2007-12-06 09:13:34 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | GAS PLAN REVIEW: | | REVISION DENIED: | | | | 1. SHEET P1 AND P2: WITH THE GAS PIPING MATERIAL BEING | | CHANGED TO CSST AND LONGEST LONGEST LENGTH BEING | | INCREASED TO 123' THE GAS PIPING SYSTEM IS SIZED | | INCORRECTLY IN THE INTERIOR PER TABLE *402.4(14). | | PLEASE REFERENCE THE RED LINE CORRECTIONS TO THESE | | SHEETS AND ATTACHED TABLES TO THESE COMMENTS REFLECTING | | THE NEEDED CHANGES ON THE RESUBMITTAL. | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|