Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-10-25 13:27:37 | BUILDING REVIEW CHECKLIST: | | | | 1- NEED RECORDED NOTICE OF COMMENCEMENT. | | | | 2- ACCORDING TO KEY PLAN SUBMITTED ALL OPENINGS WILL | | HAVE ACCORDION SHUTTERS.PLEASE, IDENTIFY WHICH ONE IS | | THE MEANS OF ESCAPE WHEN SHUTTERS ARE UP IN ORDER TO | | COMPLY WITH SEC. R310.4 2004 FLORIDA RESIDENTIAL CODE. | | | | 3- PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE FOR | | PRODUCT APPROVAL SUBMITTED.GO TO | | WWW.FLORIDABUILDING.ORG TO DOWNLOAD ALL INFORMATION. | | | | 4- PROVIDE COMPLETE INFORMATION IN THE INSTALLATION | | SCHEDULE. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. SEE | | ATTACHED SAMPLE COPY OF INSTALLATION SCHEDULE. COMPLETE | | ALL INFORMATION THAT APPLIES. | | | | 5- CHECK PRODUCT APPROVAL FOR PROPER WAY OF MEASURING | | SHUTTER SPAN. SHUTTER SPAN AND OPENING HEIGHT IS NOT | | THE SAME DIMENSION.REVISE AS REQUIRED. | | | | 6-IF EDGE DISTANCE IS LESS THAN 3 1/2", THEN | | CALCULATE ANCHOR SPACING ACCORDING TO CHART SHOWN AT | | BOTTOM OFSHEET11 OF 14 OFACCORDION SHUTTERS | | #05-195. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|