE ACTUAL
 PANEL BEING USED FOR LIGHTING CONTROLS. PLEASE SEE
 THERE ARE SEVERAL PANELS INDICATE IN THE MANUFACTURE
 SPECS/CUT SHEETS SUBMITTED AND THE ACTUAL UNIT NEEDS TO
 BE HIGH-LIGHTED IN SPECS. PLANS SHALL ALSO BE REQUIRED
 TO PROVIDE THE TECHNICAL INFORMATION AT EACH LIGHTING
 CONTROL PANEL. (LCP)
 ** PLEASE KNOW AS REFERENCE TO LIGHTING CONTROL PANELS
 IN NOTES HERE ON WILL BE DESIGNATED AS "LCP'S". PLEASE
 SEE RISER INDICATES LCP'S AS 225A RATED, WHICH IS OK,
 HOWEVER PLEASE BE SURE THE INFORMATION AS SHOWN ON
 CUT/SPEC SHEETS IS BROUGHT OVER TO THE PLANS AND LISTED
 ON EACH LCP.
  
 8) NOTE: PLEASE KNOW THERE IS CONCERN OVER THE TYPE OF
 SYSTEM BEING PROPOSED AND CONTROLS OF SAID SYSTEM.
 PLANS CALL FOR A "SWEEP" EACH HOUR FOR THE SYSTEM OUT
 OF NORMAL BUSINESS HOURS AND THIS WILL TURN OFF ANY AND
 ALL DEVICES. THE DEVICES WILL THEN HAVE THE ABILITY TO
 OVER RIDE THE SYSTEM IN ANY PARTICULAR AREA WHICH THE
 CIRCUIT/SWITCH IS DESIGNATED TO. PLEASE KNOW THIS
 BUILDING IN SEVERAL SECTIONS WILL BE OCCUPIED OUT OF
 THE NORMAL BUSINESS HOURS WHICH ARE SET UP AND WILL
 CAUSE DARKNESS EACH HOUR EVEN WHEN OCCUPIED. PLEASE SEE
 SPECS SHEETS AS SUBMITTED SPEAK OF THE INCLUSION OF AN
 OCCUPANT SENSOR TYPE DEVICE TO ALLEVIATE THIS.
 (UNINTENDED BLACK-OUTS). PLEASE SEE AREAS LIKE THE
 LIBRARY, COMMISSIONS CHAMBERS, OFFICE DESIGNATED FOR
 POLICE, AND OTHER AREAS.
 PLEASE SEE THE CODE ON THE OTHER HAND FOR ALL AREAS
 WHICH DURING NORMAL BUSINESS HOURS WHICH WILL REQUIRE
 ROOMS TO BE OFF. PLEASE SEE 13-415.1.ABC.1.2, FOR ALL
 ROOMS CONTAINING FLOOR TO CEILING HEIGHT PARTITIONS
 WHICH WILL REQUIRED SEPARATE CONTROL. PLEASE SEE AS
 SHOWN ON PLANS, THESE ROOMS WILL COME "ON" AT THE SET
 BUSINESS HOUR TIMES AND WILL REMAIN ON UNTIL AFTER THE
 "ONE HOUR SWEEP" AFTER THE NORMAL OPERATIONAL TIMES
 HAVE PASSED.
 PLEASE SEE CLOSETS, OFFICES, STORAGE AREAS ETC. THERE
 ARE FAR TOO NUMEROUS ROOMS TO LIST.
 PLEASE SEE THERE ARE MANY ROOMS ON PLANS WHICH DO
 INDICATE "OC" TYPE DEVICES; HOWEVER THERE IS NOT DETAIL
 ON THE LIGHTING CONTROL RISER HOW THESE WILL BE
 CONNECTED OR TIED IN.
 PLEASE SEE BATHROOMS ETC.
 PLEASE KNOW THIS TYPE OF DEVICE WILL WORK IN MANY AREAS
 IN THIS BUILDING; HOWEVER THERE ARE AREAS WHICH WILL
 NOT MEET CODE OR THE INTENT IN SEPARATE SPACES. PLEASE
 KNOW AT THIS TIME, AS SHOWN THERE ARE SEVERAL ITEMS
 WHICH WILL BE REQUIRED TO BE ADJUSTED. PLEASE ALSO
 OBTAIN A LETTER FROM THE "SENTRY SWITCH" MANUFACTURE
 WHICH PERMITS THIS TYPE OF DEVICE TO BE USED WITH THE
 LUTRON GRAFIK PANEL.
 110.3, 90.7 NEC.
  
 9) NOTE: PLEASE SEE THERE ARE SEVERAL ROOM NUMERICAL
 DESIGNATIONS ON CALCULATIONS WHICH COULD NOT BE LOCATED
 ON PLANS. PLEASE SEE GARAGE PLANS.
 PLEASE SEE SOME WHERE THE ROOM DESIGNATION IS THERE
 HOWEVER IT SEEMS TO BE VERY LIGHT IN COLOR AND CAN NOT
 BE EASILY READ. PLEASE SEE OTHER AREAS WHICH THE
 FIXTURE DESIGNATION COVERS THE ROOM IDENTIFICATION OR
 VICE VERSA, THE FIXTURE TYPE COULD NOT BE SEEN DUE TO
 THE OVER LAY OF THE NUMERICAL DESIGNATION.
 PLEASE COORDINATE. A1-116-2-1.610 ETC
 FBC ADMIN SECTION 106.1.2, 106.1.3
  
 10) NOTE: PLEASE BE SURE ALL INFORMATION IS PROVIDED ON
 ALL FIXTURES AS SHOWN ON PLANS ON THE FIXTURE LEGEND.
 PLEASE KNOW THAT THE WATTAGE, TYPE ETC SHALL BE
 SPECIFIED AT THIS TIME. THESE CAN ALWAYS BE REVISED AT
 A LATER DATE.
 FBC 106.1.2,NEC 110.3, ETC
  
 11) NOTE: PLEASE SEE THAT BATTERY BACK UP FIXTURES OF
 SOME TYPE WILL BE REQUIRED FOR THE FOLLOWING LOCATIONS.
 SOME ARE SHOWN ALREADY, HOWEVER NOT ALL. THE MAIN
 ELECTRICAL ROOM, THE FIRE COMMAND CENTER, BOTH FIRE
 PUMP ROOMS, ELEVATOR EQUIPMENT ROOM, AND AT THE
 LOCATION OF THE ROOF TOP GENERATOR WILL ALL REQUIRE
 THIS. PLEASE SEE THAT ALL STAIR TOWERS AND EGRESS PATHS
 SHALL ALSO INCLUDE SOME SORT OF BATTERY BACK UP
 FIXTURE. THERE ARE MANY LOCATIONS WHICH INCLUDE THIS;
 HOWEVER AS SOME OF THE FIXTURE INFORMATION IS NOT CLEAR
 AT THIS TIME THIS CAN NOT BE VERIFIED. THIS BUILDING IS
 EXPECTED TO BE OCCUPIED IN THE TIME OF POWER OUTAGES
 AND IN THE EVENT OF THE TRIPPING OF A SINGLE MEANS OF
 OVER CURRENT PROTECTION (EMSB1) OR GEN MAIN, THIS WILL
 PLACE MANY AREAS IN COMPLETE DARKNESS WHICH IS NOT
 PERMITTED. NEC 700.12E, 700.16, LS 101 7.9.
  
 12) NOTE: PLEASE SEE LIGHTING CONTROL RISER WHICH
 INDICATES ALL LCP'S BEING FED FROM THE SAME PANEL?
 1HA/LCP1A PLEASE ADJUST.
  
 13) NOTE: PLEASE CORRELATE ALL LCP'S WITH THE HOUSE
 PANELS AND THE CIRCUITS FROM THE HOUSE PANELS WHICH
 FEED THESE LCP'S AND CIRCUITS. PLEASE SEE NUMEROUS
 CIRCUITS WHICH CONTAIN THE DESIGNATION OF "LC" NEXT TO
 THE CIRCUIT HOWEVER MANY WHICH DO GO THROUGH THE PANEL
 DO NOT? PLEASE COORDINATE.
 FBC106.1.2 ADMIN SECT.
  
 14) NOTE: PLEASE SEE FIXTURE "E", PLEASE SEE IT APPEARS
 TO BE BATTERY BACK UP, BUT NOT ENOUGH INFORMATION IS
 PROVIDED. PLEASE SEE FIXTURES, Z,ETC.
  
 15) NOTE: PLEASE SEE CIRCUITING FOR ATM ROOM/AREA AND
 THE CIRCUITING FOR THE FIRE COMMAND CENTER. PLEASE SEE
 PANEL SCHEDULE FOR 1LB2, 29 AND 31, ETC. PLEASE PROVIDE
 THE CORRECTED IDENTIFICATION FOR THE CIRCUITS AND
 DESIGNATIONS.
 FBC 106.1.2 ADMIN SECT.
  
 16) NOTE: PLEASE PROVIDE ALL MINIMUM WIND LOADING FOR
 SITE LIGHTING LIGHT POLES, AND THAT OF THE POLES ON
 GARAGE ROOF STRUCTURE. PLEASE KNOW A DETAIL ON HOW
 THESE WILL BE ATTACHED ON PARKING DECK OF THE GARAGE
 AND POLE DETAIL FOR GROUND MOUNTED/BURIED POLES WILL BE
 REQUIRED. PLEASE KNOW ALL SHOW MEET THE FBC 140MPH
 (3SEC GUST) 120MPH SUSTAINED.
 THE STRUCTURAL CALCULATIONS WILL BE REVIEWED BY THE
 BUILDING PLAN REVIEWER.
 FBC 106.1.2 ADMIN SECT.
  
 17) NOTE: PLEASE CLARIFY THE LOAD FOR THE LIGHTING IN
 THE COURTYARD AREA FOR FIXTURES SA1. PLEASE SEE 1GHEA
 INDICATES A LOAD OF 7500VA, YET THE 10 FIXTURES AT 400
 EACH DO NOT CORRELATE TO THIS. PLEASE CLARIFY IN
 RESPONSE OF THE TOTAL LOAD IS BE FIGURED BASED ON THE
 INVERTER AT 7500/
 FBC 106.1.2
  
 18) NOTE: PLEASE SEE OTHER SITE LIGHTING FIXTURES SB,
 WHICH IS 24 FIXTURES AT 70W'S EACH, YET THE LOAD ON THE
 PANEL SCHEDULE IS ACTUALLY HIGHER THAN THIS? PLEASE SEE
 1GHA-18.
  
 19) NOTE: PLEASE PROVIDE THE VOLTAGE DROP ON THIS SAME
 CIRCUIT AS NOTED ABOVE IN NOTE # 18, PLEASE SEE FIXTURE
 SA INDICATE #8?S, AND YET SB WHICH CONTAIN A LONGER RUN
 AND MORE FIXTURES ONLY INCREASE UP TO A #10 AWG. PLEASE
 SEE FBC 13-413.1.ABC.1.2.
  
 20) NOTE: PLEASE PROVIDE A WORST CASE FOR BOTH FEEDER
 AND BRANCH CIRCUIT.
 13-413.1ABC.1.
 IT IS NOTEDTHAT ON MANY OF THE PANEL SCHEDULES A VD %
 IS ALREADY SHOWN, HOWEVER PLEASE BE SURE TO INDICATE
 THE ABOVE. (CAN BE DONE ON A SIMPLE TYPICAL TABLE). FBC
 106.1.2.
  
 21) NOTE: PLEASE SEE THE 100% FIRE SPRINKLER PLANS
 SUBMITTED DO NOT CORRELATE WITH THE FA OR ELECTRICAL
 PLANS SUBMITTED WITH RESPECT TO THE FIRE PUMPS. PLEASE
 SEE THE FS SHEETS WHICH INDICATE ELECTRIC, ELECTRICAL/
 DIESEL AND DIESEL. PLEASE SEE THE ELECTRICAL PLANS AND
 THE MANUFACTURE SPECS/CUT SHEETS SUBMITTED ONLY
 INDICATE DIESEL.
 PLEASE SEE THE MINIMUM FUEL TANK SIZE SHALL BE
 SUFFICIENT FOR A MINIMUM OF 8HRS AT 100% LOADS. IF
 ELECTRICAL AND BEING DRIVEN BY THE BACK UP POWER OF AN
 EMERGENCY GENERATOR, THE ON-SITE FUEL SUPPLY SHALL BE
 BASED ON THE 100% LOAD OF THE FIRE PUMP AND ALL OTHER
 LEGAL AND EMERGENCY STAND-BY LOADS AT 100% FOR TIMES
 REQUIRED.
 PLEASE SEE 2002 NFPA-110, TEXT EXTRACTED FORM THE
 CODE:
 9.6.2.2 THE FUEL SUPPLY CAPACITY SHALL BE SUFFICIENT
 TO PROVIDE 8 HOURS OF FIRE PUMP OPERATION AT 100
 PERCENT OF THE RATED PUMP CAPACITY IN ADDITION TO THE
 SUPPLY REQUIRED FOR OTHER DEMANDS.
 PLEASE SEE NFPA-20 2003 IF DIESEL DRIVEN AND THE SAME
 AMOUNT OF FUEL REQUIRED WHICH EQUALS 1GAL PER HP PER
 HOUR PLUS 5% FOR SUMP AND 5% FOR EXPANSION. PLEASE SEE
 THE FOLLOWING THE CODE.
 11.4.3.1 FUEL SUPPLY TANK(S) SHALL HAVE A CAPACITY AT
 LEAST EQUAL TO 5.07 L PER KW (1 GAL PER HP), PLUS 5
 PERCENT VOLUME FOR EXPANSION AND 5 PERCENT VOLUME FOR
 SUMP AND THE COMMENTARY SECTION AS FOLLOWS, A.11.4.3
 THE QUANTITY 5.07 L PER KW (1 GAL PER HP) IS EQUIVALENT
 TO 0.634 L PER KW (1 PINT PER HP) PER HOUR FOR 8
 HOURS. WHERE PROMPT REPLENISHMENT OF FUEL SUPPLY IS
 UNLIKELY, A RESERVE SUPPLY SHOULD BE PROVIDED ALONG
 WITH FACILITIES FOR TRANSFER TO THE MAIN TANKS.
  
 22) NOTE: PLEASE BE SURE THE NFPA-20 2003 EDITION IS
 REFLECT ON ALL PLANS AS THE CURRENT CODE IN EFFECT FOR
 THE SCOPE OF WORK AND DESIGN RELEVANT TO THIS PROJECT.
  
 23) NOTE: PLEASE SEE NEC 210.8B3 FOR ALL RECEPTACLES IN
 KITCHENS IN OTHER THAN DWELLING UNITS. PLEASE SEE THIS
 WOULD BE REQUIRED FOR CAFE/ KITCHENETTE AREAS AS SHOWN
 ON PLANS.
  
 24) NOTE: PLEASE SEE MANY AREAS WHERE THE
 FUTURE/PROPOSED FURNITURE LAYOUTS WERE REMOVED FROM THE
 PLANS WHERE THEY WERE ON THE 50% AND THE 90% PLANS?
 PLEASE LOCATE BACK ON PLANS FOR REVIEW OF THE EGRESS
 PATHS AND LIFE SAFETY FOR MINIMUM WIDTHS ETC. THIS MAY
 ALREADY BE IN THE FIRE MARSHAL'S OFFICE REVIEW
 COMMENTS, HOWEVER IF NOT, THIS IS REQUIRED WHETHER OR
 NOT COMMENT IS MADE.
 LS 101 7.8, 7.9, 7.8.1.3, 7.9.2.2.
  
 25) NOTE: PLEASE SEE MISSING THE PHOTO-METRICS FOR THE
 GARAGE STAIR TOWERS. PLEASE SEE THE PHOTO-METRICS AS
 SUBMITTED ARE A LITTLE CONFUSING. PLEASE PREVIOUS
 COMMENTS ONLY REQUESTED EGRESS PATHS OF LEVELS
 SURFACES/ CORRIDORS AND EGRESS PATHS THAT OF THE STAIR
 TOWERS. PLEASE SEE THERE MUCH INFORMATION SUBMITTED
 GIVING FIXTURE DESIGNATIONS AND ROOM BY ROOM LEVELS?
 PLEASE PROVIDE THE EGRESS PATHS INFORMATION INDICATING
 THE CLEAR NORMAL AND EMERGENCY LEVELS AS NEEDED AND
 REQUIRED BY CODE.
 PLEASE PROVIDE A BREAKDOWN OF THE NORMAL AND EMERGENCY
 AVERAGE. PLEASE SEE THAT INFORMATION OF WHICH IS
 SUPPLIED ON EACH "OVER-ALL" SHEET DOES NOT SUPPLY THE
 INFORMATION AS NEEDED.
 PLEASE SEE 9-4.1 WHICH INDICATES IN TITLE BLOCK,
 EMERGENCY/ NORMAL?
  
 26) NOTE: PLEASE SEE 9-5.2 WHICH SEEMS TO INDICATE
 "DOUBLE FIXTURES" IN STAIR TOWER AREAS.
 PLEASE CLARIFY FOR EACH SECTION OF THE BUILDING AND ON
 EACH LEVEL.
 FBC 106.1.2 ADMIN SECTION.
  
 27) NOTE: PLEASE CLARIFY GARAGE LIGHTING WHICH SHOWS
 "ON" NEXT TO SOME FIXTURES ON PLANS. (RAMP AREAS) THIS
 IS UNCLEAR AT THIS TIME WHAT IS MEANT BY THIS.
 FBC 106.1.2 ADMIN SECTION
  
 28) NOTE: PLEASE PROVIDE A NOTE ON PLANS AND PLEASE BE
 SURE TO CORRELATE WITH THE MECHANICAL PLANS AS THE "XP"
 LCP'S ARE REQUIRED TO BE INSTALLED IN AREAS WITH LESS
 THAN 90% HUMIDITY AS REQUIRED BY THE MANUFACTURE.
 PLEASE BE SURE ALL ROOMS IN WHICH THESE PANELS ARE
 LOCATED SHALL BE CONDITIONED AS REQUIRED. PLEASE
 PROVIDE THE ADDITIONAL NOTE AND ANY CHANGES ON
 MECHANICAL PLANS ALONG WITH NOTE ON 5-3.0.
 110.3, 90.7.
  
 29) NOTE: PLEASE SEE MISSING LCPG.COULD NOT LOCATE ON
 PLANS, SCHEDULE, AND RISER OR ON PLANS.
 FBC 106.1.2ADMIN SECTION.
  
 30) NOTE: PLEASE SEE MISSING THE ELECTRICAL ROOM FOR
 1HMGB AND 1HMGA ON THE LAYOUTS FOR THE ELECTRICAL
 ROOMS.
 PLEASE PROVIDE. 106.1.2,
 NEC 110.26
  
 31) NOTE: PLEASE SEE MAIN ELECTRICAL ROOM AND THE
 MISSING ELECTRICAL ROOM FROM NOTE #30 ABOVE WHICH IS
 STILL INDICATING DOORS WITH AN "IN-SWING" WHICH IS NOT
 PERMITTED. PLEASE ALSO BE SURE TO ADD A NOTE WITH
 RESPECT TO PANIC HARDWARE REQUIRED FOR ALL DOORS AS
 REQUIRED PER 110.26. (MAIN ELECTRICAL ROOM/ AND ROOM
 NOTED ON NOTE #30).
 PLEASE SEE THE DOOR SWINGS WERE NOTED ON ALL OF THE
 REVIEWS BASED ON THE 50%, 90% AND THIS REVIEW. PLEASE
 GO OVER ALL PLANS AND DOORS.
  
 32) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT
 SHEETS FOR AL THE TANK-LESS WATER HEATER UNITS. THESE
 MAY ALSO LABELED AS INSTA-HOTS. PLEASE SEE MISSING
 DISCONNECTS AS REQUIRED ON THESE UNITS. THESE COULD NOT
 BE LOCATED ON PLANS.
 PLEASE SEE SIZING OF THE OVER CURRENT DEVICES,
 DISCONNECTS AND ETC SHALL BE BASED ON EACH UNIT. PLEASE
 SEE 422.31, 110.3, AND 90.7.
  
 33) NOTE: PLEASE SEE SOME TWH UNITS WHICH ARE SHOWN ON
 PLANS ARE MISSING THE REQUIRED CIRCUITING. CAN NOT
 REVIEW FOR COMPLIANCE OF LOAD, CONDUCTOR SIZE, OCP ETC
 AT THIS TIME.
 PLEASE COMPLETE. 240.4, 310.16, 408.4, FBC 106.1.2
  
 34) NOTE: PLEASE PROVIDE INFORMATION FOR FAIL SAFE
 OPERATION OF THE POWER OPERATED DOORS. THE FAILURE OF
 POWER SHALL NOT IMPEDE THE EGRESS FROM A BUILDING
 DURING A POWER FAILURE AT ANY TIME EVEN IF THESE
 CIRCUITS ARE ON THE BACK-UP GENERATOR.
 LS 101 7.19
 THIS MAY BE IN THE FIRE MARSHAL'S REVIEW COMMENTS,
 HOWEVER IF NOT THIS ISSTILL REQUIRED.
  
 35) NOTE: PLEASE ALSO PROVIDE THE FAIL SAFE OPERATION
 OF THE GATES AT THE GARAGE.
 THE SAME NOTE AS ABOVE FOR GATES.
  
 36) NOTE: PLEASE SEE THERE ARE SEVERAL ELECTRICAL ROOMS
 ON PLANS WHICH THE GROUND BAR IS BEING IN THE DOOR WAY?
 THIS IS APPEARS TO BE A MISPRINT. PLEASE CORRECT AND
 ADJUST PLANS AS NEEDED.
 FBC 106.1.2, NEC 110.26
  
 37) NOTE: PLEASE SEE ELECTRICAL ROOM LAYOUT AS THERE
 ARE SOME PANELS WHICH ARE SHOWN IN THE DOOR WAY OR
 PROTRUDING INTO THE DOOR WAY. THIS SEEMS TO BE AN
 OVERLAY/MISPRINT ISSUE AS NOTED ABOVE.
 110.26.
  
 38) NOTE: PLEASE SEE ELECTRICAL ROOM'S LAYOUTS WHICH
 ARE MISSING WALLS AND DOORS. PLEASE SEE 2ND, 3RD, AND
 4TH FLOORS ROOM #4. 4-2.0,4- 3.0,4-4.0
 CAN NOT VERIFY SOME CODE RELATED ITEMS AT THIS TIME.
 110.26.
 FBC 106.1.2 ADMIN SECTION.
  
 39) NOTE: PLEASE SEE ELECTRICAL ROOM LAYOUTS WHICH ARE
 SHOWING PANELS WHICH ARE NOT ON ANY RISER, PANEL
 SCHEDULES ETC. PLEASE ALSO SEE TRANSFORMERS BEING SHOWN
 WHICH ARE NOT LABELED ALSO?
 PLEASE LABEL AS "FUTURE" IF INDEED THE SPACE IS BEING
 ALLOTTED FOR FUTURE EXPANSION WHICH IS REQUIRED BY CODE
 UNDER 90.8, 110.26
  
 40) NOTE: PLEASE BE SURE TO LABEL ALL LCP?S ON PLANS,
 ELECTRICAL ROOMS, RISER AND CORRELATE WITH THE LCP'S
 SCHEDULE.9EXAMPLE LCP1D, LCP3B, ETC)
 FBC 106.1.2, 106.3.5.1.2
  
 41) NOTE: PLEASE SEE ELECTRICAL ROOM LAYOUTS, SOME SHOW
 TRANSFORMER SIZES AND SOME DO NOT. PLEASE COMPLETE AND
 SHOW.
 450, FBC 106.1.2, 110.26, 450.9, ETC
  
 42) NOTE: PLEASE SEE ELECTRICAL ROOM LAYOUTS INDICATE
 WHAT IS BEING SHOWN AS "NAC" PANELS; HOWEVER IT IS
 UNCLEAR WHAT THESE ARE? PLEASE EXPLAIN.
 FBC 106.1.2, 106.3.5.1.2
  
 43) NOTE: PLEASE SEE "SHADED" AREAS ON MEZZANINE LEVEL
 PLANS E-1.1.4, PLEASE CLARIFY
 106.1.2 FBC ADMIN SECTION.
  
 44) NOTE: PLEASE SEE STAIR TOWERS WHICH ALSO INDICATE
 AN ELECTRICAL ROOM IN THE STAIRWELL. THIS APPEARS TO BE
 SOME SORT OF MISPRINT. THIS IS BEING SHOWN ON MORE THAN
 ONE FLOOR AND LOCATION. PLEASE BE SURE TO CORRELATE
 WITH ALL OTHER PLANS.
 FBC 106.1.2
 *** ONLY AS NOTED, IT IS KNOWN THAT NO ELECTRICAL
 EQUIPMENT OR OTHER ITEMS ARE PERMITTED IN EXIT
 STAIRWAYS UNLESS PERTAINING TO STAIRWAYS.
  
 45) NOTE: PLEASE SEE OTHER SHEETS WHICH INDICATE THE
 OPENING FOR THE DOOR LEADING INTO THE STAIRS ACTUALLY
 THROUGH WHAT WOULD BE THE LOW VOLTAGE ELECTRICAL DATA
 ROOM. WHERE THE SANE LOCATION IS SHOWING WHAT APPEARS
 TO BE A DOOR ON THE SHEER/RATED STAIRWAY WALL. PLEASE
 SEE THIS IS SHOWN LIKE THIS AT MANY LOCATIONS AND ON
 MULTIPLE FLOORS. PLEASE BE SURE TO COORDINATE LAYERS,
 LEVELS, AND SHEETS FOR ALL.
 FBC 106.1.2 ADMIN SECTION.
  
 45) NOTE: PLEASE SEE WHAT APPEARS TO BE MISSING WALLS,
 DOORS SEPARATION E-1-1.2, LIBRARY/MUSEUM/ STORE? PLEASE
 SHOW AS THE REQUIREMENTS FOR CHAPTER 13 CAN NOT
 VERIFIED FOR CONTROL OF LIGHTING. LIGHTING OF SOME TYPE
 INCLUDING EXIT/EMERGENCY LIGHTS ARE STILL REQUIRED IN
 SPACE, EVEN IF FOR FUTURE BUILD OUT. PLEASE SEE LS 101
 7.8, 7.9 AND POSSIBLE COMMENTS FROM FIRE MARSHAL?S
 OFFICE.
 13-415.1.ABC.1.ABC.1.1, .1.2, .1.3
  
 46) NOTE: PLEASE VERIFY LIGHTING POWER DENSITIES FOR
 GARAGE. SOME OF WHICH WERE NOTED ABOVE IN COMMENTS FOR
 CHAPTER 13 REQUIREMENTS, HOWEVER THIS IS ALSO BE NOTED
 SEPARATELY.
 PLEASE SEE CONTROL MEANS.
 SEE FBC CHAPTER 13. (ALL)
  
 47) NOTE: PLEASE PROVIDE AN ELEVATION/DETAIL FOR ALL
 ELECTRICAL CONDUITS BEING RUN FROM GARAGE TO THE MAIN
 BUILDING. THIS BUILDING IS BEING CONSIDERED "ATTACHED"
 AND ONE " BUILDING" BY DEFINITION, HOWEVER DUE THE
 UNDERSTANDING OF MANY OF THE CONDUITS ARE NOW BEING
 INSTALLED IN THE SLAB OR UNDER GROUND AND THE AMOUNT OF
 OTHER CONDUITS, PIPING, BEING INSTALLED IN THIS SAME
 AREA, IT IS OF CONCERN FOR THE SPACE REQUIREMENTS FOR
 BUNDLING OF CONDUITS, DE-RATING OF CONDUCTOR
 AMPACITIES. ETC. (THIS CAN BE A DETAIL LIKE A DUCT-BANK
 DETAIL)
 FBC 106.1.2, 310.16, 300.8, 300.10, 310.10, 310.15,
 310.16, 300.17 ETC.
 THERE ARE MANY SECTIONS WHICH COULD BE REFERENCED.
 PLEASE ALSO SEE COMMENT WITH RESPECT TO WIRING METHODS
 OF EMERGENCY FEEDERS ETC.
  
 48) NOTE: PLEASE VERIFY THE SHUNT TRIP FOR THE 4TH
 FLOOR IT PANEL. PLEASE SEE THIS SHUNT TRIP BREAKER
 SHOULD BE LOCATED IN 1HEE. PLEASE ALSO SEE THAT PLANS
 INDICATE WHAT SEEMS TO BE A PUSHBUTTON AT ONE DOOR
 LABELED EPO, AND ONE WHICH APPEARS TO BE THE SAME
 HOWEVER NOT LABELED AS EPO.PLEASE LABEL. AN EPO WILL
 BE REQUIRED AT EACH DOOR.
 PLEASE SEE 645.10, HANDBOOK WHICH EXPLAINS THE
 DISCONNECTING AT THEIR SUPPLY POINT.
  
 49) NOTE: PLEASE KNOW AS NO INFORMATION FOR THE IT ROOM
 EQUIPMENT IS BEING SUBMITTED WITH THIS RECORD SET OF
 PLANS, PLEASE PLACE NOTE AND CLOUD ON 4TH FLOOR POWER
 PLANS THAT ALL ELECTRICAL EQUIPMENT, UPS, SERVER
 EQUIPMENT ETC IN THE IT ROOM SHALL BE UNDER A SEPARATE
 PERMIT, PLANS, AND FEES BASED ON THE EQUIPMENT BEING
 INSTALLED IN THIS ROOM. REVIEW FOR CODE COMPLIANCE FOR
 THIS ROOM CAN NOT BE COMPLETED AT THIS TIME. THE
 REQUIREMENTS FOR THE CONSTRUCTION OF THIS ROOM IS
 REQUIRED AT THIS TIME, INCLUDING THE MINIMUM 1HRA
 RATING, THE FIRE DAMPERS ETC (IF APPLICABLE) AND THE
 SHUT DOWN OF AN AND ALL A/C EQUIPMENT.
 NEC 645, NFPA-75
  
 50) NOTE: PLEASE PLACE NOTE ON THE LIGHTNING PROTECTION
 PLANS, BOTH THE LAYOUT OF THE SYSTEM AND THE SYSTEM
 DETAIL.
 THESE PLANS MAY BE USED FOR REFERENCE OF PERMITTING
 PROJECT; HOWEVER SEPARATE PERMIT AND FEES WILL BE DUE
 UPON APPLICATION. THE LP SYSTEM IS NOT PART OF THE
 VALUE FOR SCOPE OF WORK.
 PLEASE ALSO NOTE THAT SYSTEM MUST BE INSTALLED BY A
 LICENSED LIGHTING PROTECTION CONTRACTOR WHO WILL
 PROVIDE A MASTER UL CERTIFICATION OF THE SYSTEM UPON
 COMPLETION.
 (OR WORDS TO THAT AFFECT)
  
 51) NOTE: PLEASE SEE LOADS FOR RECEPTACLE CIRCUITS
 SHALL BE BASED ON 180VA MINIMUM FOR CIRCUITS. PLEASE
 SEE CIRCUITS FOR WHAT IS A "J" BOX FOR FUTURE MODULAR
 FURNITURE IS LABELED AS RECEPTACLES? PLEASE LABEL FOR
 THE INTENDED USE.
 408.4, 220.10
  
 52) NOTE: PLEASE SEE PLANS WHICH INDICATE A TRIANGULAR
 SYMBOL WITH A "F" NEXT TO THESE HOWEVER COULD NOT ANY
 INFORMATION ON WHAT THESE ARE ON ANY SYMBOL LEGEND?
 PLEASE REMOVE OR DESIGNATE.
 FBC 106.1.2
  
 53) NOTE: PLEASE COORDINATE ALL OVER-LAYS AND LAYOUTS
 FOR ELECTRICAL, MECHANICAL, PLUMBING, BUILDING AND ALL
 OTHER TRADE PLANS. PLEASE KNOW THE ELECTRICAL 100%
 PLANS DO NOT SHOW THE SAME ELECTRICAL ROOMS AND
 EQUIPMENT AS THE 100% MECHANICAL PLANS, PLUMBING OR
 BUILDING PLANS ALONG WITH OTHER SHEETS FROM OTHER
 TRADES.
 REVIEW OF ALL APPLICABLE ITEMS WILL STILL NEED TO BE
 DONE AS REQUIREMENTS FOR ELECTRICAL AND OTHER TRADES
 WILL MOST CONTAIN CLEAR CONFLICTS WHICH MAY OR MAY NOT
 BE PERMITTED.
 110.26, 240.24 NEC.
 FBC 106.3.5.1.1 ADMIN SECTION FOR ALL TRADES FOR
 COMMERCIAL PLANS.
  
 54) NOTE: PLEASE CORRELATE THE PLANS WITH THE
 MANUFACTURE SPECS/CUT SHEETS FOR THE GENERATOR WHICH IS
 BEING SUBMITTED AS A LARGER UNIT IN THE SPEC BOOK AS
 SHOWN ON PLANS. THIS WILL AFFECT THE FUEL SUPPLY, AND
 THE FUEL LINE SUPPLY FOR THE PROPOSED NATURAL GAS
 LINE.
 90.7, 110.3,
 FBC 106.1.2
  
 55) NOTE: PLEASE INCLUDE DETAIL AND ATTACHMENT FRO THE
 LIGHTNING PROTECTION SYSTEM AS PART OF THE MAIN
 GROUNDING ELECTRODE SYSTEM AS REQUIRED PER 250.106. IT
 IS NOTED THAT THE DETAIL IN THE LP DETAILS IN THE REAR
 OF PLANS, HOWEVER DOES NOT INCLUDE THE GE SYSTEM, OR
 THE GE RISER, SYSTEM DOES NOT INCLUDE THE LP GROUNDING
 ATTACHMENT.
  
 56) NOTE: PLEASE INCLUDE ALL OTHER METAL WATER PIPING
 SYSTEMS AS PART OF THE GROUNDING ELECTRODE SYSTEM AS
 REQUIRED PER 250.106. (FIRE SPRINKLER)
  
 57) NOTE: PLEASE SEE SOME BATHROOMS CONTAIN OC SENSORS
 AND MANY DO NOT, PLEASE EXPLAIN AND PLEASE SEE OTHER
 COMMENTS FOR TYPE OF DEVICES WHICH WILL BE REQUIRED.
 13-415.1.ABC.1.2
  
 58) NOTE: PLEASE KNOW SOME SORT OF BATTERY BACK UP
 FIXTURE WILL BE REQUIRED IN THE LARGER BATHROOMS (ROOM
 OTHER THAN SINGLE POINT OF USE).
 PLEASE SEE LS 101 7.8., 7.9
 THIS WAS DISCUSSED WITH THE FIRE MARSHAL CHIEF AND WILL
 BE REQUIRED BOTH BY THIS OFFICE AND THE FIRE MARSHAL'S
 OFFICE IN THE INTEREST OF LIFE SAFETY AND CODE AS
 REFLECT.
  
 59) NOTE: PLEASE SEE NUMEROUS OFFICES ON ONE CIRCUITS
 COMING FROM THE LIGHTING CONTROL PANEL(S). PLEASE SEE
 THE FOLLOWING SCENARIO: IN THE EVENT OF AFTER HOURS,
 THE TIMER ?SWEEPS? THROUGH AND TURNS OFF THAT
 PARTICULAR CIRCUIT, AND EMPLOYEE WILL "RESET" THE
 SENTRY SWITCH WHICH IN-TURN TURN THAT BRANCH CIRCUIT
 BACK ON. WOULD THAT NOT IN-TURN ON OTHER LIGHTS ON THAT
 CIRCUIT. (OTHER ROOMS, OFFICES ETC?)
 PLEASE SEE PREVIOUS NOTE ABOVE #9 WHICH ALSO TOUCHED ON
 THE LIGHTING CONTROL SYSTEM BEING PROPOSED, HOWEVER
 THERE ARE SCENARIOS WHICH ARE STILL IN QUESTION OR NEED
 TO BE WORKED OUT.
 13-415.1.ABC.1.1
  
 60) NOTE: PLEASE SEE MISSING CONTROLS FOR ELEVATOR PIT
 LIGHTS. 13-415.1.ABC.1.2,
 620.24B.
  
 61) NOTE: PLEASE SEE THERE ARE SOME LOCATIONS ON PLANS
 WHICH ARE SHOWING "NL'S" (NIGHT LIGHTS) BEING PART OF A
 PERMANENT ON SCENARIO, HOWEVER THE NUMBER OF FIXTURES
 BEING PROPOSED TO REMAIN ON AS NIGHT LIGHTS ARE OVER
 WHAT IS BEING CONSIDERED AS NORMAL. PLEASE KNOW THIS
 CAN BE GONE OVER, HOWEVER PLEASE SEE SOME AREAS WHERE
 THERE ARE 10-20PLUS LIGHTS BEING LEFT ON.
 THE INTENT OF CHAPTER 13 AND ALSO THE INTEREST OF LIFE
 SAFETY SHOULD BE CONSIDERED. PLEASE CALL TO OVER. SEE
 SHEET E2-1.2 FOR EXAMPLE IN LOBBY AREA.
  
 62) NOTE: PLEASE SEE NFPA-20 11.3, 11.3.2, 11.3.2.3 AND
 FLORIDA FIRE PREVENTION CODE , NFPA-1 7-4FOR OTHER
 REQUIREMENTS FOR FIRE PUMPS AND ROOMS IN WHICH THEY ARE
 LOCATED.
 PLEASE ALSO SEE 11.4.6.2 FUEL PIPING SHALL NOT BE
 GALVANIZED STEEL OR COPPER.
 PLEASE KNOW AS PART OF THE COMPLETED TESTING AND
 ACCEPTANCE AS REQUIRED IN CHAPTER 14, DOCUMENTATION FOR
 TESTING FOR FIRE PUMP ON A WEEKLY BASIS IS REQUIRED TO
 THE OWNER OF RECORD.CODE TEXT FROM NFPA-20: 11.6.1.1
 ENGINES SHALL BE STARTED NO LESS THAN ONCE A WEEK AND
 RUN FOR NO LESS THAN 30 MINUTES TO ATTAIN NORMAL
 RUNNING TEMPERATURE.
  
 63) NOTE: PLEASE SEE NFPA-110 CHAPTER 7 FOR THE
 INSTALLATION OF THE GENERATOR. PLEASE SEE 7.4 AND 7.5,
 PROVIDE DETAIL FOR MOUNTING OF UNIT TO ALLEVIATE ANY
 INTEGRITY INTERFERENCE OF THE STRUCTURE.
  
 64) NOTE: PLEASE SUBMIT THE SPEC/CUT SHEET FOR THE
 PROPOSED MTS. THE "KIRK KEY" AS SHOWN AND HAND WRITTEN
 ON SPECS IS NOT ACCEPTED AT THIS TIME. THERE ARE MANY
 OF THESE SYSTEMS ON THE MARKET WHICH WILL PERMIT THE
 POWER FROM TWO SOURCES AT ONCE WHICH IS STRICTLY
 PROHIBITED. PLEASE SEE 700.6, 701.7, 110.3, AND 90.7
 CAN NOT VERIFY AT THIS TIME. PLEASE ALSO SEE THE
 FOLLOWING COMMENT.
  
 65) NOTE: PLEASE SEE RISER AND PLANS WERE REVISED FROM
 THE 50% AND 90% PLANS CHANGING ALL ATS UNITS TO 3-POLE
 UNITS. PLEASE SEE ALTHOUGH GF PROTECTION IS NOT
 REQUIRED ON THE EMERGENCY SIDE OF THE EMERGENCY SYSTEM
 AND LEGALLY REQUIRED SYSTEMS, PROPER GROUND FAULT
 SENSING IS REQUIRED. PLEASE KNOW DOCUMENTATION FROM
 MORE THAN ONE MANUFACTURE WAS SENT TO THE ENGINEER
 PRIOR TO THE REVIEW WHEN THE PLANS WERE SUBMITTED ON
 THE 7TH OF NOV. PLEASE SEE NFPA-110 6.2.15** ISOLATION
 OF NEUTRAL CONDUCTORS. PROVISIONS SHALL BE INCLUDED FOR
 ENSURING CONTINUITY, TRANSFER, AND ISOLATION OF THE
 PRIMARY AND THE EPS NEUTRAL CONDUCTORS WHEREVER THEY
 ARE SEPARATELY GROUNDED TO ACHIEVE GROUND-FAULT
 SENSING.
 PLEASE SEE AN ATTACHED BRIEF EXPLANATION FROM"ASCO"
 WHITE PAPER: WHERE GROUND FAULT PROTECTION IS TRIGGERED
 BY THE CODE AND AN ALTERNATE POWER SUPPLY IS INCLUDED,
 SWITCHING OF THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT
 SHOWN ABOVE ILLUSTRATES SUCH A CIRCUMSTANCE. THE
 SERVICE IS LARGER THAN 1,000 AMPS. CONSEQUENTLY, GROUND
 FAULT PROTECTION IS REQUIRED AT THE MAIN SERVICE
 DISCONNECT AT A MINIMUM. IF IT IS INSTALLED THERE AND
 THE GENERATOR NEUTRAL GROUNDING WAS THROUGH A SOLID
 CONNECTION TO THE MAIN SERVICE NEUTRAL, A GROUND FAULT
 WHEN THE GENERATOR IS FEEDING THE LOAD WILL CAUSE THE
 MAIN SERVICE DISCONNECT TO OPEN. THIS WILL NOT
 DISCONNECT THE ARCING FAULT FROM THE GENERATOR.
 COORDINATION IS THUS LOST."
 PLEASE KNOW BASED ON THE INFORMATION FROM SEVERAL
 MANUFACTURES AND THE CODE PLEASE ADJUST AS REQUIRED.
 PLEASE ALSO SEE GENERATOR GROUNDING DETAIL WILL BE
 REQUIRED TO BE REVISED.
 PLEASE SEE E5-1.1.18 WHICH NOTES A #3 CONDUCTOR, WHICH
 WOULD NOT BE LARGE ENOUGH.
 PLEASE SEE 250.20, 250.30, 250.66, 240.13, 230.95,
 700.7D, 700.26
 PLEASE SEE THE MTS.
  
 66) NOTE: PLEASE SEE THERE ARE MANY EXIT/EMERGENCY
 LIGHTS WHICH DO NOT SHOW ANY CONNECTION TO ANY LOCAL
 CIRCUIT IN ANYWAY. PLANS NOTE THIS AND MANY ARE SHOWN
 THIS WAY, HOWEVER NOT ALL. PLEASE GO THROUGH PLANS.
 PLEASE SEE 700.12E WHICH REQUIRES THE BRANCH CIRCUIT
 FEEDING THE UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL LIGHTING IN THE AREA
 AND CONNECTED AHEAD OF ANY LOCAL SWITCHES.
  
 67) NOTE: PLEASE SEE OVER ALL 3RD FLOOR PLANS, WHICH
 SEEM TO BE SHOWING LIGHTING OF SOME KIND ON GARAGE
 PLANS?
 PLEASE ALSO SEE E2-4.0
 FBC 106.1.2 ADMIN SECTION.
  
 68) NOTE: PLEASE SEE NOTE #2 ON RISER WITH RESPECT TO
 THE MTS WHICH IS TO PROVIDE FUTURE PROVISIONS FOR
 POSSIBLE PORTABLE GENERATOR TO RUN THE EMERGENCY
 SYSTEMS, PLEASE KNOW A DETAIL TO A LOCATION AND HOW
 THIS CONNECTION WILL BE MADE IS REQUIRED.THE RUNNING
 OF CORDS, CONDUCTORS ETC SHALL BE PERMITTED TO TRAVEL
 THROUGH THE ELECTRICAL ROOM DOORS, ON SIDEWALK AREAS OR
 ANY LOCATIONS PROVIDING A TRIPPING HAZARD OR NOT
 SECURING LIVE PARTS ETC.
 PLEASE PROVIDE A DETAIL AS THIS CONNECTION POINT WILL
 BE SUBSTANTIAL IN NATURE. (J-BOX) ETC ON THE OUTSIDE OF
 BUILDING ETC.
 110.26, 110.27, NEC 527.
  
 69) NOTE: PLEASE PROVIDE CALCULATIONS ON NEUTRAL
 CONDUCTORS FOR ALL NON-LINEAR CIRCUITS. PLEASE SEE ALL
 CIRCUITS WHICH CONTAIN THESE LOADS SHALL MEET THE
 SIZING REQUIREMENTS TO HANDLE AND ALLEVIATE THE OVER
 LOADING OF THE NEUTRAL ON A 3-PHASE 4-WIRE SYSTEM WITH
 PREDOMINATELY OR ACTUALLY IN MANY CASES ALL NON-LINEAR
 LOADS. PLEASE SEE THIS CAN BE DONE BY USING MANY
 METHODS. THE K-RATED TRANSFORMERS WERE REMOVED FROM THE
 DESIGN AS ON PREVIOUS PLANS, SO PLEASE SEE THE REQUEST
 FOR FULL NEUTRAL LOAD CALCULATION OR THE SIZING OF THE
 NEUTRAL AT 200%.
 PLEASE SEE THE RISK OF FIRE AND CAUSE TO PROPERTY
 DAMAGE IS OF CONCERN PLEASE SEE STUDIES IN WHITE PAPERS
 WHICH INDICATE AS MUCH AS 1.7 TIMES THE RATED LOAD OF
 THE CONDUCTOR.
 PLEASE SEE THE FOLLOWING CODES: THIS OFFICE IS AWARE OF
 WHAT A FPN MEANS, HOWEVER SEE SECTIONS GIVEN WHICH DO
 NOT CONTAIN FPN. 210.4A (FPN), 220.22 (FPN(2), 310.10,
 310.15B4(C), 400.5, 520.44, 408.16, AND FBC 104.6
 ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF WEST
 PALM BEACH.
  
 70) NOTE: PLEASE SEE E2-4.2 STAIR TOWER AREA WHICH
 MENTIONS "HOLD FOR ARCHITECT" ? PLEASE SEE PREVIOUS
 NOTE WITH RESPECT TO DOORS INTO STAIRWAYS ETC.
 FBC 106.1.2 ADMIN SECTION.
  
 71) NOTE: PLEASE KNOW IF IT IS THE INTENT TO UTILIZE
 THESE PLANS FOR FUTURE LOW VOLTAGE WORK FOR LOCATIONS
 OF PHONE, DATE DROP ETC, PLEASE COMPLETE PLANS AS
 SUBMITTED SHOWING ALL LOCATIONS FOR DROPS.PLEASE SEE
 MANY AREAS WHICH LOW VOLTAGE DATE/PHONE DROPS WILL BE
 REQUIRED OR INSTALLED, HOWEVER THESE LOCATIONS ARE NOT
 BEING SHOWN AT THIS TIME.
 IF THE LV SCOPE IS PART OF THE PERMITTED PLANS AS
 SUBMITTED PLEASE REMOVE AND NOTE AS UNDER SEPARATE
 PERMIT PLANS AND FEES.
  
 72) NOTE: PLEASE PROVIDE VD FOR THE FEEDER FOR THE IT
 PANEL. 13-413.1.ABC.1.1
  
 73) NOTE: PLEASE SEE 700.9D FOR THE FEEDERS FROM THE
 GENERATOR TO THE EMSB1 AND THE FEEDERS OUT TO SYSTEMS
 WHICH MAY BE CONSIDERED INSIDE THE BUILDING. PLEASE SEE
 THE CODE AS THERE ARE WAYS TO MEET THE INSTALLATION OF
 THESE FEEDERS, HOWEVER PLANS SHALL INDICATE WHICH WILL
 BE USED. (TYPE OF CABLE, ENCASED IN 2INCHES OF
 CONCRETE, FULLY SPRINKLED ETC)
 PLEASE KNOW AS THE REQUIREMENT OF FULLY SPRINKLED IS
 OFTEN MISTAKEN AS A BUILDING CONTAINING SPRINKLERS.
 THIS IS NOT THE CASE. PLEASE SEE THE INTENT OF 700.9D
 FOR THIS HAS ALWAYS BEEN THAT ALL AREAS CONTAINING
 THESE FEEDERS BE SPRINKLED IF INSTALLED IN OPEN OR
 ABOVE CEILINGS. PLEASE KNOW A COMMENTARY IN THE 2005
 NEC MAKES IS CLEAR WHAT THE INTENT OF THE CODE AND THE
 FURTHER EXPLANATION IS PROVIDED.
  
 74) NOTE: PLEASE SEE NOTE WHICH MENTIONS A "LOCK-OFF"
 DEVICE IS REQUIRED FOR THE FIRE ALARM CIRCUIT. THIS IS
 OK; HOWEVER PLEASE ELABORATE ON THE NOTE AS THE DEVICE
 SHALL BE AN INTEGRAL PART OF THE BREAKER. PLEASE KNOW
 THAT SNAP ON/CLIP ON TYPE DEVICES ARE NOT ACCEPTABLE TO
 THIS AHJ.
 110.3, 90.4
  
 75) NOTE: PLEASE SEE TRANSFORMER TYPICAL DETAIL WHICH
 INDICATES #6 FOR 75KVA TRANSFORMERS. PLEASE SEE
 250.30A2 AND 250.66 FOR THE SIZE ACCORDING TO THE
 4/0'S.
 PLEASE ADJUST. THIS WILL AFFECT THE SIZE TO THE GROUND
 BAR ONLY IN EACH ROOM FROM THIS TRANSFORMER.
  
 76) NOTE: PLEASE PROVIDE THE SIZE OF THE CONDUCTOR ON
 THE GROUNDING ELECTRODE RISER AS PROVIDED. PLEASE SEE
 THE GROUNDING ELECTRODE DETAIL SHOWS A 4/0'S, HOWEVER
 PLEASE SEE E5-2.0.
 250.50, 250.58
  
 77) NOTE: PLEASE SEE THE SIZE OF THE CONDUCTORS ON THE
 SECONDARY SIDE OF ANY TRANSFORMER SHALL BE SIZED AND
 TERMINATE IN OVER-CURRENT PROTECTION WHICH LIMITS THE
 LOAD ON THE CONDUCTORS. PLEASE SEE 240.21C, 310.16.
 PLEASE SEE 1LD2
  
 78) NOTE: PLEASE SEE 4HA, WHICH INDICATE 114A'S OF LOAD
 ON A BREAKER RATED AT 100A?S. PLEASE ALSO SEE 5HA WHICH
 SHOWS A LOAD OF 99A'S ON A 100A BREAKER.
 PLEASE ADJUST AS REQUIRED AS THE LOADS SHALL NOT EXCEED
 THAT OF THE RATING OF THE BREAKER, FEEDERS ETC. 310.16,
 240.4, ETC.
  
 79) NOTE: PLEASE SUBMIT LOAD CALCULATIONS. PLEASE
 INDICATE AND SHOW ALL CONTINUOUS LOADS AND LARGEST
 MOTOR LOADS AT 125%.
 220.3, 220.10, 220.11, 220.13, 215.3,230.42 ETC
  
 80) NOTE: PLEASE SEE SOME SHEETS ON THE UPPER LEVELS,
 1-5.2, 8-5.2 INDICATE A "VAULT", HOWEVER THIS WAS
 COMMENTED ON PREVIOUS REVIEWS AND WAS REMOVED FROM SOME
 SHEETS. PLEASE SEE A SHEET FOR THE SW CORNER OF PROJECT
 AFTER E6-2.1 IF THIS IS INDEED THE SAME AREA. PLEASE
 CLARIFY.
 FBC 106.1.2 ADMIN SECTION.
  
 81) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 MINIMUM FOOT CANDLES REQUIRED. PLEASE SEE GARAGE SHALL
 CONTAIN EGRESS PATHS WHICH MEET THIS MINIMUM. BASED ON
 SOME AREAS SHOWN ON PHOTO-METRICS, IT DOES NOT APPEAR
 THIS IS MET.
 PLEASE SEE LIFE SAFETY CODE NFPA-101 2003 7.8.1.3,
 7.9.2.2
  
 82) NOTE: PLEASE SEE WHAT IS KNOW AS STAIR #9, MORE
 THAN ONE FIXTURE BEING SHOWN ON THE SAME LEVEL ON THE
 SAME WALL. THIS IS OK, HOWEVER ONLY A NOTE FOR
 VERIFICATION.
 E9-2.2
  
 83) NOTE: PLEASE CORRELATE THE TRANSFORMERS ON THE
 ELECTRICAL ROOM LAYOUTS AND THE ELECTRICAL RISER.
 PLEASE SEE THERE ARE MANY WHICH ARE SHOWN AS 15KVA ON
 ONE SHEET AND 45KVA ON OTHER SHEETS OR 45KVA ON ONE AND
 75KAV ON ANOTHER. PLEASE ALSO SEE RISER.
 PLEASE SEE SOME BELOW AS NOTED, THIS IS ONLY SOME AND
 IS IN NO WAY ALL POSSIBLE.
 1HB, 75KVA ON RISER, 45KVA IN ELECTRICAL ROOM. 2HB,
 75KVA ON RISER, 45KAV IN ELECTRICAL ROOM. 1GLA-1GHA,
 45K ON RISER, 15K ON ELECTRICAL ROOM PLANS. ETC
  
 84) NOTE: PLEASE BE SURE TO GO THROUGH ALL TRANSFORMERS
 AS THE SIZES AS SHOWN MAY AFFECT THE OVER CURRENT
 PROTECTION ON UNITS, THE CONDUCTORS ON THE PRIMARY AND
 SECONDARY SIDE OF THE UNITS. PLEASE SEE COMMENTS WITH
 RESPECT TO SOME.
 PLEASE SEE TRANSFORMER DETAIL ON 6-1.0, THIS SCHEDULE
 IS BEING SHOWN FOR TYPICAL, HOWEVER IT DOES CORRELATE
 WITH SOME UNITS AS NOTED. SOME ARE SHOWN AS 75KVA WHICH
 ON TYPICAL SCHEDULE MENTIONS 225A OVER CURRENT
 PROTECTION ON THE SECONDARY SIDE, YET SOME TERMINATE IN
 150A OCP ON THE SECONDARY SIDE.
 PLEASE GO THROUGH THESE: 3LC2, EXAMPLE.(NOT ALL)
  
 85) NOTE: PLEASE SEE FBC 2004 CHAPTER 11 FOR
 REQUIREMENTS FOR ADA WITH RESPECT TO HORNS, AND
 STROBES. THE AUDIBLE LEVELS SHALL BE PER BOTH FBC
 CHAPTER 11 AND NFPA-72 AS NOTED, HOWEVER THE MORE
 STRINGENT SHALL APPLY.
 PLEASE SEE 11-4.28.1, 11-4.28.2 AND 11-4.28.3(4).
 PLEASE BE SURE THE LEVELS ARE INDICATED ON PLANS.
 PLEASE KNOW THE LIGHTING CANDELA LEVELS AS REQUIRED IN
 THE FBC ARE FAR GREATER THAN THAT OF NFPA-72. THE
 MINIMUM LEVELS FOR VISUAL SHALL BE 75 CANDELAS. PLEASE
 ADJUST AND PLACE REQUIREMENTS ON PLANS. PLEASE SEE ALL
 FA SHEETS WHICH ONLY INDICATE NFPA-72.
  
  
 86) NOTE: PLEASE KNOW A RESPONSE LETTER/NOTES WERE
 PROVIDED, HOWEVER AS THIS REVIEW WAS MORE OF A REVIEW
 FOR CODE COMPLIANCE, A MORE DETAILED RESPONSE WOULD
 GREATLY HELP IN THE REVIEW PROCESS. THIS RESPONSE COULD
 INDICATE THE SHEETS/LOCATIONS OF CHANGES, CORRECTIONS
 OR ANY COMMENTS RELATED TO AND RESPECT TO THIS
 REVIEWERS NOTES.
 IF ANY OF THESE COMMENTS ARE NOT CLEAR IN ANY FASHION
 OR IF ANY ITEMS ARE NOT UNDERSTOOD IN ANY WAY?PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
  
 ** PLEASE KNOW AS THERE IS SOME INFORMATION NOT YET
 SUBMITTED PLEASE BE SURE TO GO OVER ALL.
  
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. ONCE AGAIN IF THERE
 ARE ANY QUESTIONS , PLEASE DO NOT HESITATE IN CONTATING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-11-25 08:33:56REVIEW BACK IN PROGRESS 11/25/06
2006-11-22 07:38:23REVIEW IN PROGRESS
2006-11-21 20:11:49REVIEW STOPPED, WILL CONTINUE ON 11/22
2006-11-21 18:54:07ELECTRICAL REVIEW HAS NOW RESUMED FROM 11/8
2006-11-08 19:53:56ELECTRICAL REVIEW STILL IN PROGRESS.
2006-11-07 16:03:13NEW ELECTRICAL PLANS BROUGHT IN BY MR. JAMES MINDUR AT
 1500HRS ON 11/6/06
 ELECTRICAL REVIEW IN PROGRESS.