Plan Review Notes
Plan Review Notes For Permit 06100546
Permit Number 06100546
Review Stop B
Sequence Number 1
Notes
Date Text
2006-10-25 13:27:37BUILDING REVIEW CHECKLIST:
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- ACCORDING TO KEY PLAN SUBMITTED ALL OPENINGS WILL
 HAVE ACCORDION SHUTTERS.PLEASE, IDENTIFY WHICH ONE IS
 THE MEANS OF ESCAPE WHEN SHUTTERS ARE UP IN ORDER TO
 COMPLY WITH SEC. R310.4 2004 FLORIDA RESIDENTIAL CODE.
  
 3- PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE FOR
 PRODUCT APPROVAL SUBMITTED.GO TO
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD ALL INFORMATION.
  
 4- PROVIDE COMPLETE INFORMATION IN THE INSTALLATION
 SCHEDULE. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. SEE
 ATTACHED SAMPLE COPY OF INSTALLATION SCHEDULE. COMPLETE
 ALL INFORMATION THAT APPLIES.
  
 5- CHECK PRODUCT APPROVAL FOR PROPER WAY OF MEASURING
 SHUTTER SPAN. SHUTTER SPAN AND OPENING HEIGHT IS NOT
 THE SAME DIMENSION.REVISE AS REQUIRED.
  
 6-IF EDGE DISTANCE IS LESS THAN 3 1/2", THEN
 CALCULATE ANCHOR SPACING ACCORDING TO CHART SHOWN AT
 BOTTOM OFSHEET11 OF 14 OFACCORDION SHUTTERS
 #05-195.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712